34
Advanced functions
There may be a difference between the setpoint temperature and the temperature actually
measured in the room. This is generally due to the radiator installation conditions (location,
power/volume, room insulation, etc.). Calibration is used to adapt the thermostat setting to
the actual room conditions.
1 - Switch the radiator to manual mode at 20°C, and wait for a few hours.
2 - Measure the room temperature using a thermometer and calculate the difference
difference = measured temperature - setpoint temperature.
3 - Press and hold the
and
buttons at the same time for more than 3 seconds to
display
(Calibration).
4 - Press
,
will flash alternately with the currently set difference
.
5 - Set the new value using the
buttons (between -3°C and +3°C).
6 - Press
to exit.
Example: After several hours in manual mode with a setpoint temperature of 20°C, I measure
a room temperature of 18°C. So I set a difference of 18-20=-2.
X2
> 3 s
CALIBRATION
The radiator can save a maximum temperature (of between 19° C and 28° C), which the
settings cannot exceed. By default, it is set to 28° C.
1 - Press and hold the
and
buttons at the same time for more than 3 seconds to
display
.
2 - Press
to display
(Max Temperature).
3 - Press
,
will flash alternately with the currently set maximum temperature
.
4 - Set the new value using the
buttons (between 19°C and 28°C).
5 - Press
to exit.
Example: I want to prevent a setpoint temperature above 24°C from being set.
X4
> 3 s
MAXIMUM TEMPERATURE
a
cceSSing
the
advanced
functionS
Then press and hold these two buttons at the
same time for more than 3 seconds.
at the same time
min. 3 seconds
Press any button to activate the display.