[parameter 2/3
]
Press the Down key or Up key to set
the acceptable high point and
acceptable low point of input voltage:
HLS:
High loss voltage in eco
mode(parameter 2) (the setting
range (par 3) is from +7V to
+24V of the nominal voltage).
Default=12V
LLS:
Low loss voltage in Line
mode (the setting range is from
-7V to -24V of the nominal
voltage). Default=-12V
06: ByPassEnable/Disable
Interface
Setting
[parameter 3
]
ENA:
Bypass mode enable.
DIS:
Bypass mode disable.
07: Bypass voltage range setting
Interface
Setting
[parameter 2/3
]
Press the Down key or Up key to set
the acceptable high point and
acceptable low point of input voltage:
HLS:
High loss voltage in Line
mode (the setting range is from
230Vac to 264Vac of the nominal
voltage).
Default=264Vac.
Parameter 3.
LLS:
Low loss voltage in Line
mode (the setting range is from
170Vac to 220Vac of the nominal
voltage).
Default=170Vac.
Parameter 3.