- 7 -
►
General characteristics
1
Hydraulic unit: Sound pressure level at (x) m from the appliance,
1.5m o
ff
the ground, open
fi
eld directionality 2 / Outdoor unit : Sound
pressure level at (x) m from the device, halfway between the ground
and top of the outdoor unit, open
fi
eld directionality 2.
2
The sound power level is a laboratory measurement of the emitted
sound power. It does not correspond to a measurement of the
perceived sound power.
3
Refrigerant R32 as per NF EN 378.1 standard.
4
Filling with refrigerant R32 is done at the factory.
5
Taking into account a possible additional
fi
ll of refrigerant R32
(see
"Additional
fi
lling", page 28
).
6
The announced thermal and acoustic performances are measured
with 7,5m length refrigerant lines.
Alfea Extensa A.I. R32 / INSTALLATION / 2114 - EN
Model
5
6
8
Rated heating performances
(outdoor temp. /
fl
ow temp.)
Heat output
+7°C/+35°C - Under
fl
oor heating system
kW
4.50
5.50
7.50
+7°C/+55 °C - Radiator
kW
4.50
5.50
7.00
Power consumption
+7°C/+35°C - Under
fl
oor heating system
kW
0.949
1.18
1.69
+7°C/+55°C - Radiator
kW
1.70
2.06
2.63
Coe
ffi
cient of Performance (COP) (+7°C/+35°C)
4.74
4.65
4.43
Electrical speci
fi
cations
Electrical voltage (50 Hz)
V
230
230
230
Maximum current for appliance
A
13
13
18
Maximum current of the Heating system electrical backup (according option)
A
13 (26.1)
13 (26.1)
13 (26.1)
Power of the Heating system electrical backup (according option)
kW
3 (6 kW option available)
Circulation pump actual power consumption
W
38
38
38
Maximum power consumed by the outdoor unit
W
3260
3260
4510
DHW electrical backup power
W
1500
1500
1500
Hydraulic Circuit
Maximum operating pressure heating / hot water tank
MPa (bar)
0.3 (3) / 1 (10)
0.3 (3) / 1 (10)
0.3 (3) / 1 (10)
Flow rate of the hydraulic circuit for
Δ
t=4°C (rated conditions)
l/h
970
1185
1616
Flow rate of the hydraulic circuit for
Δ
t=8°C (rated conditions)
l/h
485v
593
808
Miscellaneous
Weight of outdoor unit
Kg
39
39
42
Noise level at 5 m
1
(outdoor unit)
dB (A)
35
35
38
Sound power level in accordance with EN 12102
2
(outdoor unit)
dB (A)
57
57
60
Weight of hydraulic unit (empty / full of water)
Kg
145 / 363
145 / 363
145 / 363
Water capacity of the hydraulic unit / hot water tank
l
24 / 190
24 / 190
24 / 190
Noise level at 1 m
1
(hydraulic unit)
dB (A)
32
32
32
Sound power level in accordance with EN 12102
2
(hydraulic unit)
dB (A)
40
40
40
Heating system operating limits
Outdoor temperature min/max
°C
-20 / +35
-20 / +35
-20 / +35
Max. heating water
fl
ow temperature under
fl
oor heating
°C
45
45
45
Max. heating water
fl
ow temperature low temperature radiator
°C
52
52
52
Refrigeration circuit
Gas pipe diameters
Inches
1/2
1/2
1/2
Liquid Piping Diameters
Inches
1/4
1/4
1/4
Factory
fi
ll of refrigerant R32
3
g
970
970
1020
Maximum operating pressure
MPa (bar)
4.2 (42)
4.2 (42)
4.2 (42)
Minimum / Maximum length of pipes
4 / 6
m
3 / 15
3 / 15
3 / 15
Maximum length of pipes
5
/
Maximum level di
ff
erence
m
30 / 20
30 / 20