ATI Technologies C12-17 Скачать руководство пользователя страница 11

  

  

 

C

12-17 Combustible Gas Transmitter

 

 

12 

O&M Manual 
Rev-D 

 
 

 
 

Figure 7 - Sensor/Transmitter Connectors, Controls and Test Points (ATI-0143) 

 

TRANSMITTER ZERO 

 
 

 

The transmitter zero is adjusted with the sensor exposed to air that contains no combustible gas.  

Generally, the  easiest method  of  zeroing the transmitter is to make the adjustment  when  you know that 
the  area  is  free  of  combustibles.    Because  it  is  normally  necessary  to  check  the  area  with  a  portable 
combustible  detector  prior  to  removing  the  cover  from  the  transmitter,  the  absence  of  an  combustible 
gases or vapors can be verified fairly easily.   
 
 

The transmitter can also be set to zero using "zero air" available in cylinders.   Zero air cylinders 

and regulators are available from ATI or from specialty gas suppliers.  Connect the zero air cylinder to the 
calibration adapter and  adjust gas flow  to  500 cc/min.  When the  DVM stabilizes near  40mV, adjust the 
zero potentiometer until the DVM reads 40 ± 0.5 mv.   
 

 
NOTE:  If using the ATI receiver display when adjusting the transmitter zero, place the receiver in 

the "Inhibit" mode.  When in the inhibit mode, the blanking around zero is disabled so that 
the zero can be set accurately.

 

 

 

LEL Transmitter

S

P

A

N

Z

E

R

O

Содержание C12-17

Страница 1: ...nology Inc ATI UK Limited 6 Iron Bridge Drive Unit 1 2 Gatehead Business Park Collegeville PA 19426 Delph New Road Delph Phone 800 959 0299 Saddleworth OL3 5DE 610 917 0991 Phone 44 0 1457 873 318 Fax...

Страница 2: ...PARTS LIST 19 C12 17 TRANSMITTER WITH DISPLAY SPARE PARTS LIST 20 TABLE OF FIGURES FIGURE 1 TYPICAL SYSTEM DIAGRAM ATI 0145 4 FIGURE 2 COMBUSTIBLE GAS SENSOR TRANSMITTER DIMENSIONS ATI 046 6 FIGURE 3...

Страница 3: ...in two versions one containing an integral display and single alarm relay and a second that is a simple blind transmitter with no display or alarm functions Gas sensors are housed in a corrosion resi...

Страница 4: ...VDC Display Optional 2 digit LCD Alarm Single setpoint or Trouble with SPDT 1A 125VAC 1A 30VDC alarm relay Temperature Limits 40 to 70 C Sensor Materials 316 Stainless Steel Enclosure Blind Galvanized...

Страница 5: ...ion system is to be activated within a few days of installation the cap should be removed when installation is complete Otherwise leave the cap in place until the system is to be placed in service Be...

Страница 6: ...rs contain two heated elements One of these elements is active and will allow combustible gases or vapors to burn on its catalytic surface The other is passive and does not react to gases These two el...

Страница 7: ...ngle conductor for the common of both the power supply and the output signal Figure 3 shows typical connections to a power supply and a panel indicator running off the 4 20 mA signal from the C12 17 t...

Страница 8: ...losure are factory wired as shown below However sensors can be supplied with up to 25 feet of cable for remote mounting The wiring diagram for the extended cable version is also shown below Extended c...

Страница 9: ...calibration adapter can be used with this system to allow gas to be fed from a point near the transmitter as shown in Figure 6 Figure 5 Dual Condulet Connections ATI 0579 EXPLOSION PROOF JUNCTION BOX...

Страница 10: ...00 LEL also differs for each gas While methane gas standards can always be used for calibration the value that the transmitter is adjusted to will vary depending on what type of gas the system is mean...

Страница 11: ...from the transmitter the absence of an combustible gases or vapors can be verified fairly easily The transmitter can also be set to zero using zero air available in cylinders Zero air cylinders and r...

Страница 12: ...gas cylinder is marked with a concentration of 2 5 Methane the calculation would be V 40 mV 160 mV X 2 5 V O 5 V O 120 mV When the span has been set turn off the span gas flow and remove the calibrat...

Страница 13: ...the system is meant to detect a gas or vapor other than methane A 1 methane gas standard may still be used for calibration of combustible transmitters when used for other gases However the voltage tha...

Страница 14: ...ver If the sensor does not respond it should be replaced SENSOR REPLACEMENT Combustible gas sensors used in the C12 are warranted for 12 months and generally last 5 years or more in the absence of poi...

Страница 15: ...r local alarm of a high gas condition without the need for wiring back and forth to a remote alarm module In normal operation this version of the C12 17 will continuously display LEL on the integral l...

Страница 16: ...C12 17 Combustible Gas Transmitter 17 O M Manual Rev D Figure 9 Transmitter with Display Customer Connections ATI 0570...

Страница 17: ...is done using a magnet through the window of the display A magnetic screwdriver is supplied with the transmitter for this purpose If the relay activates and the gas concentration returns to normal sim...

Страница 18: ...ploded View ATI 0146 Part Number Description 00 1256 C12 17 Combustible Transmitter Module 80 0017 Explosion proof Enclosure 00 1198 D10 17 Combustible Sensor Assembly 92 0043 10 32 x 1 PHMS S S Phill...

Страница 19: ...oded View ATI 0571 Part Number Description 00 1258 C12 17 Combustible Transmitter Module with Display 80 0074 Explosion proof Enclosure for Display Module 00 1198 D10 17 Combustible Sensor Assembly 92...

Страница 20: ...improper storage or extended exposure to excessive gas concentrations Should inspection indicate that sensors have failed due to any of the above the warranty shall not apply The Manufacturer assumes...

Страница 21: ...DUCTS NH3 Ammonia CO Carbon Monoxide H2 Hydrogen NO Nitric Oxide O2 Oxygen CO Cl2 Phosgene Br2 Bromine Cl2 Chlorine ClO2 Chlorine Dioxide F2 Fluorine I2 Iodine HX Acid Gases C2H4O Ethylene Oxide C2H6O...

Отзывы: