Page 21
KN INSTALLATION AND OPERATION INSTRUCTIONS
Wiring single boiler
(continued)
7
Figure 19
Circulator wiring terminal strip (see Figure 15
for location) — Also see the wiring summary
illustrations on the next pages)
Figure 17
Wiring the boiler circulator using a circulator
relay (required for motors over 1/4 hp)
Figure 18
Wiring the boiler circulator using a relay or
starter (required for motors over 1/4 hp)
Circulator wiring
Postpurge circulator
•
The circulator shipped installed with the
K N-2
boiler cannot be used for system circulation.
It must
be used as supplied from the factory. It circulates water after
the boiler stops firing to prevent potential damage from
heat pocketing in the top of the heat exchanger.
• The postpurge circulator is factory-piped and pre-wired. Do
not change the usage, the wiring, the location or the piping.
Boiler circulator
• See section 5 of this manual for circulator piping.
• Figure 19 shows wiring of the Boiler circulator (or boiler/
system circulator) to the terminal strip of the
K N
electrical
connection board.
• DO NOT directly connect a circulator with a motor larger
than 1/4 hp. For larger motors, install a circulator relay or
motor contactor . Figures 17 and 18 show the correct ways
to install the boiler circulator using a relay or motor starter.
(KN-2 only)