www.atestgaz.pl
Output current value of the Gas Detector in
fault state
Output current
Emergency state
0.25 mA
Data memory error
0.75 mA
Program memory error
1.25 mA
Gas Detector measurement system error
1.75 mA
Gas Detector signal reference system error
2.25 mA
Short circuit in the sensing element supply line
2.75 mA
Break in the sensing element supply line
3.00 mA
Other critical failure
3.25 mA
Temperature measurement system error