www.atestgaz.pl
3
Input-output interfaces
3.1
Electric interface
Figure 2: Electric connections
No.
Name
Terminal
Description
1
SERVICE
Service port
A
Signal line A
B
Signal line B
GND
Negative supply pole. Both terminals „GND” are internally connected
2
PWR1
Supply port 1
GND
Negative supply pole (connected with GND of PWR1 port)
+
Positive supply pole (with serial diode)
3
PWR2
Supply port 2
GND
Negative supply pole (connected with GND of PWR1 port)
+
Positive supply pole (with serial diode)
4
R1 FAILURE
Failure relay output (negated)
COM
Common terminal of relay
NO
Normally open contact of relay
5
EBUS
External communication port
A
Signal line A
B
Signal line B
GND
Negative supply pole. Both terminals „GND” are internally connected
6
JCS
Internal communication bus port
A
Signal line A
B
Signal line B
GND
Negative supply pole. Both terminals „GND” are internally connected
Table 2: Electric interface description
Relay output
Function
R1 FAILURE
FAILURE
Sigma MOD DRV is in failure status or
isn't powered
Sigma MOD DRV isn't in failure status
Table 3: Operation of relays output
p. 6|10
User's Manual: POD-005-ENG R02
1
2
3
4
B
GND
A
GND
+
GND
+
COM NO
SERWIS
ZAS1
ZAS2
PK1 AWARIA
EBUS
JCS
A
GND
B
A
GND B
5
6
Содержание Sigma MOD DRV
Страница 1: ...POD 005 ENG R02 User Manual Control Unit Module Sigma MOD DRV Product code PW 027 A...