www.atestgaz.pl
2
Closed loop configuration
Cross-section of
a single cable
conductor
[mm
2
]
Alpa EcoTerm XT Gas Detector
System without backup battery supply
(U
IN
= 24 V)
System with backup battery supply
(U
IN(min)
= 20 V)
L1 [m]
L2 [m]
Quantity of detectors
L1 [m]
L2 [m]
Quantity of detectors
1
61
541
17
58
448
14
93
543
16
90
450
13
128
548
15
127
457
12
166
556
14
167
467
11
207
567
13
213
483
10
1,5
56
656
21
33
543
18
88
658
20
64
544
17
122
662
19
97
547
16
157
697
18
132
552
15
195
705
17
170
560
14
2,5
41
881
29
40
730
24
72
882
28
72
732
23
104
884
27
104
734
22
139
889
26
138
738
21
171
891
25
174
744
20
207
897
24
211
751
19
Table 4: Maximum quantity Alpa EcoTerm XT detectors – closed loop configuration
Atest-Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
p. 2/3
Appendix: PU-Z-106-ENG R01
•
Figure 2: Closed loop configuration for Alpa EcoTerm XT detectors
Control
unit
Detectors installed 30 m apart
Length L2 [m]
Length L1 [m]
Alpa
EcoTerm XT
Alpa
EcoTerm XT
Alpa
EcoTerm XT
L1 – distance T-connector of the first detector from the control unit
L2 – distance T-connector of the last detector from the control unit (also the length of loop return cable)