background image

DPA digital power amplifier

5

© 2018, ATEÏS, member of PAX ProAV Group

2

DPA digital power amplifier

The DPA  is  a  class-D  power  amplifier  with  extremely  low  power  consumption  (0.2W  per  channel)
during  standby  mode,  and  high  amplification  efficiency  of  90%.  A  four-step  DIP  switch  can  be
configured to enable/disable the function of standby  mode (power-save mode) when powered by  AC
mains;  to  request  the  LEDs  on  the  front  panel  to  comply  to  EN54-16;  and  to  enable/disable  the
battery monitoring.

The  amplifiers  are  powered  by  100  VAC  ~  240  VAC  50/60  Hz  or  48  VDC  battery  backup.  Each
model  has  the  line  inputs  with  individual  volume  gain,  status  LEDs  (power,  battery,  fault,  general
fault, overload and signal) on the front panel, and the DPA models can bridge two channels  to double
the power wattage.

2.1

Front panel

The  front  panel  of  DPA2500/DPA4125/DPA4250/DPA8060  is  identical,  except  the  number  of

channel is different. 

1. Power LED:

This LED lights up if the DPA is powered by AC mains power.

2. Battery LED:

This LED lights up if the DPA is powered by 48VDC power supply.

3. GEN-fault LED:

This LED lights up in yellow if one of the following situation occurs: output  over-current,  overheat,
AC power fault, battery power fault (the [BAT-MNT] DIP switch is set ON) and Lamp Test input is
short circuit. 

4. Overload LED:

The overload LED will blink as soon as  the output  power exceeds  the nominal value.  If this  LED
is  blinking,  check  whether the speaker is  connected correctly  and  still  in  good  condition,  also
check if the level of input signal is over 0 dB.

5. Channel fault LED: 

Содержание DPA2500

Страница 1: ...MODEL 2018 ATEÏS member of PAX ProAV Group User Manual Revision History v1 07 DIGITAL POWER AMPLIFIER DPA8060 DPA4125 DPA4250 DPA2500 ...

Страница 2: ...mplifier 5 5 2 1 2 1 Front panel 6 2 2 2 2 Rear panel 3 Hardware installation 8 8 3 1 3 1 Mounting 8 3 2 3 2 Connect to AC mains power 8 3 3 3 3 Connect to battery charger power sharing 9 3 4 3 4 Audio input audio output 9 3 5 3 5 Bridged output 4 Maintenance 11 5 Troubleshooting 12 6 Technical data 13 7 Standard and certification 15 8 Contact information 16 ...

Страница 3: ...nect the power cord only to an AC outlet of the type stated in this manual or as marked on the unit Otherwise fire and electrical shock hazard results When disconnecting the power cord from an AC outlet always grab the plug Never pull the cord A damaged power cord is a potential risk of fire and electrical shock hazard Avoid touching power plugs with wet hands Doing so is a potential electrical sh...

Страница 4: ...hazard To prevent the unit from falling down and causing personal injury and or property damage avoid installing or mounting the unit in unstable locations Leave enough space above and below the unit to provide good ventilation of the device If the airflow is not adequate the device will heat up inside and may cause a fire Operate the device in an environment with a free air temperature of between...

Страница 5: ...verload and signal on the front panel and the DPA models can bridge two channels to double the power wattage 2 1 Front panel The front panel of DPA2500 DPA4125 DPA4250 DPA8060 is identical except the number of channel is different 1 Power LED This LED lights up if the DPA is powered by AC mains power 2 Battery LED This LED lights up if the DPA is powered by 48VDC power supply 3 GEN fault LED This ...

Страница 6: ...hausts it from the rear panel Please make sure that these inlet holes are not obstructed 2 2 Rear panel DPA2500 DPA4125 DPA4250 DPA8060 The rear panel of DPA2500 DPA4125 DPA4250 DPA8060 is identical except the number of channel is different and the DPA8060 does not have Lamp input and Spare contact input 1 AC mains power socket Connect the mains AC power to this power socket 100 VAC 240 VAC 50 60 ...

Страница 7: ...is malfunction 4 Spare contact input DPA2500 4125 4250 Reserved for further usage 5 Channel 1 8 output Each channel delivers 60W DPA8060 125W DPA4125 250W DPA4250 500W DPA2500 and both EU and US types are available as different models EU type 100V 50V 4 ohm US type 70V 35V 4 ohm 6 Channel 1 8 inputs volume gain There is a balanced terminal and a gain control for each input channel 7 48VDC battery ...

Страница 8: ... heat generating devices like power supplies or power amplifiers 3 2 Connect to AC mains power 1 The DPA has a 100 VAC 240 VAC mains power supply please make sure the voltage is applicable for your country s main voltage 2 Connect the power cord to the DPA and plug it into the mains outlet 3 3 Connect to battery charger power sharing The connection diagram below is using the BOUTIQUE system for ex...

Страница 9: ...ection of amplifier output on DPA is varies with EU 100V 50V 4 ohm and US types 70V 35V 4 ohm 3 Connect and loudspeakers on BTQ VM8 controller 3 5 Bridged output Bridge the two channels of DPA amplifier such as 500W x 2 CH DPA2500 to 1000W x 1 CH or bridge each two channel of DPA8060 60W x 8 CH to 120W x 4 CH Please see the instruction as below 1 Connect an audio input on Channel 1 2 Bridge the au...

Страница 10: ...10 2018 ATEÏS member of PAX ProAV Group 4 Set the volume of gain knob on Channel 1 to the maximum volume ...

Страница 11: ...ir jet between the fins of the heat sinks User maintenance User maintenance should be done by qualified personnel only Dangerous mains voltages are present inside the units Unplug the main power supply before you do any maintenance Users can inspect if any broken connectors ground cable connections or loose screws on the outside of amplifier If any loose parts rattle around on the inside when the ...

Страница 12: ...ccurred See Technical Data Loudspeakers Outputs 2 Disconnect the speakers and check if the output is short 3 Check if the Service Request Contact output is open If yes the hardware is damaged broken AC power fault Battery power fault 1 Check the voltage is under the normal range AC mains 100 240VAC Battery supply 43 56VDC 2 Check if the Service Request Contact output is open If yes the hardware is...

Страница 13: ...70V 35V 4 ohm EU type 100V 50V 4 ohm Audio characteristics Frequency response 50 Hz 20 kHz 3 dB 0 dBu SNR 90 dB THD N 0 1 1 kHz Max input level 0 dBu Input impedance DPA2500 10K ohm DPA8060 DPA4125 DPA4250 12K ohm Crosstalk 70 dB 0 dBu gain Loudspeakers outputs 1 min at 40 C per CH Model Rated output power Rated load resistance DPA8060 60W 167 ohm 100V 82 ohm 70V 41 6 ohm 50V 20 ohm 35V DPA4125 12...

Страница 14: ...x 15 2 inch DPA2500 437 x 88 x 387 mm 17 2 x 3 5 x 15 2 inch DPA4250 14 5 kg 32 lbs DPA2500 16 kg 35 2 lbs Mounting 19 2U rack Color RAL 7016 Environmental Operating temperature 5 ºC 55 ºC 23 ºF 131 ºF Storage temperature 40 ºC 70 ºC 40 ºF 158 ºF Relative humidity 20 to 95 Air pressure 600 to 1100 hPa Heat dissipation DPA8060 767 BTU hr DPA4125 512 BTU hr DPA4250 1024 BTU hr DPA2500 1092 BTU hr ...

Страница 15: ...m is approved processing pending and complied to the following Europe Voice Alarm EN54 16 in process Europe CE EMI EN55032 2015 AC 2016 Class A Europe CE EMC EN61000 3 2 2014 EN61000 3 3 2013 EN55020 2007 A11 2011 Europe CE LVD EN60065 2014 in process USA Mass Notification Systems UL2572 pending USA Safety UL60065 pending ...

Страница 16: ...nion Way Worthing West Sussex BN14 8NW United Kingdom Tel 44 0 1903 215315 Fax 44 0 1903 215415 sales pentonuk co uk Russian Federation 115280 Moscow Leninskaya Sloboda str 26 bld 28 Business Center Slobodskoy office 122 Tel 7 495 803 3655 Fax 7 495 803 3655 info xavtel ru com ATEÏS Far East CORP Far East Asia ATEÏS Suisse SA Switzerland South East Europe No 60 Xinghua 2nd Rd Tanzi Taichung 427 Ta...