Leak Size Indicator 

 

The digital leak size indicator remains off normally but once a 
leak is detected, a number from 1-9 will be displayed for all 
HFC and HCFC refrigerants 

regardless of the sensitivity 

setting.  

 
The number will continue to increase or decrease depending 
on the amount of refrigerant sensed.  The maximum value will 
be displayed once the leak source has been located.  The 
table below can be used to approximate the size of leak: 

 

Maximum # displayed 

Leak Size (oz/yr) 

1 -3 

< 0.1 

4-6 

0.1 to 0.5 

7-9 >0.5 

 

 

Low Battery Indicator 

 

Replace the 4 AA Alkaline batteries when the red LED on the 
control panel is lit.  Follow battery installation instructions 
under 

Maintenance

 section. 

 

 
 

Audio Mute Function 

 
To silence or mute the audio beep and alarm signal, press the 
MUTE button.   To restore the audio sound, press the MUTE 
button again. (Note: a few seconds is required to restore 
sound if the mute button is pressed in rapid succession.) 

 

 

Adjusting Sensitivity Levels 

 

The Leak Detector will default to the NORM sensitivity level 
automatically once the unit comes out of the warm up cycle and 
the green LED will turn on.  
 
To change sensitivity levels, press the SENS once for HI 
sensitivity (red LED will turn on) and again for LO sensitivity 
(yellow LED will turn on). 

 

Leak Test Vial 

 

The leak detector comes with a Leak Test Vial that allows the 
user to make sure the detector is performing properly.  To test: 
 

1.  Remove the plastic seal cap on top of the Leak Test Vial 

by pulling it off (see fig. below).   

 
2.  Turn on the detector and allow the unit to complete the 

warm up cycle.  

 
3.  Place the sensor close to the small hole in the top of the 

Leak Test Vial. The beep rate should increase and the 
Digital Leak Size Indicator should display a number from 
4-6 indicating that the sensor and electronics are working 
properly.   

 
 
 
 
 
 
 
 
 
 
NOTE:  Always remember to replace plastic seal cap after 
leak test is completed.  Replace Test Vial when the green 
color is no longer visible. 
 

Remove 

Seal Cap 

To test 

Leak Test Vial 