6
II.
Hardware Installation
Connect OACIS Power In & Ground
Connect Analog Inputs
✓
Each Analog Input Channel has its own GND terminal.
✓
Signal Type Selection Switch (ONLY AI#5, 6) needs to be set properly per the
input signal type.
⚫
Allowable Signal Range with Input Setting
Voltage Input Current Input
±10V
4~20mA
AMP CBL
0 VDC
POWER CBL
OACIS-1XC
OUT +
SGA
+24 VDC
OUT -
ANALOG INPUT 1
ANALOG INPUT 2
TB
#1
FG
AI GND 1
AI GND 2
ANALOG IN 1~2 [V]
The power cable and AMP cable should be
separated each other.
✓
It is recommended to separate Power In
Connection from frequent Turn On and Off
circuit like Light Curtain
Over current or voltage input may cause severe damage to OACIS.
The Analog Inputs should be wired to OACIS AI channels directly not through
any other Terminal Blocks.