REQUIREMENTS FOR THE COMMONWEALTH OF 

MASSACHUSETTS

For all side wall horizontally vented gas fueled 

equipment installed in every dwelling, building or 

structure used in whole or in part for residential 

purposes, including those owned or operated by 

the Commonwealth and where the side wall ex

-

haust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, 

including but not limited to decks and porches, 

the following requirements shall be satisfied:

INSTALLATION OF CARBON 

MONOXIDE DETECTORS

At the time of installation of the side wall horizon

-

tal vented gas fueled equipment, the installing 

plumber or gas fitter shall observe that a hard 

wired carbon monoxide detector with an alarm 

and battery backup is installed on the floor level 

where the gas equipment is to be installed. In 

addition, the installing plumber or gas fitter shall 

observe that a battery operated or hard wired car

-

bon monoxide detector with an alarm is installed 

on each additional level of the dwelling, building or 

structure served by the side wall horizontal vented 

gas fueled equipment. It shall be the responsibility 

of the property owner to secure the services of 

qualified licensed professionals for the installation 

of hard wired carbon monoxide detectors.

In  the  event  that  the  side  wall  horizontally 

vented  gas  fueled  equipment  is  installed 

in a crawl space or an attic, the hard wired 

carbon  monoxide  detector  with  alarm  and 

battery back-up may be installed on the next 

adjacent floor level.

In  the  event  that  the  requirements  of  this 

subdivision  can  not  be  met  at  the  time  of 

completion  of  installation,  the  owner  shall 

have a period of thirty (30) days to comply with 

the above requirements; provided, however, 

that during said thirty (30) day period, a battery 

operated carbon monoxide detector with an 

alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required 

in accordance with the above provisions shall 

comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

SIGNAGE

A metal or plastic identification plate shall be 

permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust 

vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The 

sign shall read, in print size no less than 1/2" in 

size, "GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS".

INSPECTION

The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment 

shall not approve the installation unless, upon 

inspection,  the  inspector  observes  carbon 

monoxide detectors and signage installed in 

accordance with the provisions of 248 CMR 

5.08(2)(a) 1 through 4.

EXEMPTIONS: The  following  equipment  is 

exempt from 248 CMR 5.08(2)(a) 1 through 4:

•  The equipment listed in Chapter 10 entitled 

"Equipment Not Required To Be Vented" 

in the most current edition of NFPA 54 as 

adopted by the Board; and

•  Product Approved  side  wall  horizontally 

vented gas fueled equipment installed in a 

room or structure separate from the dwell

-

ing, building or structure used in whole or 

in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided 

When the manufacturer of Product Approved 

side wall horizontally vented gas equipment 

provides a venting system design or venting 

system components with the equipment, the 

instructions provided by the manufacturer for 

installation of the equipment and the venting 

system shall include:

•  Detailed instructions for the installation of 

the venting system design or the venting 

system components; and

•  A complete parts list for the venting system 

design or venting system.

Gas Equipment Venting System Not 

Provided

When  the  manufacturer  of  a  Product Ap

-

proved side wall horizontally vented gas fu

-

eled equipment does not provide the parts for 

venting the flue gases, but identifies "special 

venting systems", the following requirements 

shall be satisfied by the manufacturer:

•  The referenced "special venting system" in

-

structions shall be included with the appliance 

or equipment installation instructions; and

•  The "special venting systems" shall be Prod

-

uct Approved by the Board, and the instruc

-

tions for that system shall include a parts list 

and detailed installation instructions.

A  copy  of  all  installation  instructions  for  all 

Product Approved  side  wall  horizontally 

vented gas fueled equipment, all venting in

-

structions, all parts lists for venting instruc

-

tions,  and/or  all  venting  design  instructions 

shall remain with the appliance or equipment 

at the completion of the installation.

f i r e - p a r t s . c o m

Содержание Mission36TEN

Страница 1: ...ty damage personal injury or death AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incindie ou d explosion ou pour viter tout d...

Страница 2: ...e absence of these codes complies with the National Fuel Gas Code ANSIZ223 1 NFPA 54 State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Mas...

Страница 3: ...nce is not convertible for use with other gases unless a certified kit is used 2 For propane LP fireplace do not place propane LP supply tank s inside any structure Locate propane LP supply tank s out...

Страница 4: ...Shrink wrapped on cardboard Three 3 plastic bags containing lava rock pan and ember materials Rear Log Remove two plastic quick ties from around burner and grate Grate Stand Lift off of burner pan Ch...

Страница 5: ...closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psi 3 5 kPa For the purpose of input adjustment two...

Страница 6: ...5 WC 2 66 kPa 10 5 WC 2 66 kPa Orifice Size 30 29 GAS RATING PROPANE LP Max Input Rating 40 000 Btu Hr 45 000 Btu Hr Manifold Pressure 10 WC 2 49 kPa 10 WC 2 49 kPa Minimum Supply Pressure 11 WC 2 74...

Страница 7: ...e components in relation to fireplace opening Spacer 3 7 6 cm 1 1 2 3 8 cm Max B 6 15 2 cm A 12 22 9 cm Combustible Materials Header Figure 5 Mantel Clearances Side View Cross Section 1 1 2 3 8 cm Max...

Страница 8: ...eenthemate rial used and the face is caulked withanoncombustiblecaulking Figure 7 Rough Opening for Installing in Wall B C A Figure 8 Corner Installation Guidelines A B C D These Dimensions Allow for...

Страница 9: ...line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP CLEAR...

Страница 10: ...um height in accordance with the roof pitch and a minimum of 8 ft distance from a vertical wall or obstruction see Figure 11 page 11 A B type venting system must be connected to appliance for venting...

Страница 11: ...lation It is not recommended that this appliance be common vented with an existing gas burning appliance However if it becomes necessary to common vent this appliance the venting system must be sized...

Страница 12: ...l Receiver Extension Cord Ignition Module Plug NOTICE This appliance is equipped with a vent safety shutoff switch which will shut down the appliance in the case of aventingproblem Donotbypass thevent...

Страница 13: ...black iron gas line be routed from the gas source through a sediment trap shown in Figure 18 and into appliance Once connected through appliance a flexible gas line may be used for ease of installatio...

Страница 14: ...aks can be detected and corrected Donotuseanopenflameforleak testing and do not operate any appliance if a leak is detected INSTALLATION Continued Complete your gas installation by connect ing incomin...

Страница 15: ...on left of log 2 see Figure 25 Rest lower end of log 5 on grate as shown in Figure 26 6 Insert lower end of log 6 between first two grate fingers as shown in Figure 26 and position upper end of log 6...

Страница 16: ...upper end of log 5 into notch on top inner right of log 1 see Figure 29 Rest lower end of log 5 on middle grate finger as shown in Figure 30 6 Place log 6 into notch on top right of log 1 see Figure...

Страница 17: ...Between Appliance and Framing INSTALLING OPTIONAL GLASS DOOR ACCESSORY CAUTION Use only glass doors certified for use with this appliance Note Glass door may be heavy for some individuals If this is...

Страница 18: ...ide pins are free of frame rail see Figure 35 CAUTION Always operate the appliance with the doors ei ther fully opened or fully closed Operating the appliance with the doors partially open can re sult...

Страница 19: ...justment Screw FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A T...

Страница 20: ...o press ON OFF buttons on hand held remote control unit for up to 3 seconds to assure proper operation 2 Press the ON OFF button to turn burner on and off Check pilot flame pattern and burner flame pa...

Страница 21: ...n cleaning is complete Burner and controls should be cleaned with compressed air to remove dust dirt or lint Use a vacuum cleaner or small soft bristled brush to remove excess dust dirt or lint LOGS I...

Страница 22: ...at 1 800 655 2008 When calling please have your model and serial numbers of your fireplace ready You can also visit INNOVATIVE HEARTH PRODUCTS s web site at IHP US com IMPORTANT NOTICE Young children...

Страница 23: ...MEDY 1 Check to see if you have gas supply and that equipment shutoff valve is opened 2 Repeat lighting procedure several times to purge all air out of lines If after repeated attempts appliance does...

Страница 24: ...as low fuel supply 3 Gas leak See Warning statement at top of page 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas lea...

Страница 25: ...ed Brass Finish BD42P 42 Platinum Finish FIXED GLASS DOORS FD36 36 Black Finish FD36B 36 Brushed Brass Finish FD36P 36 Platinum Finish FD42 42 Black Finish FD42B 42 Brushed Brass Finish FD42P 42 Plati...

Страница 26: ...0858 F0860 AND F0862 MISSION42TEN CATALOG NUMBERS F0864 F0866 AND F0868 51 21 1 10 11 6 50 50 22 3 8 20 9 52 13 43 14 45 48 44 40 23 4 39 17 2 42 41 9 54 54 46 19 47 7 53 53 47 18 5 16 12 15 52 33 31...

Страница 27: ...1 25 11165 11165 Screw 10 x 5 8 2 26 107796 01 107796 02 Grate Assy 1 27 107742 01 107742 02 Burner Pan 1 28 107795 01 107831 01 Burner Tube 1 29 107748 01 107748 01 Burner Brckt 1 30 107985 01 107985...

Страница 28: ...1 108166 01 108171 01 Rear Refractory Herringbone 1 15 106661 01 107818 01 Bottom Rear Refractory Std Brick 1 108167 01 108172 01 Bottom Rear Refractory Herringbone 1 16 106662 01 107820 01 Bottom Fr...

Страница 29: ...AND F0862 KEY NO PART NO DESCRIPTION QTY 107999 01 Log Set 1 108724 01 Right Front 9 Split Log 1 2 901098 01 Rear Log 1 3 108720 01 Top Right Log 11 3 4 1 4 108721 01 Top Right Log 16 1 5 108722 01 T...

Страница 30: ...Log 11 1 2B 108839 01 Right Front Log 15 3 4 Round 1 3 108722 01 Top Left Log 13 1 2 Y Log 1 4 108838 01 Inside Top Left Log 15 3 4 Split 1 5 108721 01 Inside Top Right Log 16 1 6 108720 01 Top Right...

Страница 31: ...r acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal use The Pro...

Страница 32: ...arranty verification P126754 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications pricesandalsotodiscontinuecolors stylesandpr...

Отзывы: