A practical example of control unit setting is given below. 

Let us assume that there is an installation where our objective is to decrease the pump flow when the wind is between 10 Km/h and 20 Km/h 
and for winds faster than 20km/h, switching the unit off to prevent equipment damage and for safety reason. 

For this, there is one anemometer and one control unit, that unit will be set following below control parameters: 

-

 

Relay 1 will be disabled if wind is faster than 10km/h during 5 seconds of detection time.  

-

 

Relay 1 will be activated again when wind is slower than 8 Km/h during a release time longer than 5 seconds. 

-

 

Relay  2 will be disabled if wind is faster than 20 km/h during 5 seconds of detection time 

-

 

Relay 2 will be activated again when wind is slower than 15 km/h during a release time longer than 5 seconds.  

 

Note:

 In this case, both relays Will be set as NC. 

Control unit setting: 

Relay 3 

In this case, Relay 3 is not necessary, then, it will be set as out of order, thus both minimum and maximum configurable wind speed must be 
disabled.   

Procedure:  

-

 

Press the key with a circle.  

-

 

Press the arrows to reach 

Relay 3

 and press the circle´s key. 

-

 

Press the arrows until 

Definition working mode

 and press the circle´s key. 

-

 

Press the arrows to reach 

Wind speed minimum

 

and press the circle´s key. 

-

 

Press the arrows to reach

 

Operative 

and press the circle´s key. 

-

 

Press the arrows to reach 

Return 

and press the circle´s key. 

-

 

Press the arrows to reach 

Wind speed detection minimum

 and press the circle´s key. Type 0.0 and validate. 

-

 

Press the arrows to reach 

Wind speed release minimum 

and press the circle´s key. Type 0.1 and validate. 

-

 

Press the arrows to reach 

Definition working mode

 and press the circle´s key. 

-

 

Press the arrows to reach 

Wind speed maximum

 

and press the circle´s key. 

-

 

Press the arrows to reach 

Non operative

 and press the circle´s key. 

-

 

Press the arrows to reach 

Wind speed minimum

 

and press the circle´s key. 

-

 

Press the arrows to reach 

Non operative

 and press the circle´s key. 

  

 

Содержание 66577

Страница 1: ...ation operation and manteinance manual Manuel d installation d exploitation et maintenance Manuale di installazione operativo e manutenzione Manual de instala o opera o e manuten o EQUIPOS PARA FUENTE...

Страница 2: ...2 Fig 1 Fig 2...

Страница 3: ...E 4 1 3 OPERATION AND MAINTENANCE SAFETY 4 2 INSTALATION AND ASSEMBLY 4 2 1 SENSOR FASTNING AND LEVELLING 4 2 2 CONTROL UNIT FASTENING 5 2 3 WIRING DIAGRAM 5 2 4 SETTINGS 6 2 5 CONTROL UNIT OPERATION...

Страница 4: ...uld lose its warranty 1 3 OPERATION AND MAINTENANCE SAFETY Do not handle any component beyond the current manual instructions Don not handle the unit with wet hands The unit may only be handled by aut...

Страница 5: ...ctrical cabinet 2 3 WIRING DIAGRAM Connect the sensor to the terminals Y1 and Z1 The output will be connected to terminals 15 18 25 28 35 38 of the control unit depending on the relay whose operation...

Страница 6: ...ctivations in function of the wind detected by the anemometer NAVIGATION BY MENUS To navigate by the menus and realize the set up the control unit has three keys Keys to navigate through menus and mod...

Страница 7: ...Fountain units 7 SET UP MIN MAX WIND SPEED VALUES SET UP DELAY ON DETECTION AND OR ON RELEASE...

Страница 8: ...Relay 3 In this case Relay 3 is not necessary then it will be set as out of order thus both minimum and maximum configurable wind speed must be disabled Procedure Press the key with a circle Press th...

Страница 9: ...ows to reach Wind speed release maximum y and press the circle s key Type 8 0 and validate Adequate the deactivation detection strong wind value km h to the installation Press the arrows until Definit...

Страница 10: ...s the arrows to reach Definition working mode and press the circle s key Press the arrows to reach Release mode and select the Delayed option Press Return Press the arrows to reach Timer Release and p...

Страница 11: ...he wind speed reaches MAX2 10 km h our Relay 1 after a Td is deactivated Arrived to MAX3 20 km h and passed again a Td our Relay 2 will be deactivated When the speed will go down again under MAX2 our...

Страница 12: ...T 20 C Secure management of electrical and electronic waste Directive 2002 96 CE RAEE WEEE The unit s documentation must be read before use Danger of electric shocks 7 WARRANTY The unit s warranty is...

Отзывы: