Astraada DRV-22 inverters Communication protocol
72
Note: the blank in the above command is for illustration. The blank can not be added in the actual application unless the upper monitor can remove the blank by
themselves.
7.3.8.3 Example of continous writing command10H
Example 1: make the inverter whose address is 01H run forward at 10Hz. Refer to the instruction of 2000H and 0001. Set the address of “communication setting
frequency” is 2001H and 10Hz corresponds to 03E8H. See the table below.
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
Communication
control command
2000H
0001H:forward running
W/R
0002H:reverse running
0003H:forward jogging
0004H:reverse jogging
0005H:stop
0006H:coast to stop (emergency stop)
0007H:fault reset
0008H:jogging stop
The address of
communication
setting
2001H
Communication setting
frequency(0~Fmax(unit: 0.01Hz))
W/R
2002H
PID given, range(0~1000, 1000 corresponds
to100.0% )
Set P00.01 to 2 and P00.06 to 8.
The command sent to the inverter:
If the response message is as below:
Example 2: set the ACC time of 01H inverter as 10s and the DEC time as 20s
P00.11
ACC time 1
ACC time means the time needed if the inverter speeds
up from 0Hz to the Max. One (P00.03).
DEC time means the time needed if the inverter speeds
down from the Max. Output frequency to 0Hz (P00.03).
300 series inverters define four groups of ACC/DEC
time which can be selected by P05. The factory default
ACC/DEC time of the inverter is the first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
Depend
on
model
○
P00.12
DEC time 1
Depend
on
model
○
The corresponding address of P00.11 is 000B, the ACC time of 10s corresponds to 0064H, and the DEC time of 20s corresponds to 00C8H.
The command sent to the inverter:
If the response message is as below:
Note: The space between above commands is for instruction and there is no space between the commands during actual applications.
Common communication fault
Common communication faults: no response to the communication or the inverter returns abnormal fault.
The possible reason for no response to the communication:
Selecting wrong serial interface, for example, if the converter is COM1, selecting COM2 during the communication
The baud rate, digital bit, end bit and check bit are not the same with the in and - of RS485 are connected in reverse.
The 485 wire cap on the terminal board of the inverter is not plug in. the wire cap in behind the terminal arrangement.