25
Astra P-8 USER MANUAL
• ERRORS
Service required
Indication
:
Icon
Service
lights
constantly
Code
E001: Keyboard error
E002: IR communication error
E003: RF communication error
E004: MB communication error
E101: Fire error
E105: NTC2 error
E106: NTC3 error
E107: TC2 error
E108/109: Security switch or Pressure switch error
E110: NTC1 error
E111: TC1 error
E112: Pellets hopper overheating error
E115: General error
Cause:
The combustion
system has malfunctioned
and not operational.
Solution:
note the error
code and contact service
personnel.
Unspecific errors on the display
Indication
:
Icon
Service
lights
constantly
Unknown error is displayed on the screen
Cause:
Certain information
stored in the controller
is updated to the display
at startup moment, for
example, configuration data.
An unexpected error appears
on the screen when making
changes to the controller
settings.
Solution:
disconnect and
then reconnect the display
to reset it. If the problem
persists, contact service
personnel for support.
•
POWER SUPPLY FAILURE
During power supply failure, the
controller remains active due to internal
battery. Its internal status remains as it
was before the power failure. Internal
electronics runs in power saving mode
consuming very little amount of energy.
In case of the power supply failure, the
controller operates as follows:
Duration of power
supply failure
Operation before the
power supply failure
Operation after the power supply
failure
Less than 1 minute
Fire up phase
The controller continues normally.
Burning phase
The controller checks the flue gases
temperature and continues in the Burning
phase or restarts in the Fire Up phase.
OFF phase
Remains OFF.
More than 1
minute
Fire Up phase
The controller continues normally.
Burning phase
The controller checks the flue gases
temperature. If the flue gases
temperature dropped below some
setting (PAR56), the combustion system
restarts in the Fire Up phase, otherwise
it continues in the Burning phase.
OFF phase
Remains OFF.