Manual switching amplifier BS 805
Subject to technical change. 10/2017
Page 5 of 12
A.S.T. Angewandte SYSTEM-TECHNIK GmbH Dresden
5. Function of key T1
5.1. Code table
Element
Function
Code
Relay 1
Normal
from
appointed SP1
current less
211
Inverse
from
appointed SP1
current on
212
Hysterese 0,0mA
230
Hysterese 0,1mA
231
Hysterese 0,5mA
232
Hysterese 1,0mA
233
Hysterese 2,0mA
234
Relay 2
Normal
from
appointed SP2
current less
221
Inverse
from
appointed SP2
current on
222
Hysterese 0,0mA
240
Hysterese 0,1mA
241
Hysterese 0,5mA
242
Hysterese 1,0mA
243
Hysterese 2,0mA
244
Mandatory security
SP1
Switching attitude
SP1, SP2:
normal,
adjustment SP1: to
2mA over SP2,
fault: SP1 and SP2
current less and
output signal 2mA
251
Relay 1 and Relay 2
Reset at normal
255
Constant current
4,0
311
(mA)
12,0
312
20,0
313
+ 0,2
344
+ 0,5
343
+ 1,0
331
+ 2,0
332
+ 3,0
333
+ 4,0
334
+ 5,0
335
- 0,2
341
- 0,5
342
- 1,0
321
- 2,0
322
- 3,0
323
- 4,0
324
- 5,0
325
Example
16,8=12,0+5,0-0,2
“312”+”335
”+”341”
Current to reset
Back to measuring
mode
355 or
voltage
supply 10–
30VDC to
break
Element
Function
Code
Basic setting
(only BS 805.01
)
SP1: normal / without
hysteresis
SP2: normal / without
hysteresis
Strain gauge input
positive
Zero point -/+ 0,5
mV/V
555
Setup-protection
on
421
off
425
Strain gauge input
tension and
compression:
12mA=0mV/V
411
Negative
412
Positive
415
Test signal
on
422
off
423
>V< - limit stop left
∆16mA = ∆2,0mV/V 431
∆16mA = ∆1,5mV/V 432
∆16mA = ∆1,0mV/V 433
∆16mA = ∆2,5mV/V 435
>V< - limit stop right
∆16mA = ∆0,5mV/V 441
∆16mA = ∆1,0mV/V 442
∆16mA = ∆1,5mV/V 443
∆16mA = ∆0,83mV/V 445
>0< - adjusting range - 1,00 ... 0,00mV/V 451
- 0,75 ... +0,25mV/V 452
- 0,25 ... +0,75mV/V 453
0,00 ... +1,00mV/V 454
- 0,50 ... +0,50mV/V 455