11
Figure 8: Removing the EBP Front Cover
b)
On the bottom of the UPS front cover, remove the EBP cableknockout (see
Figure 9).
Figure 9: Removing the UPS Cable Knockout
c)
For the bottom (or only) EBP, remove the EBP cable knockout on the top
of the EBP front cover. See Figure 10 for the location of the top EBP cable
knockout.
d)
If you are installing more than one EBP, for each additional EBP remove
the EBP cable knockout on the top andbottom of the EBP front cover. See
Figure 10 for the location of the EBP cable knockouts.
CAUTION
A small amount of arcing may occur when connecting an EBP to the UPS.
This is normal and will not harm personnel. Insert the EBP cable into the
UPS battery connector quickly andfirmly.
e)
Plug the EBP cable(s) into the battery connector(s) as shown inFigure 10.
Up to four EBPS may be connected to the UPS. Connect black to black,.
Press the connector tightly together to ensure a proper connection.
To connect a second EBP, unclip the EBP connector onthe first EBP and pull
gently to extend the wiring to the EBP connector on the second EBP.
Repeat for any additional EBPs.