In ordinary delayed exit, the fail safe lock releases after the delay and remains released until the 
reset switch performs relocking.  In facilities where a threat exists from the outside, the question 
arises as to security against unauthorized entry after the release delay has expired.  It may be 

that the delayed exit cycle was initiated by mistake or as an act of vandalism.  It may take some 
time for a guard to arrive at the door to effect relocking and there is always some risk that 
security procedures will fail, despite the alarm signals, and the door will be left in this released 
state for an extended period of time. 
 

If a latch equipped panic bar is present on the door, some security will still exist against 
unauthorized entry.  However, many doors will employ a non latch equipped initiate device such 
as Securitron's Touch Sense Bar.  Also, any door which combines delayed exit with controlled 
entry (such as from a card reader) must depend only on the fail safe lock for entry security. 
 
The XDT can be set so that after the release delay expires, the fail safe lock remains 

engaged so long as the initiate device is not being pressed. When the initiate device is 
pressed, the lock immediately releases but resecures after the initiate device is no 
longer being pressed.  This preserves security from the outside.  To implement this, 
simply run a wire from terminal DC to terminal IN. This is the only use for terminal DC. 
We believe that this method of operation meets the intent of all exit delay codes but it is 

certainly possible that conservative safety officials might reject it, so we advise that specific 
approval be sought for this variation. 

 

8.  MAGNACARE

 LIFETIME REPLACEMENT WARRANTY 

For warranty information visit: www.securitron.com/en/site/securitron/About/MagnaCare-Warranty/ 
 

IN

RS

DC

 

Содержание SECURITRON XDT-12

Страница 1: ...evice is one that relies on no special knowledge for operation Securitron s Touch Sense Bar is an excellent choice for non fire rated doors A switch equipped fire rated panic bar is appropriate for fire rated doors Push buttons are also used but they may not be acceptable to local building officials on the grounds of requiring special knowledge Other initiate devices include mats curtain detectors...

Страница 2: ...inning of the release delay period until the door is relocked The remote alarm relay is intended to signal to a security office that a security violation is occurring at the door It ignores the nuisance delay period as this should be seen as a false alarm unless the delay becomes irrevocable It also continues to signal until the door is relocked correcting the security violation The remote alarm r...

Страница 3: ... with the local authority 3 3 UNIFORM BUILDING CODE NUISANCE DELAY Required and must be set at 2 seconds RELEASE DELAY 15 seconds only RELOCKING Must be manual and must be located at the door This is generally interpreted to mean that a doorswitch can t be used for relocking A keyswitch is typical POWER The door must release when power to it is cut off The door must also release if power to the sm...

Страница 4: ...local authorities may require a 45 second delayed BOCA relocking The standard XDT board does not support this Contact the factory to order a modified board with the 45 second feature See section 3 4 for a description of BOCA relocking 5 POWER Two versions of the XDT exist which operate respectively on 12 or 24 VDC Voltage can vary from 10 to 20 and must be filtered or regulated Pulsating DC transf...

Страница 5: ...ke 2 wire component packed with the XDT board It is installed in parallel with the fail safe lock and its function is to absorb the inductive kickback which is generated when the lock is switched off If the MOV is omitted electronic noise from the lock may interfere with proper operation of the board and relay life will be shortened If you are used Securitron s Magnalock in the installation the MO...

Страница 6: ...D TO BP THE LOCK WILL RELEASE AND ALL ALARMS WILL BE SUPPRESSED USE WITH AN ALTERNATE SWITCH ALLOWS RELEASE OF THE LOCK FOR A PERIOD OF TIME USE OF A MOMENTARY SWITCH RELEASES THE LOCK FOR 5 SECONDS TO PERMIT AUTHORIZED USE OF THE DOOR NO DC 7 2 BYPASS FUNCTION The optional bypass function has two purposes door release for extended periods and authorized entry or exit through the door Release for ...

Страница 7: ...S BP FE IN RS DC The free egress mode differs from the bypass mode as follows When the door is bypassed the fail safe lock is released so that both entry and exit is freely possible Also during bypass mode the board performs no monitoring functions In the free egress mode the lock remains secure so that entry is blocked but egress without alarm signaling occurs immediately when the initiate device...

Страница 8: ...equipped initiate device such as Securitron s Touch Sense Bar Also any door which combines delayed exit with controlled entry such as from a card reader must depend only on the fail safe lock for entry security The XDT can be set so that after the release delay expires the fail safe lock remains engaged so long as the initiate device is not being pressed When the initiate device is pressed the loc...

Отзывы: