Assa Abloy SECURITRON XDT-12 Скачать руководство пользователя страница 6

 

 

 

PN# 500-14900

 

 

Page 6 

Rev. D, 06/11 

7.  OPTIONAL FUNCTIONS 
The following optional functions are not necessary to meet delayed exit safety codes but may be 
implemented as desired to increase the utility of the application. 

 
7.1  LOCK STATUS REPORTING 
The LS input is for optional lock (or door) status reporting.  Note that when the XDT is delivered, 
the LS terminal is jumpered to the "+" terminal.  In this mode, the board interprets the lock as 
being secure so no reporting occurs, and the board can be used for normal delayed exit. 

 
To implement lock status reporting, a lock status switch, door switch or positive voltage signal 
should be connected to LS so that +V is present on LS when the lock or door is secure.  If the 
lock or door stops reporting secure when the door has not been released by the board, the 
remote alarm relay will switch 5 seconds later and remain switched until LS again reV.  
The purpose for the 5 second delay is to allow a door to reclose and again report secure after 

legitimate use.  If any function of the XDT board has released the door, the LS input will be 
ignored until the board has relocked the door.  This feature allows use of the XDT board to 
perform exit delay and yet also report on propped doors or forced doors. 
 

FIG. 3:  OPTIONAL LOCK STATUS AND BYPASS FUNCTIONS 

NO

NC

C1

C2

C3

+

LS

BP

FE

IN

RS

NC

NC

NO

WHEN DOOR OR LOCK STATUS SWITCH
COV TO "LS", THE DOOR IS
CONSIDERED SECURE.  IF THE SWITCH
OPENS WHEN THE DOOR SHOULD BE
SECURE, THE REMOTE ALARM RELAY 
WILL SIGNAL AFTER A 5 SECOND DELAY AND REMAIN IN THIS 
STATE UNTIL THE SWITCH CLOSES AGAIN.  THE WHITE WIRE OF 
A SECURITRON "S" MAGNALOCK CAN CONNECT DIRECTLY TO 
"LS".

WHEN +V IS CLOSED TO "BP", THE LOCK WILL RELEASE 
AND ALL ALARMS WILL BE SUPPRESSED.  USE WITH AN 
ALTERNATE SWITCH ALLOWS RELEASE OF THE LOCK
FOR A PERIOD OF TIME.  USE OF A
MOMENTARY SWITCH RELEASES THE LOCK
FOR 5 SECONDS TO
PERMIT AUTHORIZED
USE OF THE DOOR.

NO

DC

 

7.2  BYPASS FUNCTION 
The optional bypass function has two purposes:  door release for extended periods and 
authorized entry or exit through the door.  Release for extended periods is usually implemented 
on a time schedule.  A door may be released all day and put into delayed exit mode at night for 
security.  To accomplish this, +V is simply switched into the BP terminal by a time clock or other 

alternate action switch.  When the BP input is recV, the lock is released and all other 
functions of the board are suppressed.  The initiate switch will not start nuisance or release 
delay and lock status monitoring is suppressed since, during bypass, the lock is not supposed to 
be secure.  The two alarm relays will remain in their normal states. 
 
For authorized door use, a momentary switch connects between BP and +V.  When the switch 

closes, the door releases.  When the switch reopens, the door remains released for 5 seconds.  
This is called an "off delay" function.  When the BP terminal is used in this manner with a 
momentary switch, timed authorized entry or exit can be performed. 
 
A typical application for the bypass function is the use of a double momentary keyswitch such as 

Securitron's model MK with MKS second switch.  When turned in one direction, the MK will 
perform relocking after a delayed exit event.  When turned in the other direction, the MK will 
perform bypass so that an authorized person will be able to release the door for 5 seconds for 
immediate egress without creating any alarm.  In similar fashion, a momentary keyswitch can 
operate the bypass function from the exterior of the door for authorized timed entry. 

Содержание SECURITRON XDT-12

Страница 1: ...evice is one that relies on no special knowledge for operation Securitron s Touch Sense Bar is an excellent choice for non fire rated doors A switch equipped fire rated panic bar is appropriate for fire rated doors Push buttons are also used but they may not be acceptable to local building officials on the grounds of requiring special knowledge Other initiate devices include mats curtain detectors...

Страница 2: ...inning of the release delay period until the door is relocked The remote alarm relay is intended to signal to a security office that a security violation is occurring at the door It ignores the nuisance delay period as this should be seen as a false alarm unless the delay becomes irrevocable It also continues to signal until the door is relocked correcting the security violation The remote alarm r...

Страница 3: ... with the local authority 3 3 UNIFORM BUILDING CODE NUISANCE DELAY Required and must be set at 2 seconds RELEASE DELAY 15 seconds only RELOCKING Must be manual and must be located at the door This is generally interpreted to mean that a doorswitch can t be used for relocking A keyswitch is typical POWER The door must release when power to it is cut off The door must also release if power to the sm...

Страница 4: ...local authorities may require a 45 second delayed BOCA relocking The standard XDT board does not support this Contact the factory to order a modified board with the 45 second feature See section 3 4 for a description of BOCA relocking 5 POWER Two versions of the XDT exist which operate respectively on 12 or 24 VDC Voltage can vary from 10 to 20 and must be filtered or regulated Pulsating DC transf...

Страница 5: ...ke 2 wire component packed with the XDT board It is installed in parallel with the fail safe lock and its function is to absorb the inductive kickback which is generated when the lock is switched off If the MOV is omitted electronic noise from the lock may interfere with proper operation of the board and relay life will be shortened If you are used Securitron s Magnalock in the installation the MO...

Страница 6: ...D TO BP THE LOCK WILL RELEASE AND ALL ALARMS WILL BE SUPPRESSED USE WITH AN ALTERNATE SWITCH ALLOWS RELEASE OF THE LOCK FOR A PERIOD OF TIME USE OF A MOMENTARY SWITCH RELEASES THE LOCK FOR 5 SECONDS TO PERMIT AUTHORIZED USE OF THE DOOR NO DC 7 2 BYPASS FUNCTION The optional bypass function has two purposes door release for extended periods and authorized entry or exit through the door Release for ...

Страница 7: ...S BP FE IN RS DC The free egress mode differs from the bypass mode as follows When the door is bypassed the fail safe lock is released so that both entry and exit is freely possible Also during bypass mode the board performs no monitoring functions In the free egress mode the lock remains secure so that entry is blocked but egress without alarm signaling occurs immediately when the initiate device...

Страница 8: ...equipped initiate device such as Securitron s Touch Sense Bar Also any door which combines delayed exit with controlled entry such as from a card reader must depend only on the fail safe lock for entry security The XDT can be set so that after the release delay expires the fail safe lock remains engaged so long as the initiate device is not being pressed When the initiate device is pressed the loc...

Отзывы: