PN# 500-15600

 

 

Page 2 

Rev. D, 03/11 

The relay has 2 amp contacts; the operation of the SP-1 is fail safe.  When the SP-1 receives 
power, its control relay automatically energizes.  It de-energizes when the plate is touched.  For 
applications releasing an electric lock, the following drawing (Figure 2) shows typical connections 

of sensor, power supply and both fail safe (secure when powered) or fail secure (released 
when powered) electric locks.  Note installation of the MOV in parallel with the electric lock.  The 
MOV is supplied loose with the SP-1.  It is a black or blue disk-like component with two bare 
wires for connection.  The MOV acts to suppress the inductive kickback from the lock which will 
greatly shorten the life of the relay contacts if not suppressed.  To work properly it should be 

spliced in as close to the electric lock as possible.  It has no polarity.  If, however, 
Securitron's Magnalock is used in the installation, the MOV is not necessary as the 
Magnalock is internally suppressed. 

 

The sensor operates on 12-24 volts DC and is normally powered by the same power supply that 
operates the electric lock.  When wiring power, polarity must be observed.  Note that the 
sensor draws 40 mA when "at rest" and 25 mA when it is releasing the lock. .  As an additional 

safety feature, the SP-1 includes a low voltage sensing circuit.  The unit will keep working 
normally if input voltage declines until it reaches roughly 9 volts.  At that point, the SP-1 will 
automatically act as if all power was removed.  If a lock is being controlled, it will release.  Input 
voltage could decline if the unit was being operated on batteries and the batteries were 
discharging or because of a fault in the power supply. 

 

When employing the cable to make electrical connections, never coil the gray cable within 
the white backbox
.  It must be pulled straight out.  A coiled cable in the white backbox will 
interfere with proper electronic operation of the unit. 

 

FIGURE 2:  SP-1 TYPICAL WIRING 

CABLE

RED (+ POWER)
BLACK (- POWER)

WHITE (RELAY COM1)
GREEN (RELAY N.C.1)

POWER SUPPLY

12-24  VDC

+

MOV

ELECTRIC

LOCK

CABLE

RED (+ POWER)
BLACK (- POWER)
BLUE (RELAY COM2)

ORANGE (RELAY N.O.2)

POWER SUPPLY

12-24 VDC

+

-

MOV

ELECTRIC

LOCK

NOTE 1: MOV NOT NEEDED IF SECURITRON MAGNALOCK USED

NOTE 2: POWER SUPPLY MUST ALWAYS CONNECT DIRECTLY TO

NOTE 3: INPUT POWER POLARITY MUST BE OBSERVED.

SENSOR.  OTHER CONTROL SWITCHES SHOULD BREAK OR PARALLEL RELAY CONTACTS.

WIRING FOR FAIL SAFE LOCK 

WIRING FOR FAIL SECURE LOCK 

 

3.1  DOUBLE BREAK WIRING 
Many installations include a controlled entry device such as a digital keypad or card reader.  
Such devices typically have a REX (request to exit) input.  

 

If the REX input alone is used for exiting a safety/reliability problem will exist.  If the entry 
device malfunctions, exit will not be possible and people may be trapped.  We therefore always 
recommend double break wiring which is supported by the SP-1 because of its two pole relay.  
The SP-1's NC contacts are used to break power to the fail safe electric lock while its NO 
contacts trip the REX input of the controlled entry device.  This releases the lock a second time, 
hence the term, "double break".  If the controlled entry device fails for any reason, direct exit is 

still possible.  This type of circuit works only with fail safe locks but these comprise the great 
majority of lock types used for safety related exit. 

Содержание Securitron SP-1

Страница 1: ...ew includes a spring that goes around the screw below the plate Do not lose this spring as its presence is necessary for proper operation It is not necessary to remove the top screw with the spring on it but to just loosen this screw and rotate the plate enough to access the mounting screw points Mount the unit to the wall using the supplied screws Note that there are two approaches to mounting Yo...

Страница 2: ...ne if the unit was being operated on batteries and the batteries were discharging or because of a fault in the power supply When employing the cable to make electrical connections never coil the gray cable within the white backbox It must be pulled straight out A coiled cable in the white backbox will interfere with proper electronic operation of the unit FIGURE 2 SP 1 TYPICAL WIRING CABLE RED POW...

Страница 3: ... some of the label with it When the backing has been removed you can edit the label copy by carefully removing portions of the message Use a knife tip to peel away the vinyl characters Then line up and press the label top carrier onto the plate Firmly rub all over the top carrier sheet to apply the vinyl lettering to the stainless plate and remove air bubbles Then slowly peel off the top carrier s...

Страница 4: ...e red and black wires it s possible that it s not getting into the sensor Check the connector block that plugs into the sensor circuit board for loose wires Finally it is possible that the connection from the sensor to the plate has come loose Review Figure 1 The ring terminal must go around the top mounting screw and the spring must be present around the screw PROBLEM The LED remains on constantl...

Отзывы: