Assa Abloy Securitron Shear Aligning Magnalock SAM Series Скачать руководство пользователя страница 20

Rev. A.4, 12/01

Page- iii

voltage will be dropped in the wires (1.6 volts) leaving 22.2 volts to operate the Magnalock.  This will cause a minor
reduction in holding force but in general, will be acceptable.

To calculate the wire resistance, you need to know the distance from the power supply to the Magnalock and the
gauge (thickness) of the wire.  The following chart shows wire resistance per 1000 ft (305 meters):

Wire Gauge

Resistance/1,000 ft

Wire Gauge

Resistance/1,000 ft

8 Gauge

.6 Ohms

16 Gauge

4.1 Ohms

10 Gauge

1.0 Ohms

18 Gauge

6.4 Ohms

12 Gauge

1.6 Ohms

20 Gauge

10.1 Ohms

14 Gauge

2.5 Ohms

22 Gauge

16.0 Ohms

Let's look at some other sample calculations.  Suppose a SAM operating at 24 volts is 1200 ft from its power supply
and we're using 20 gauge wire.  First, the total length of the power wires is 2400 ft.  

Remember that you combine

the wire lengths from the power supply to the lock and back to the power supply to get the total circuit wire
length.

  The wire resistance than becomes 2.4 X 10.1 Ohms which is 24.2 Ohms.  Adding this to the (24V) SAM

resistance of 140 Ohms yields a total resistance of 164.2 Ohms.  24.2 divided by 164.2 yields the percent drop in
the wires which is nearly 15%.  This is excessive.  The problem can be dealt with in 2 ways.  You can utilize 16
gauge wire which would reduce the drop to a more acceptable 6% range or you can provide extra voltage at the
power supply (sometimes the wiring is pre-existing).  For instance, Securitron 24 V power supplies are adjustable
from 24 to 28 volts.  If you set the power supply at 28 volts, for example, you would be supplying 14% overvoltage
which would compensate for the 15% voltage drop in the wires.  If the power supply is operating a number of locks,
those closer the supply will receive more voltage, but the SAM will accept up to 30% overvoltage without ill effects.

Note when you operate the SAM at 12V, it exhibits 

1/4th

 the resistance (35 Ohms) that it does at  24 V.  This

means that wire voltage drops are 4 times more significant in a 12 volt system than in a 24 volt system.  

In any job

that has wire runs long enough to be of concern, always use 24 volts.

  Note also that it's common to mount 2

Magnalocks on a double door and operate them as one lock (only 2 power wires).  In this case, the resistance of
the pair of locks is half the resistance of a single lock.  The SAM2’s are less of a concern because they draw a lot
less current (roughly 1/3 of the SAM).  The SAM-2-12 draws 125 mA which corresponds to a resistance of 96
Ohms.  The SAM2-24 draws 62 mA for a resistance of 355 Ohms.

In multiple lock jobs with a single power supply, the calculation of wiring voltage drops is more difficult.  So long as
you run a separate pair of power wires to each lock, the calculation is as simple as has been described above, but
if a common power wire is used in a loop structure, the locks powered by the single loop will have an increasingly
low combined resistance so that the loop wire resistance will become more significant to the point where the locks
don't receive enough voltage.  To find the combined resistance of multiple locks powered by a common wire, divide
the resistance of one lock by the number of locks.  For example, eight SAM’s operating at 24 volts would have a
combined resistance of 140 divided by 8 which is only 17.5 Ohms.  Another method is to calculate the current in
Amps in the wire and divide that into the circuit voltage.  Since each SAM operating at 24 volts draws .175 Amps,
eight would draw 1.4 Amps.  Dividing this into the same 24 volt input voltage yields the same 17.5 Ohm combined
resistance.

In general, you have to be cautious about using common wires for loads in long distance situations unless you're
very confident about your ability to calculate the correct configuration.  Bear in mind, however, that anytime you're
uncertain about the voltage drop in wiring, you can meter the voltage at the lock 

while it's connected

 and you will

be able to see if it's receiving adequate voltage.  If the lock is not connected when you make this measurement, the
result will be false as the circuit will not see any lock resistance to compare to the wire resistance.  You will read
the full input voltage.

PATENTS

Securitron’s Shear Aligning Magnalock is covered under U.S. patent #4,516,114 and
#6,007,119 with other US and international patents pending.

Содержание Securitron Shear Aligning Magnalock SAM Series

Страница 1: ...ions below SECTION 2 2 1 HOLLOW ALUMINUM DOOR FRAME MOUNTING Page 4 SECTION 2 2 2 HOLLOW METAL DOOR FRAME MOUNTING Page 4 SECTION 2 2 3 SOLID WOOD DOOR FRAME MOUNTING Page 5 SECTION 2 3 STRIKE PLATE M...

Страница 2: ...where the lock is distant from the power supply SECTION 3 5 SC SENSTAT OPTION Page 13 Read this section if you have a Senstat unit SAMSC SECTION 3 6 DOUBLE DOOR PROCEDURE FOR STATUS REPORTING Page 14...

Страница 3: ...port version with metric fasteners Product Specifications are Input voltage 12 or 24 VDC 30 overvoltage is acceptable undervoltage proportionately reduces holding force Current SAM 350 mA 12 VDC 175 m...

Страница 4: ...the door is tried and by not allowing the door to flex the risk of the door taking on a permanent bend is eliminated FIG 1 SHEAR ALIGNING MAGNALOCK ASSEMBLY SAM Bottom mounting is a last resort It is...

Страница 5: ...the door edge as possible when the lock is mounted on the top or bottom of the door Centering the position of the magnet body is more critical because there is not a lot of free width in the door fra...

Страница 6: ...door without encountering an obstacle such as a door adjustment screw that will interfere with mounting the strike Then three holes must be drilled on each end of the cut out following the template To...

Страница 7: ...be positioned close to the edge of the frame opposite from the hinges in the case of horizontal mounting to maintain security Also two holes must be drilled on each end of the cut out following the t...

Страница 8: ...he plate facing downwards Because of gravity and to maintain optimum operation two of the springs need to be changed in the strike assembly when it is mounted with the strike plate facing downwards Th...

Страница 9: ...on the magnet body Accurate centering is crucial Also two holes must be drilled on each end of the cut out following the template To actually mount the strike plate once you have prepared the cut out...

Страница 10: ...d to the door recess flat via four supplied flat head machine screws into the holes in that you have previously drilled and tapped Be sure to apply the supplied threadlock to all mounting machine scre...

Страница 11: ...so that the strike plate will be centered on the magnet body The template also shows where to drill pilot holes for the supplied 8 x 3 4 sheet metal screws that will affix the idle bracket to the ins...

Страница 12: ...eration The optimum gap is 1 10 but this is difficult to measure It is however exactly the height of the interference buttons on the strike plate so position yourself so you can visually look across t...

Страница 13: ...y do not show the normal characteristics of an electromagnetic or other inductive load Inductive kickback is suppressed so arcing across switch contacts need not be a concern This suppression also pro...

Страница 14: ...scent lamp in parallel with the lock so that the lamp would be illuminated when the lock is powered The lamp acts like a resistor and allows current recirculation which will greatly slow lock release...

Страница 15: ...200 FT 20 GA 26 GA 1500 FT 12 GA 18 GA 400 FT 18 GA 24 GA 3000 FT 10 GA 14 GA 3 5 SC SENSTAT OPTION Securitron s optional patented Senstat feature provides true lock status sensing and is available o...

Страница 16: ...hite and green wires will be open The orange wires are not used See Figure 5 FIG 5 DOUBLE DOOR WIRING WITH SENSTAT LOCKS SAM ONLY WHITE GREEN WHITE SC LOCK SC LOCKS ARE INTERWIRED AS SHOWN TO PROVIDE...

Страница 17: ...customer The replacement at SECURITRON s sole option may be the identical item or a newer unit which serves as a functional replacement In the event that the product type has become obsolete in SECURI...

Страница 18: ...uired The second possible cause is that the gap between the magnet body and strike plate has widened to the point that the magnet can no longer pull the strike plate in This can happen for example whe...

Страница 19: ...e edge of the door This is easily detectable by manually attempting to move the strike towards and away from the magnet body PROBLEM Apparent electronic noise interference with the access control syst...

Страница 20: ...wire runs long enough to be of concern always use 24 volts Note also that it s common to mount 2 Magnalocks on a double door and operate them as one lock only 2 power wires In this case the resistance...

Отзывы: