Assa Abloy Securitron Shear Aligning Magnalock SAM Series Скачать руководство пользователя страница 18

Rev. A.4, 12/01

Page- i

APPENDIX A

TROUBLESHOOTING

PROBLEM

-- No magnetic attraction between magnet and strike plate.

To verify no magnetic attraction, attempt to put a steel object like a paperclip or screwdriver against the magnet
surface (covering at least two bars of the magnet body).  It should adhere weakly.  If it falls away with no
adherence, you have no magnetic field.  To analyze the problem, first be sure the lock is being correctly powered
with DC voltage.  This includes connecting the power wires with correct polarity.  Positive must go to red and
negative to black.  If the SAM is wired in reverse polarity, it will not be damaged, but it will not operate.  If the unit
continues to appear dead, it must be electrically checked with an Ammeter.  It must be powered with the correct
input voltage and checked to see if it draws the specified current. If the unit meters correctly, it is putting out the
correct magnetic field and the problem must lie with the mounting alignment in the door (see next paragraph).

PROBLEM

-- The lock does not engage even though magnetic attraction is present.

SAM’s operate by pulling the strike plate against the magnet face when the door closes thereby seating conical
buttons on the strike into corresponding machined holes at either end of the magnet body.  If the buttons do not
seat, the lock will not hold and should be considered 

not engaged

.  There are three potential causes that can

produce a failure of the buttons to seat.  First the mounting alignment between the strike and the magnet body can
be off such that the buttons don’t line up with the conical machined holes in the T brackets.  To make this unlikely,
the diameter of the machined holes exceeds that of the buttons by 1/8” and this provides a margin for error in
mounting.  A misalignment greater than this either along the long axis of the lock or in the door closing direction will
cause engagement failure.  You can normally visually detect such an alignment problem.  Watch the strike closely
as you very slowly close the door.  You should see it “try” to move against the magnet body but note that the
buttons are acting as stand-offs because they are not lining up with the holes.  In some cases, this problem can be
corrected by adjusting the door but re-mounting the unit properly is often required.

The second possible cause is that the gap between the magnet body and strike plate has widened to the point that
the magnet can no longer pull the strike plate in.  This can happen, for example, when the lock is mounted at the
top of the door and the door sags downwards which increases the gap.  Note that the gap is supposed to be 1/10”
or the point at which the tops of the buttons just graze the magnet surface.  If the actual gap is significantly greater
than this, you have found the problem.  It can be corrected by either readjusting the hanging position of the door or
readjusting the level of the strike (by turning the two strike mounting screws) so as to reduce the gap to the correct
dimension.  The final possible cause is that the strike mounting hardware has somehow become frozen so that the
strike has lost its movement ability towards and away from the magnet body.  You can check this by trying the
move the strike by hand with the door open.  If it will not move, dismount it and clean and lubricate (or replace) the
mounting hardware.

PROBLEM

-- Reduced holding force.

This problem usually expresses itself in terms of being able to kick the door open or to open it with a shoulder.  The
cause is usually a build-up of dirt or other material between the magnet body and strike.  Check to see if anything is
interfering with a flat fit.  Even a small air gap can greatly reduce the holding force.  Another possibility is if you are
operating the lock on AC instead of DC or on half wave rectified DC (trans single diode).  Half wave
rectified DC is unacceptable; you must, at a minimum employ full wave rectified DC (trans bridge).

PROBLEM

-- The Senstat output does not report secure.

Because of the simplicity of Securitron's patented Senstat design, this is almost always a case of the lock status
sensor doing its job.  It is not reporting secure because a small obstruction or too stiffly mounted strike is causing
the Magnalock to hold at reduced force.  The problem is corrected by cleaning the surfaces of the magnet.  If this
doesn't work, you can verify function of the Senstat feature as follows.  Note that there are 2 thin vertical lines on
the magnet face that can be said to separate the core into 3 sections from left to right.  The Senstat output is
created by the strike establishing electrical contact between the leftmost and rightmost core segments.  With the
lock powered, use a pair of scissors and press the points respectively into the leftmost and rightmost core

Содержание Securitron Shear Aligning Magnalock SAM Series

Страница 1: ...ions below SECTION 2 2 1 HOLLOW ALUMINUM DOOR FRAME MOUNTING Page 4 SECTION 2 2 2 HOLLOW METAL DOOR FRAME MOUNTING Page 4 SECTION 2 2 3 SOLID WOOD DOOR FRAME MOUNTING Page 5 SECTION 2 3 STRIKE PLATE M...

Страница 2: ...where the lock is distant from the power supply SECTION 3 5 SC SENSTAT OPTION Page 13 Read this section if you have a Senstat unit SAMSC SECTION 3 6 DOUBLE DOOR PROCEDURE FOR STATUS REPORTING Page 14...

Страница 3: ...port version with metric fasteners Product Specifications are Input voltage 12 or 24 VDC 30 overvoltage is acceptable undervoltage proportionately reduces holding force Current SAM 350 mA 12 VDC 175 m...

Страница 4: ...the door is tried and by not allowing the door to flex the risk of the door taking on a permanent bend is eliminated FIG 1 SHEAR ALIGNING MAGNALOCK ASSEMBLY SAM Bottom mounting is a last resort It is...

Страница 5: ...the door edge as possible when the lock is mounted on the top or bottom of the door Centering the position of the magnet body is more critical because there is not a lot of free width in the door fra...

Страница 6: ...door without encountering an obstacle such as a door adjustment screw that will interfere with mounting the strike Then three holes must be drilled on each end of the cut out following the template To...

Страница 7: ...be positioned close to the edge of the frame opposite from the hinges in the case of horizontal mounting to maintain security Also two holes must be drilled on each end of the cut out following the t...

Страница 8: ...he plate facing downwards Because of gravity and to maintain optimum operation two of the springs need to be changed in the strike assembly when it is mounted with the strike plate facing downwards Th...

Страница 9: ...on the magnet body Accurate centering is crucial Also two holes must be drilled on each end of the cut out following the template To actually mount the strike plate once you have prepared the cut out...

Страница 10: ...d to the door recess flat via four supplied flat head machine screws into the holes in that you have previously drilled and tapped Be sure to apply the supplied threadlock to all mounting machine scre...

Страница 11: ...so that the strike plate will be centered on the magnet body The template also shows where to drill pilot holes for the supplied 8 x 3 4 sheet metal screws that will affix the idle bracket to the ins...

Страница 12: ...eration The optimum gap is 1 10 but this is difficult to measure It is however exactly the height of the interference buttons on the strike plate so position yourself so you can visually look across t...

Страница 13: ...y do not show the normal characteristics of an electromagnetic or other inductive load Inductive kickback is suppressed so arcing across switch contacts need not be a concern This suppression also pro...

Страница 14: ...scent lamp in parallel with the lock so that the lamp would be illuminated when the lock is powered The lamp acts like a resistor and allows current recirculation which will greatly slow lock release...

Страница 15: ...200 FT 20 GA 26 GA 1500 FT 12 GA 18 GA 400 FT 18 GA 24 GA 3000 FT 10 GA 14 GA 3 5 SC SENSTAT OPTION Securitron s optional patented Senstat feature provides true lock status sensing and is available o...

Страница 16: ...hite and green wires will be open The orange wires are not used See Figure 5 FIG 5 DOUBLE DOOR WIRING WITH SENSTAT LOCKS SAM ONLY WHITE GREEN WHITE SC LOCK SC LOCKS ARE INTERWIRED AS SHOWN TO PROVIDE...

Страница 17: ...customer The replacement at SECURITRON s sole option may be the identical item or a newer unit which serves as a functional replacement In the event that the product type has become obsolete in SECURI...

Страница 18: ...uired The second possible cause is that the gap between the magnet body and strike plate has widened to the point that the magnet can no longer pull the strike plate in This can happen for example whe...

Страница 19: ...e edge of the door This is easily detectable by manually attempting to move the strike towards and away from the magnet body PROBLEM Apparent electronic noise interference with the access control syst...

Страница 20: ...wire runs long enough to be of concern always use 24 volts Note also that it s common to mount 2 Magnalocks on a double door and operate them as one lock only 2 power wires In this case the resistance...

Отзывы: