Assa Abloy Securitron DK-26 Скачать руководство пользователя страница 16

 

 

 

PN# 500-16900

 

 

Page 15 

Rev. D, 12/11 

don’t violate egress building codes when employing a keypad on the inside of a door.  
Check with your local building or fire department. 
 

7.2  HARDWIRED CODE DISABLING 
This means making a switch connection to the CPU board which will cause valid codes to not be 
accepted.  The DK-26 has two terminals marked “HCD” and “UCD” which will respectively 
disable the Hard code and all User codes
.  Simply connect the SRC terminal to either of 
these terminals via an external switch and the respective codes will not function while the switch 

is closed.  Alternately if you 12V or +24V from the DC+ terminal to either of these 
terminals, it will have the same effect. 
 
The main reason for doing this is to support 
day/night operations
.  For example, you could 
allow all User codes to be active during the day 

but disable them at night by closing a switch 
between SRC and UCD.  The Hard code would be 
the only method of entry at night.  Or, you could 
have no Hard code programmed so that there 
would be no entry at night.  This could be done by 

timer controlled contacts from a timer such as 
Securitron’s model DT-7
.  It’s finally possible to flip the codes (Hard and all User) so that, for 
example, User codes are active only during the day and the Hard code is active only at night.  
An SPDT switch or relay is needed to do this as the drawing to the right shows.  Note that you 
won’t be able to use one of these disabling features (Hard or User) if you have implemented the 

door prop alarm (Section 6.4) or anti-tailgating (Section 7.4) features.  These reassign one of 
the terminals. 
 
7.3  ALARM SYSTEM SHUNTING 
The DK-26's lock control relay is of the double pole, double throw type.  Note that in all the 
other drawings in this manual, we show only one of the poles being used (C1, NC1 and NO1).  

The most common use for the second pole (C2, NC2 and NO2) is to shunt out an alarm 
system, which would be connected to the door when the DK-26 is being utilized.  The idea is 
that if the door opens without the DK-26 having been activated, an alarm signal should result.  
When the DK-26 is employed to open the door, the alarm signal should be shunted. 
 

The alarm system will be connected to a door switch or other detector at the door via two wires.  
You will need to determine if this “loop” is closed when the door is closed and opens when the 
door opens (the most common) or is open when the door is closed and closes when the door 
opens.  In the former case (closed when the door is closed), splice wires respectively from C2 
and NO2 into the wires from the detector or switch.  When the DK-26 operates, this connection 

will close preventing the alarm loop from opening (alarm condition).  In the latter case (open 
when the door is closed), cut one of the alarm loop wires and splice wires respectively from C2 
and NC2 into the ends of this wire.  When the DK-26 operates, this connection will open 
preventing the alarm loop from closing (alarm condition). 
 

FIG 8  WIRING TO SHUNT ALARM SYSTEM ON DOOR 

NC2

C2

NO2

DOOR
SWITCH

NC2

C2

NO2

DOOR
SWITCH

ALARM SIGNAL WHICH IS
CLOSED WHEN DOOR IS CLOSED;
OPENS TO ALARM

ALARM SIGNAL WHICH IS
OPEN WHEN DOOR IS CLOSED;
CLOSES TO ALARM

CUT EITHER
WIRE FROM
SWITCH

TO ALARM PANEL

TO ALARM PANEL

 

SRC REX UCD HCD

C

NC

NO

SPDT
SWITCH
OR RELAY

WITH THE CONTACTS
AS SHOWN, THE HARD
CODE IS DISABLED.
WHEN THEY SWITCH,
ALL USER CODES
WILL BE DISABLED.

 

Содержание Securitron DK-26

Страница 1: ...500 16900 Rev D 12 11 ASSA ABLOY the global leader in door opening solutions MODEL DK 26 DIGITAL KEYPAD SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS Securitron Magnalock Corp www securitron com Tel...

Страница 2: ...PROGRAMMING Page 8 SECTION 4 2 KEYPAD CHANGEABLE PROGRAMMING Page 9 SECTION 4 2 1 CHANGING THE USER AND PROG CODE FROM KEYPAD Page 10 SECTION 4 2 2 ADDING MULTIPLE USER CODES Page 10 SECTION 4 3 MAST...

Страница 3: ...eypad is pulled down firmly on to the screw A 3 8 10MM hole is then drilled for the cable After the cable has been pulled through the final screw secures the keypad to the wall Note finally that a bla...

Страница 4: ...which could cause the microprocessor to malfunction The MOV should be spliced into the lock power wires as close to the lock as possible Some DC electric locks have internal kickback protection includ...

Страница 5: ...om an AC transformer when the DK 26 is used Select a transformer of the same voltage as the lock 12 or 24 The CPU board converts the input AC to DC to operate the lock Make sure the capacity of the tr...

Страница 6: ...DK 26 and the lock The DK 26 does not require regulated power but certain specialized electric locks do so follow the rule of matching the power supply to the requirements of the lock DC locks come i...

Страница 7: ...to send power to the lock Figure 6 shows how to add external contacts for non timed remote release of the lock for both lock types FIG 6 ADDING EXTERNAL CONTACTS FOR FAIL SAFE AND FAIL SECURE LOCKS NC...

Страница 8: ...while its normally open contacts activate the DK 26 In effect the lock is released twice Note that the NC contacts are placed in the circuit before the DK 26 s lock control relay This is to aid possi...

Страница 9: ...programming in a situation where the end user is not likely to ever change the code or at least that changes would be rare Fixed programming can be used in lower security traffic control applications...

Страница 10: ...ixed code programming 4 2 KEYPAD CHANGEABLE PROGRAMMING In this application two codes are programmed into the DK 26 The first called the Program code acts as a password which allows changing the User...

Страница 11: ...ately by a new 2 7 digit User code Wait 5 seconds Note two red LED flashes for confirmation note rapid yellow flashing LED returns Press Bell key to terminate program mode or wait 30 seconds Re enter...

Страница 12: ...code The unit could not be put into program mode from the keypad The DK 26 however avoids this problem by rejecting any code that is a subset of another code in memory It signals this rejection by sh...

Страница 13: ...y by entering a User code and then secured all night by entering a User code again When you have enabled toggle mode activation of the REX input will successively energize and deenergize the lock cont...

Страница 14: ...inary operation must be via one or more User codes see Section 4 2 for programming Program the Hard code as your duress code see Section 4 1 Put the unit in program mode and enter 7 5 You will see the...

Страница 15: ...e simply by using the second pole of the lock control relay to shunt the door switch see Section 7 3 Generally you mount a Sonalert on the CPU board enclosure It will sound if the door is left open to...

Страница 16: ...e terminals 7 3 ALARM SYSTEM SHUNTING The DK 26 s lock control relay is of the double pole double throw type Note that in all the other drawings in this manual we show only one of the poles being used...

Страница 17: ...K 26 is often used with Securitron s Touch Sense Bar and magnetic lock The following drawing shows wiring for this particular configuration Note that the REX input is not used Since touching the bar o...

Страница 18: ...timer Two digit codes must be entered from 01 to 99 seconds Default is 5 seconds Entering 00 sets toggle mode APPENDIX B TROUBLESHOOTING Note first that the DK 26 replaces older Securitron keypads the...

Страница 19: ...nt through the PolySwitch trips it so that it clamps the current down to roughly 100 mA The PolySwitch will continue to clamp until all power is removed for about 5 seconds It is not enough to correct...

Страница 20: ...ace the keypad for full operation PROBLEM Unit beeps when keys are pressed but does not accept programming If the problem occurs on initial installation usually it s caused by misunderstanding the pro...

Страница 21: ...ry slot 45 You test the code by re entering 4 5 1 2 and the door opens because the sequence includes the real code 1 2 Later it will be noticed that the door is opening on 1 2 as this is such a simple...

Страница 22: ...a fail secure lock is operated from the same supply as the DK 26 When the lock is energized it may draw too much power for the power source This reduces the voltage and these voltage swings can crash...

Страница 23: ......

Отзывы: