Assa Abloy HES KS200-640 Скачать руководство пользователя страница 6

3085006.002 Rev. 3 

3. Installing the Lock 

1. SLIDE lock into cutout. 

NOTE:

  (Optional) Install RS485 termination jumper (KS210). 

(Optional) The DPS signal is closed when the handle is 
resting in its locked position.  The DPS circuit can be 
extended to include normally open DPS switches 
arranged in a series to monitor additional doors and 
panels. 

DPS Extension Cable 

DPS 

Switches 

(SPST-

NO): As 

Needed  

Switch #1        

(SPST-NO):              

Provided 

2. PERFORM the following to 

extend the DPS Circuit. 

a. REMOVE the DPS jumper. 
b. CONNECT the included 

DPS extension cable. 

c. CONNECT additional 

normally-open DPS 
switches as shown to 
monitor additional panels. 

3. CONNECT the female, 10-position Hirose

 

connector on the lock side interface cable 
to the KS200. 

4. ENSURE the lock side interface cable will 

properly protrude from the bottom of the 
KS200 
prior to attaching the rear bracket. ENSURE 
the wiring is not obstructing the mounting 
holes prior to securing the rear bracket. 

Содержание HES KS200-640

Страница 1: ...3085006 002 Rev 3 1 HES Inc Phoenix AZ 1 800 626 7590 www hesinnovations com KS200 640 KS210 640 Server Cabinet Lock Series Installation Instructions...

Страница 2: ...0 KS210 Current Consumption Model KS200 KS210 Input Voltage V DC 12V DC 24V DC Current Standby Avg 1 50 mA 40 mA Max Avg 2 100 mA 75 mA Peak3 130 mA 130 mA 1 Standby AVG RMS current draw without a car...

Страница 3: ...3085006 002 Rev 3 3 Operating Temperature 10C to 50C Holding Force 250 lbs...

Страница 4: ...iCLASS SEOS iCLASS SE ISO 15693 ICLASS ISO 14443A Mifare Mifare Plus Desfire SE Desfire EV1 EV2 NFC BLE NOTE Contact HID Global Technical Support at 1 866 607 7339 for additional configuration cards...

Страница 5: ...ent 6 or 7 pin SFIC cores 2 Preparing the Cabinet 1 LOCATE the 1 25 mm x 6 150 mm lock cutout on the door some doors may require modification 2 ENSURE power is available at the rack 3 RE USE the exist...

Страница 6: ...es SPST NO As Needed Switch 1 SPST NO Provided 2 PERFORM the following to extend the DPS Circuit a REMOVE the DPS jumper b CONNECT the included DPS extension cable c CONNECT additional normally open D...

Страница 7: ...that the lock is fully secured and flush to the mounting surface in order to depress tamper switch on back of device for correct operation NOTE If the tamper switch is not fully depressed the lock op...

Страница 8: ...1 Black 2 White 3 N A 4 N A 5 Red 6 Green 7 Orange 8 Brown 1 Gray 2 Yellow 3 Violet 4 Blue Function 12 VDC Reader Wiegand Data N A N A 12 VDC Reader Wiegand Data LED 12 24 VDC Lock Tamper DPS 12 24 V...

Страница 9: ...ires for Wiegand may be reused for OSDP However standard Wiegand cable may not meet RS485 twisted pair recommendations for maximum data transmission speed and distance Note For OSDP cable lengths grea...

Страница 10: ...3085006 002 Rev 3 10 Connector and Cable Diagram...

Страница 11: ...3085006 002 Rev 3 11 Server Cabinet Wiring Example...

Страница 12: ...esting the Lock with the Access Control System 1 TEST the lock with a known good credential to confirm it will open as desired when installed a PRESENT a credential known to the EAC b LIFT lever and T...

Страница 13: ...3085006 002 Rev 3 13 This page intentionally left blank...

Страница 14: ...D JQ6 ICLASSBTM Model KS210 Contains IC ID 2236B ICLASSBTM Canada Radio Certification This device complies with Industry Canada license exempt RSS standard s Operation is subject to the following two...

Отзывы: