Rev.  A.1, 10/99 

Page- 17 

"the system is working".  When the release switch is used, the indicator will go out which will 
prompt the individual to go through the door. 

If two indicators are present, one should be wired to the zone S terminal and the other to the 
zone E terminal.  This creates a lamp switching effect which provides more positive prompting 
for door use.  As an example, suppose a green and red indicator are present on a push button 
plate.  With the green indicator wired to the S terminal, green will annunciate the normal 
(secure) condition of the door.  This is the same as the panel green indication.  With the red 
indicator wired to the E terminal, it will come on whenever the lock is legally released from either 
the remote switch or the panel toggle.  This provides a strong prompt for use of the door.  If a 
release hold timer is in the installation (section 4.5), the red indicator will come on for the 
amount of time set on the timer.  Any time that both indicators are out will show that the door is 
in violation (the panel Sonalert will be on).  If indicators are present on more than one switch (an 
example would be an entry keyswitch and exit button) they should be wired in parallel so that 
the annunciation is the same from both sides of the door. 

4.8  AC LOCK CONTROL 

Many electric locks are intended for operation on 12 or 24 volts AC.  The panel, however, only 
operates on DC and cannot supply AC from its toggle switch control outputs.  Most electric locks 
which operate on AC will also operate on DC, so the installer should check this point.  If, 
however, the locks must operate on AC or on a voltage other than 12 or 24, this can only be 
done by using the panel to energize and deenergize relays which operate on the panel voltage.  
The relay contacts will then switch the "foreign" lock voltage from a second power supply.  This 
technique is the same that must be employed if the locks draw more than 1.5 Amps current. 

 

5.  OPTION WIRING 

5.1  SILENCE LATCH WIRING (OPTION "SL") 

FIG. 7:  FIELD INSTALLATION OF SILENCE LATCH 

 

A

-

COM. NEG.

COM

NC

NO

+

-

RELAY

PUSH BUTTON

L+

L-

COM

NO

SONALERT

+

-

PAN

E

L

 T

E

R

M

IN

AL

BREAK EXISTING CONNECTION BETWEEN A
AND SO.  INSTALL BUTTON AND RELAY
AS SHOWN.  SONALERT NEGATIVE ALREADY WIRED.

FIG. 5: FIELD INSTALLATION OF SILENCE LATCH

L+=IND
L-=INDICATOR -

 

Содержание ELECTRIC LOCK

Страница 1: ...ONS Page 4 Once you have determined the options present or desired on your panel read the corresponding section below to learn the function and operation of the supplied option SECTION 2 1 SILENCE LAT...

Страница 2: ...SECTION 4 8 AC LOCK CONTROL Page 17 This section explains use of the panel with AC locks SECTION 5 OPTION WIRING Page 17 The following 5 sections explain the field wiring that relates to the options...

Страница 3: ...sure F Flush mount pull box cover with back box R 19 Rack panel face A slope front desk mount is the standard panel enclosure SL Silence Latch PB Emergency all release for fail safe locks only AM Addi...

Страница 4: ...with a much longer operating life The lamp within the HT push button operates just as the toggle bat yellow indicator 1 4 MONITORING Each zone toggle switch has a bicolor LED with green and red inter...

Страница 5: ...f the keyswitch activates a release hold timer as is commonly done a long delay is not required The timer will shunt the panel violation condition allowing the door to reclose When the timer resecures...

Страница 6: ...n switch In normal operation the red indicator in the switch is off When the switch is pressed it cuts off all DC power to the locks releasing them the PB option works with fail safe locks only The re...

Страница 7: ...wer cannot be removed from the locks by the panel The KP2 and MK2 versions are for fail secure locks When they are in the bypass position power is removed from the panel boards so that the locks stay...

Страница 8: ...ION V OUT WHEN SWITCH OFF FAIL SECURE LOCK V OUT WHEN SWITCH OFF FAIL SECURE LOCK V OUT WHEN SWITCH OFF FAIL SECURE LOCK V OUT WHEN SWITCH OFF FAIL SECURE LOCK L2 TERMINALS 1 2 3 4 They constitute the...

Страница 9: ...tion condition of the zone is shunted While the lock is legally released toggle off bicolor off toggle bat yellow LED on the zone will not violate As the lock status input S terminals reports insecure...

Страница 10: ...ply supplies V to the toggle common and then when the spring loaded toggle is pressed V is input to the R terminal of the board which is used to reset the violation alarm function The red flying lead...

Страница 11: ...devices employed No lock or door status monitoring switch is used As the drawing shows lock power comes from the L terminal and the S terminal is connected to the power wire at the lock With this con...

Страница 12: ...MONITORING AND VIOLATION ALARM FUNCTION FAIL SAFE LOCK CLOSED WHEN SECURE LOCK OR DOOR STATUS SWITCH REMOTE RELEASE SWITCH A REMOTE RELEASE SWITCH IS ADDED SUCH AS CARD READER KEYPAD PUSH BUTTON KEYS...

Страница 13: ...witches are in series An example would be a card reader for entry and a push button for exit The SPDT contacts of each remote switch are connected in NC series as shown so that either switch can relea...

Страница 14: ...S SWITCH IS ADDED TO PROVIDE MONITORING AND VIOLATION ALARM FUNCTION LOCK CLOSED WHEN SECURE LOCK OR DOOR STATUS SWITCH A REMOTE RELEASE SWITCH IS ADDED SUCH AS CARD READER KEYPAD PUSH BUTTON KEYSWITC...

Страница 15: ...orts secure and the door is closed before the green indicator comes on In theory lock status can t report secure if the door is open However combining the 2 switches enhances security in case the lock...

Страница 16: ...ith a powered switching device at the door such as a card reader or digital keypad This is to keep the drawings simple and also recognizes the fact that powered devices such as card readers will often...

Страница 17: ...lease hold timer as it releases the lock and holds the release for an amount of time Such timers are also called off delay timers In selecting the timer the requirements are that it has an SPDT relay...

Страница 18: ...imer s NO contact blue This also inputs V to the E terminal thereby annunciating legal release at the panel The timer s NC contact green breaks V to one side of the lock door status switch insuring th...

Страница 19: ...rt will be on If indicators are present on more than one switch an example would be an entry keyswitch and exit button they should be wired in parallel so that the annunciation is the same from both s...

Страница 20: ...e the entire system should be connected to this black wire When the button is pressed all DC power will be broken which will immediately release all the locks Make sure you terminate the lock negative...

Страница 21: ...e rather than delayed exit mode We advise not using this option with delayed exit To simplify this process we advocate two different connection schemes which depend on whether the bypass function of t...

Страница 22: ...number of reasons for the particular wiring method in Figure 9 Note first the connection to terminal FE on the XDT board Inputting V to this terminal places the XDT board in free egress mode which mea...

Страница 23: ...elease switch is momentary The bypass input will release the lock without signalling any alarm for 5 seconds Use of the bypass input makes substantial changes in the entire wiring scheme The lock stat...

Страница 24: ...he panel s monitoring functions are altered from the ones discussed in the previous wiring scheme without bypass In the normal secure condition the main LED is green and no alarm sounds During the nui...

Страница 25: ...ors from the boards by clipping them off 5 4 SWITCH BYPASS WIRING OPTION KP1 OR MK1 FAIL SAFE LOCKS The option comes pre wired for whichever type of keyswitch has been chosen However if the panel has...

Страница 26: ...The keyswitch removes power from all the terminal boards This bypasses the ability of the toggles to release the locks The panel s monitoring capability will also be disabled but the purpose of the k...

Страница 27: ...zone toggle on each panel is up Either toggle can release the lock but the toggle that released the lock must be used to resecure it Note that this set up is well suited for momentary toggles Since t...

Страница 28: ...red in series with the button on the master panel Switch bypass must be implemented on each panel FIG 15 CONNECTIONS BETWEEN STANDARD BOARD AND SLAVE BOARD TO POWER SUPPLY SLAVE BOARD CONNECTS TO LOCA...

Страница 29: ...e to gain access to the disabled panel during that portion of the day To accomplish this each panel must be furnished with a DPDT alternate action keyswitch with contacts of sufficient capacity to han...

Страница 30: ...C NO DPDT KEYSWITCH ON PANEL 2 ALTERNATE ACTION COM NC NO COM NC NO COM CONNECTS TO TERMINALS ON ALL BOARDS PANEL 1 PANEL 2 WIRES MUST BE ABLE TO CARRY FULL LOAD OF INSTALLATION CONNECT TERMINALS BETW...

Страница 31: ...ows continued monitoring without alarm condition The toggle switch itself will illuminate yellow when the zone is disarmed Only certain of the panel options are usefull if the panel is used for monito...

Страница 32: ...customer The replacement at SECURITRON s sole option may be the identical item or a newer unit which serves as a functional replacement In the event that the product type has become obsolete in SECURI...

Отзывы: