16
Configuration
EN
Warning!
Danger due to faulty commissioning:
In order to ensure the safety of the
product, commissioning must be performed by a qualified person.
ASSA ABLOY
Sicherheitstechnik GmbH
offers training for qualification in the requisite skills.
Safety requirements during commissioning include:
· The owner has received a confirmation of approval for use from the inspection
authorities;
· Conformity of the products with the approval according to EltVTR.
· Mounting according to the installation manual;
· Testing of the unimpeded opening and closing function of the doors with the
escape route securing system deactivated;
· Bolting of the doors after activation of the escape route securing system.
· Allows the doors to be opened after actuation of the Emergency Open
push-button(s).
· The function must be tested when connected to fire alarm system.
· The commissioning must be documented.
ASSA ABLOY Sicherheitstechnik GmbH
offers a test log book for this purpose.
Initial commissioning
All devices are connected to the
Hi-O-Technology
™ bus for the initial commission-
ing, but are not configured yet. If the voltage supply is switched on, the system is
in plug and play mode and the devices work with the factory settings.
Interfaces for locking systems
cannot work with factory settings, because they must
be logically linked to the corresponding Emergency Open push-buttons. The
configuration must be completely finished before the
interfaces for locking systems
can be commissioned.
Any changes which are made necessitate re-configuration.
!
Interface for
locking systems
Commissioning