MP9800 Series
Access 600 Integrated Wiegand
with and without MELR Option (Electric Latch Retraction)
Installation Instructions
Multi-Point Lock
FM437 11/18
Copyright © 2018, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or
in part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
For installation assistance contact Corbin Russwin
1-800-543-3658 • [email protected]
IMPORTANT: Pin 7 must be tied to earth ground in the
access control panel. Failure to follow proper ESD safe
grounding procedures could lead to equipment failure.
MELR not evaluated for UL 294 compliance, CAN/ULC-S319-05 and BHMA A156.25
READER NEG - Black, 1
READER POS - Red, 2
DATA 1 - White, 3
DATA 0 - Green, 4
RX NO NC
(
/
) - Orange, 5
RX COM
(
) - Blue, 6
*
- Brown, 7
EGND
LED - Yellow, 8
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
Not Used
12/24VDC
H N G
- +
120 VAC
Input
Whit
e
(C
)
Gree
n
(
)
N
C
Access 600 Series
(-)
12VDC
(+)
DATA 1
DATA 0
RX
RX
Electronic Access
Control Panel
(By Others)
Use (
) for
NC
Fail Safe
Operation
Lock Relay
(
) Fail
NO
Secure
Operation
DPS
DPS
Bla
ck (Hot
)
Whit
e (Neutral)
Green
(Gn
d)
Door
Position Switch
12 Conductor
ElectroLynx Harness
From McKinney
QC12 Electric
Hinge From
McKinney
Lockbody
Power Supply
(By Others)
ULC-S319 compliance:
EAC power supply utilizing battery backup
(30 minutes operation) is required.
*Access 600 M812
Requires 12 or 24VDC
UL294 Listed, Power Limited
Power Supply (or UL603)
Access 600 M802
Access 600 M812
12VDC / 24VDC System:
• Reader Draw= 150mA
• Actuator Draw= 400mA
(inrush / 15mA continuous)
• Total System Draw = 550mA
• Reader Draw= 125mA
• Actuator Draw= 400mA
(inrush / 15mA continuous)
• Total System Draw = 525mA
12VDC System (MELR):
• Reader Draw = 150mA
• 12VDC MELR Module Draw =
850mA
• Total System Draw = 1 Amp
• Reader Draw = 125mA
• 12VDC MELR Module Draw=
850mA
• Total System Draw = 975mA
24VDC System (MELR):
• Reader Draw = 150mA
(Reader is always 12VDC)
• 12VDC MELR Module Draw =
700mA
• Total System Draw = 850mA
• Reader Draw = 125mA
• 12VDC MELR Module Draw =
700mA
• Total System Draw = 825mA
6
Wiring Diagram - Typical Access 600 Application (12/24VDC Lock)
Mode 1:
• LED wire not used = RED LED
”ON” when powered
NOTE: Standard Application Shown.
For Alternative Applications Contact
1-800-810-WIRE (9473)
*Reader Electronics Require 12 or
24VDC UL294 Listed, Power Limited
Power Supply (or UL603)