80-0180-339, Rev 2 

 

 

 

 

 

 

 

PS-SE Power Supply 

Owner’s Manual 

and 

Installation Instructions

 

 

 

Содержание ADAMS RITE PS-SE

Страница 1: ...1 80 0180 339 Rev 2 PS SE Power Supply Owner s Manual and Installation Instructions ...

Страница 2: ...2 80 0180 339 Rev 2 ...

Страница 3: ... Wire the PS SE to the Exit Devices 8 Install the Battery Backup System BBK SE 8 Wire the Automatic Door Interface Optional 10 Wire the Primary Power Connection 10 Descriptions Part Numbers and Measurements 11 Descriptions and Part Numbers 11 PS SE Value Readings 11 LED Configuration 11 Frequently Asked Questions 11 Troubleshooting 12 Approved Replacement Fuses 14 Connector Signal Descriptions 15 ...

Страница 4: ...ional mode is available allowing both retraction timers to activate in response to closure of either switch The PS SE is listed as an Exit Device Access Control System unit to UL305 and UL1012 requirements for power supplies and CAN CSA C22 2 Exit devices under the system control remain latched during a complete power failure but always allow free mechanical egress Configuring the PS SE CAUTION Da...

Страница 5: ...ngs Operation Input IN1 retracts Exit Device 1 Input IN2 retracts Exit Device 2 NOTE 2 The PS SE is factory preset for Single Input Sequential Operation 1 SET the desired operation mode using SW1 dip switch 1 on the PS SE Figure 2 Operation Mode Set the Hold Open Time NOTE The PS SE has two hold open timers 1 PERFORM the following to set the hold open times a SET the hold open time for Exit Device...

Страница 6: ...e hold open time for Exit Device 2 using SW1 dip switches 6 7 and 8 see Table 2 Solenoid Hold Time Settings for Exit Device 2 for settings and hold times and Figure 3 for hold time settings example Table 2 Solenoid Hold Time Settings for Exit Device 2 Dip Switch 2 sec 5 sec 10 sec 15 sec 20 sec 30 sec 45 sec 60 sec 6 OFF ON OFF ON OFF ON OFF ON 7 OFF OFF ON ON OFF OFF ON ON 8 OFF OFF OFF OFF ON ON...

Страница 7: ... NOTE 1 Closed relay contacts indicate No Alarm Condition NOTE 2 When a fire alarm occurs the controlled exit devices will immediately latch secure Exit devices remain latched during a fire alarm but always allow free mechanical egress NOTE 3 The maximum current through the fire alarm contacts is 120 mA at 24 VDC b CONNECT the fire alarm normally closed relay contacts to Positions 9 and 10 Fire of...

Страница 8: ...0 feet 14 AWG Figure 4 Exit Device Wiring Install the PS SE 1 INSTALL the PS SE close to the exit device door operated NOTE 1 Mounting holes are in diameter NOTE 2 Enclosure dimensions are 10 wide by 10 long by 4 high 2 FASTEN the PS SE securely to the wall using the mounting holes located on the back of the enclosure Install the Battery Backup System BBK SE 1 ORDER the BBK SE Battery Backup Syste...

Страница 9: ...gure 4 Location of Battery Backup System Figure 4 Location of the Battery Backup System NOTE The Adams Rite Battery Backup System circuit board has a short wiring harness to connect to the PS SE circuit board 4 CONNECT the orange connector of the wiring harness into the BATT BACKUP connector of the PS SE circuit board 5 WIRE the battery terminals of one battery to the and terminals on the BATT1 co...

Страница 10: ...h is fully retracted and open when the latch is extended 1 CONNECT the automatic door opener as shown in Figure 5 Automatic Door Interface Wiring Figure 5 Automatic Door Interface Wiring Wire the Primary Power Connection NOTE 1 An earth ground must be made to the PS SE enclosure and to the push bar NOTE 2 Terminal block J4 will accommodate up to 12 AWG wire for the 120 VAC power input 1 CONNECT th...

Страница 11: ...rviceable Slow Blow 0230004 HXP Power Supply PS SE Value Readings OUT1 and OUT2 when IN1 and IN2 are open 1 6 VDC OUT1 and OUT2 when IN1 and IN2 are closed 24 VDC unregulated LED Configuration NOTE If OUT1 and or OUT2 are on and IN1 and IN2 are open the board will need to be replaced Power to PS SE board Main Power LED Red and Output Power LED Green are on Frequently Asked Questions The exit devic...

Страница 12: ... for shorts in the wiring particularly around the exit device and hinge 2 CHECK for rods binding The exit device intermittently locks and unlocks 1 WHEN the exit device is activated AND the motor retracts AND the push bar releases THEN ENSURE the line voltage to the PS SE is 120 VAC acceptable range of 105 VAC to 135 VAC The bar loses calibration 1 Did you connect the green ground wire of the bar ...

Страница 13: ...input switches 1 CHECK to see if an open connection in the field wiring exists between the PS SE and control switch used for activating the latch solenoids 2 CHECK if there is a defective control switch on J3 1 and J3 2 or J3 3 and J3 4 OUT1 and OUT2 lights do light in response to input switches 1 CHECK to see if there is an open connection in the field wiring between the PS SE and the exit device...

Страница 14: ...er Supply has two user serviceable fuses F1 and F2 These fuses are described below F1 2 0 A 250V 5X20MM I 2C 92 705 SLOW BLOW Fuse F1 is in line with the transformer output 24VDC Littelfuse P N 213002 MXP Adams Rite P N 29 0672 F2 2 0 A 250V 5X20MM I 2C 92 705 SLOW BLOW Fuse F2 is in line with the transformer input 115 VAC Littelfuse P N 213002 MXP Adams Rite P N 29 0672 The Battery Backup System ...

Страница 15: ... Main Power neutral return input white conductor Green Earth Ground Connected to PS SE enclosure and to local earth ground and connected to SE bar and local earth ground SE Exit Device Configuration 1 PERFORM the calibration process for the installed exit device a ENSURE power is disconnected b IF printed circuit board assembly PCBA is being replaced THEN INSTALL new PCBA c DEPRESS the push bar fu...

Страница 16: ...800 232 7329 www adamsrite com Adams Rite is a brand associated with Hanchett Entry Systems Inc an ASSA ABLOY Group company Copyright 2017 Hanchett Entry Systems Inc All rights reserved Reproduction in whole or in part without the express written permission of Hanchett Entry Systems Inc is prohibited ...