background image

8

UVR-HE Series

HYDRAULIC CONNECTIONS

The pipe installation and connection operations can compromise the good operation of the system or worse, cause irreversible damage 

to the machine.

Therefore, these operations must only be carried out by specialised personnel.

CONDENSATE DISCHARGE CONNECTION
•  The condensate collection tank is equipped with a drain.
•  The path of the condensate discharge pipe must always have a slope towards the outside.
•  Make sure that the condensate drain pipe does not strain the discharge connection of the unit

CONNECTION OF ANY WATER POST-HEATING COIL
•  Any water post-heating coil is equipped with “male” connections with gas threading.
•  Tightening operations must be carefully carried out to avoid damaging the copper manifolds of the coil.
•  The pipe path must be designed so as not to create obstructions in the removal of the unit’s coil.
•  The water inlet and outlet must be such as to allow heat exchange in countercurrent: therefore, follow the indications of the WATER 

INLET and WATER OUTLET plates.

•  Provide a vent valve at the top and a drain valve at the bottom.
•  Fix the pipes properly outside the unit to avoid bearing their weight on the coil.
•  When the connection is made, push the outer rubber gasket well against the panel to avoid air leaks.
•  The insulation must be flush with the panel to avoid burns.
•  Provide, at regulation level, the shut-off of the pipe side coil with the fan off to prevent overheating inside the control unit with possible 

damage to some components.

•  Provide an antifreeze device.
•  Provide shut-off valves to isolate the coil from the rest of the circuit in case of extraordinary maintenance.
•  In case of installation in areas with particularly cold climates, drain the system for any long system downtime.

ELECTRICAL CONNECTIONS
•  To perform the electrical connections, refer to the RCE-EC control unit instruction manual.
•  Before starting any operation, make sure that the main power supply line is disconnected.
•  The electrical connections to the control panels must be carried out by specialised personnel according to the diagrams provided.
•  Make sure that the voltage and frequency indicated on the plate match those of the electrical connection line.
•  The use of adapters, multiple sockets and/or extensions is not allowed for the general power supply of the unit and accessories.
•  The installer must provide a power supply cut-out switch for the type of installation as close as possible to the unit, together with all 

that is necessary to protect the electrical parts.

•  Connect the unit to an effective earth socket, using the appropriate screw inserted in the unit itself.
•  Connect the unit and all its accessories with cables of suitable section for the power used and in compliance with local regulations. 

However, their size must be such that a voltage drop in the start-up phase is less than 3% of the nominal one.

•  MOD.: model
•  Port. mc/h: maximum air flow rate [m³/h]
•  P.ST. mm: maximum static pressure [mmH²O]

•  WATT: electric power absorbed by the fans [W]
•  VOLT: voltage [V]
•  AMP.: electric current of fans [A]
•  R.P.M.: number of revs of the fans
•  NR°: serial number
•  Unit construction date

PLATE

19/04/2018

RECOVERY UNIT

PORT. mc/h

WATT

VOLT

AMP.

NO.

P.ST.mm

R.P.M.

UVR   500 MF HE

650

2800

49907

47

2 x 120

230

2 x 0.84

Содержание AP20071

Страница 1: ...UVR HE SeriesINSTALLATION USE AND MAINTENANCE MANUAL Serie UVR M a n U a l e d U S o e d i i n S t a l l a z i o n e ...

Страница 2: ...l abilities ie persons without experience or knowledge unless they have been trained to use the equipment by a person responsible for their safety In particular it is necessary to prevent children from using the equipment Installation must be carried out by specialised personnel When installing use suitable accident prevention clothing such as goggles gloves etc as indicated by 686 89 EEC as amend...

Страница 3: ...overy unit without mixing while the heat of the stale room air is transferred to the cold outdoor fresh air The dry output of the aluminium exchange pack under standard conditions outdoor 0 C indoor 20 C with 0 of r h is always equal to or higher than 73 BACKWARD BLADES configurable on site FORWARD BLADES configurable on request The inlet outlet connections can be configured as shown in the diagra...

Страница 4: ...ONSTRUCTION FEATURES External galvanised steel sheet casing Condensate collection basin with condensate discharge Insulation with sound absorbing mattress placed on the lower panel Air inlet and outlet circular connections Class F7 supply side flat or pleated filters Class M6 supply side flat or pleated filters Single phase adjustable fans with backward blades UVR HE models up to 1200 Adjustable s...

Страница 5: ... 675 350 300 750 178 0 AP20085 UVR 3800 MF HE 1350 1350 1255 1410 675 350 325 700 188 0 AP20087 UVR 4500 MF HE 1350 1350 1255 1410 775 350 300 750 215 0 AP20089 UVR 5400 MF HE 1650 1650 1080 1710 775 350 285 1080 302 0 AP20091 UVR 6500 MF HE 1650 1650 1080 1710 775 450 355 940 302 0 AP20093 UVR 7100 MF HE 2150 2150 2210 1100 600 425 1300 500 0 AP20095 UVR 8500 MF HE 2150 2150 2210 1100 600 425 130...

Страница 6: ...ies recovery units can be fitted with optional PRE or POST heating devices such as water or electric heating coils These accessories are equipped with male female nipples for connection to the spiral duct and can be installed on the pressing and or suction openings of the units direct installation or inside the duct circuits ...

Страница 7: ...o interfere with the maintenance operations The air ducts must be sized according to the system and the aeraulic features of the unit fans An incorrect calculation of the ducts causes power loss or the intervention of any devices on the system We recommend using insulated channels to prevent condensation and to reduce the noise level We recommend placing an anti vibration joint between the ventila...

Страница 8: ...reeze device Provide shut off valves to isolate the coil from the rest of the circuit in case of extraordinary maintenance In case of installation in areas with particularly cold climates drain the system for any long system downtime ELECTRICAL CONNECTIONS To perform the electrical connections refer to the RCE EC control unit instruction manual Before starting any operation make sure that the main...

Страница 9: ...elow Only previously trained and qualified personnel can perform maintenance operations If the unit is to be disassembled protect your hands with work gloves All maintenance operations must be carried out with the machine resting on a horizontal plane sufficiently strong to withstand the weight of the machine NEVER when it is hung on walls or ceilings FILTER CLEANING AND MAINTENANCE INSPECTION We ...

Страница 10: ...he condensate collection tank The recovery units do not have moving parts so mechanical maintenance is not necessary Check that the plate exchanger is free from any type of impurity that could significantly lower its efficiency In the presence of dust or polluting substances it is necessary to provide adequate filters upstream of the recovery unit The appliances can be cleaned with compressed air ...

Страница 11: ... the circuit upstream and or downstream of the fan Damaged impeller Circuit check and reset of the original conditions Check the impeller and if necessary replace with original spare part Fresh air temperature too cold Outdoor air below 5 C Insertion of post heating devices Insufficient exchanger output Clogged exchanger fins Exchange pack cleaning Formation of frost on the exchanger Outdoor air b...

Страница 12: ...ve 2009 125 EC and Regulation no 1253 2014 Eco Design 2018 www fantinicosmi it FANTINI COSMI SPA Via dell Osio 6 20049 Caleppio di Settala MI Italia Tel 39 02 956821 I I Fax 39 02 95307006 I I info fantinicosmi it EN79857C ...

Отзывы: