Intelligent RS-485 and RS-422 Adaptors

 

 

5

Network Expansion 

Provided the cabling is correctly installed and terminated, RS-422 and 
RS-485 networks allow a maximum total cable length of 1200 metres, 
and can support a maximum load of 31 units plus the RS-422 or RS-
485 adaptor per network.  The easiest method of allowing more than 31 
units is to split the network into multiple sections, and run each section 
from its own adaptor on different serial ports on a single PC.  Typical 
PC’s have two serial ports, and multiple serial port expansion boards 
are available that provide two, four or eight additional serial ports.  
Remember that each section of the network can be up to 1200 metres 
long, and can support up to 31 units. 

Although we have had some users connect more than 31 units together 
in a single network without experiencing any problems, we do not 
recommend doing so. 

The Main Cabling Points Again! 

• 

The cable 

must

 be shielded twisted-pair computer data cable. 

• 

The twisted pairs of wire in the cable 

must

 be used as pairs. 

• 

The cable 

must

 be installed in one continuous run - no joins, 

junctions, taps or “T” connections are allowed. 

• 

The shield 

must

 be continuous, and connected to ground pins on the 

adaptor and each unit. 

• 

The cable 

must

 be terminated at each end. 

Provided you follow these instructions, you should have no problems 
running an RS-485 or RS-422 network up to the maximum of 1200 
metres and 31 units. 

Содержание Intelligent RS-422

Страница 1: ...rocomputers 14 Business Park Drive Notting Hill Victoria 3168 Australia Telephone 03 9578 7600 FAX 03 9578 7727 email solutions asp com au World Wide Web http www asp com au ASP Microcomputers is a di...

Страница 2: ......

Страница 3: ...S 485 and RS 422 Cabling 2 Cable Termination 3 Power Supplies 4 Network Expansion 5 The Main Cabling Points Again 5 Technical Information 6 RS 232 Connector 6 RS 485 Connector 6 RS 422 Connector 7 RJ...

Страница 4: ......

Страница 5: ...ocol to communicate with to the PC with the PC being the master Because RS 422 uses a separate pair of wires for data in each direction the Intelligent RS 422 adaptor is always able to both send and r...

Страница 6: ...minal Networked Portable BCR WandNet ASP RS 422 and RS 485 networks must be wired using a single run of shielded twisted pair cable daisy chained to each unit The cable must be looped to each unit in...

Страница 7: ...ch contain two or three twisted pairs of wires respectively are available in 100 metre and 500 metre rolls from A G Garlands Co Pty Ltd in Melbourne phone 03 9543 6411 with offices in other states Oth...

Страница 8: ...S cable for RS 485 installations and MCP 3S cable for RS 422 installations provides for a spare pair of wires In some installations it will be possible to use this spare pair to provide power over the...

Страница 9: ...erial ports Remember that each section of the network can be up to 1200 metres long and can support up to 31 units Although we have had some users connect more than 31 units together in a single netwo...

Страница 10: ...nt to make your own cable Pin Function DB 25 on PC DB 9 on PC 2 Data from PC 2 3 3 Data to PC 3 2 7 Signal Ground 7 5 Note that the Intelligent RS 485 and RS 422 Adaptors use only the transmit and rec...

Страница 11: ...Supply ve RJ 45 Connector The Intelligent RS 485 and RS 422 Adaptors also provide for the use of Category 3 or Category 5 twisted pair cable via an RJ 45 socket on the front panel This connector is wi...

Страница 12: ...RS 485 adaptor the RS 422 adaptor uses the same physical PCB but with different components fitted Jumper 1 if fitted connects unregulated DC voltage from the plug pack powering the Adaptor to the RS 4...

Страница 13: ...will be paid by ASP in the case of warranty repairs ASP welcomes suggestions for improvements to our products and documentation Year 2000 Statement The Intelligent RS 485 and RS 422 Adaptors are hard...

Отзывы: