background image

Display is Flashing “E5”
Possible Causes

Possible Remedies: (Unplug stove first when possible)

1. The stove automatically flashes "E5" when turned on

The T-stat sensor has come unplugged form the control board. 

Check to see if the sensor is unplugged. If the sensor is not 

unplugged then the sensor is damaged or has a short. If the 

sensor is damaged or has a short it will need to be replaced.

4. The hopper is out of Pellets.

Refill the hopper.

5.  The hopper safety switch has failed or hopper is open.

When operating the unit, be sure the hopper lid is closed so 

that the hopper safety switch will activate. Check the wires 

leading from the hopper safety switch to the control panel and 

auger motor for secure connections. Use a continuity tester to 

test the hopper safety switch; replace if necessary.

6. The auger shaft is jammed.

Start by emptying the hopper.  Then remove the auger 

motor by removing the auger pin. Remove the auger 

shaft inspection plate in the hopper so that you can see 

the  auger  shaft.    Gently  lift  the  auger  shaft  straight  up 

so that the end of the auger shaft comes up out of the 

bottom auger bushing.  Next, remove the two nuts that 

hold the top auger biscuit in.  Then rotate the bottom end 

of the auger shaft up towards you until you can lift the 

shaft out of the stove.  After you have removed the shaft, 

inspect it for bent flights, burrs, or broken welds.  Remove 

any foreign material that might have caused the jam.  

Also, check the auger tube for signs of damage such 

as burrs, rough spots, or grooves cut into the metal that 

could have caused a jam. 

7. The auger motor has failed.

Remove the auger motor from the auger shaft and try to run 

the unit. If the motor will turn the shaft is jammed on something. 

If the motor will not turn, the motor is bad.

Stove Feeds Pellets, But Will Not Ignite
Possible Causes

Possible Remedies: (Unplug stove first when possible)

1.  Air damper open too far for ignition.

Push the air damper in closer to the side of the stove for 

startup.  In some situations it may be necessary to have the 

damper completely closed for ignition to take place.  After 

there is a flame, the damper can then be adjusted for the 

desired feed setting.

2.  Blockage in igniter tube or inlet for igniter tube.

Find  the  igniter  housing  on  the  backside  of  the  firewall.  

The air intake hole is a small hole located on bottom side of 

the housing.  Make sure it is clear.  Also, look from the front 

of the stove to make sure there is not any debris around 

the igniter element inside of the igniter housing.

3.  The burnpot is not pushed completely to the rear of 

the firebox.

Make sure that the air intake collar on the burnpot is 

touching the rear wall of the firebox.

4.  Bad igniter element.

Put power directly to the igniter element.  Watch the tip 

of the igniter from the front of the stove.  After about 2 

minutes the tip should glow.  If it does not, the element is 

bad.

5.  The control board is not sending power to the igniter.

Check the voltage going to the igniter during startup.  It 

should be a full current.  If the voltage is lower than full 

current, check the wiring.  If the wiring checks out good, 

the board is bad.

22 

Содержание AP5660L

Страница 1: ...al building or fire officials about restrictions and installation inspection requirements in your area These Pellet Stove Room Heaters have been designed for use in the US and Canada and are suitable for mobile homes This unit is not intended to be used as a primary source of heat U S Environmental Protection Agency Certified to comply with 2015 particulate emissions standards United States Stove ...

Страница 2: ... pellets under these circumstances and a safety concern may arise from sparks or fumes entering the room Allow the stove to cool before performing any maintenance or cleaning Ashes must be disposed in a metal container with a tight fitting lid The closed container of ashes should be placed on a non combustible surface or on the ground well away from all combustible materials pending final disposal...

Страница 3: ...nd may cause damage to your heater Store your pellets in a dry place DO NOT store the fuel within the installation clearances of the unit or within the space required for refueling and ash removal Doing so could result in a house fire Do not over fire or use volatile fuels or combustibles doing so may cause a personal and property damage hazards SAFETY AND EPA COMPLIANCE Your pellet stove has been...

Страница 4: ...et stove has been tested and listed for installation in residential mobile home and alcove applications in accordance with the clearances given For safety reasons please adhere to the installation clearances and restrictions Any reduction in clearance to combustibles may only be done by means approved by a regulatory authority INSTALL ALL VENTS AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER When...

Страница 5: ...e Use no more than 180 degrees of elbows two 90 degree elbows or two 45 degree and one 90 degree elbow etc to maintain adequate draft IMPORTANCE OF PROPER DRAFT Draft is the force which moves air from the appliance up through the chimney The amount of draft in your chimney depends on the length of the chimney local geography nearby obstructions and other factors Too much draft may cause excessive ...

Страница 6: ...ust exhaust above the outside air inlet elevation The termination must not be located where it will become plugged by snow or other materials Do not terminate the venting into an existing steel or masonry chimney VENT TERMINATION CLEARANCES A Minimum 4 foot 1 22m clearance below or beside any door or window that opens B Minimum 1 foot 0 3m clearance above any door or window that opens C Minimum 3 ...

Страница 7: ...ath the pellet stove This pad should extend at least 6 152mm in front of the unit 3 Place the pellet stove approximately 15 381mm away from the interior wall 4 Locate the center of the exhaust pipe of your unit This point should then be extended to the interior wall of your house Once you have located the center point on the interior wall cut a 7 175mm diameter hole through the wall 5 The next ste...

Страница 8: ...bove the snowdrift line This same installation can be used if your heater is below ground level by simply adding the clean out section and vertical pipe inside until ground level is reached With this installation you have to be aware of the snowdrift line dead grass and leaves We recommend a 3ft 0 91m minimum vertical rise on the inside or outside of the house The through the wall installation is ...

Страница 9: ...Standard HUD CFR 3280 Part 24 Canadian installations require that the heater must be connected to a 3 or 4 inch factory built chimney conforming to CAN ULC S629 See the installation illustrations in this manual for minimum height above the roof The chimney installation must allow for removal in case of mobile home transportation especially outside connections You may contact your local building au...

Страница 10: ...tton changes the two digit display from degrees Celsius to degrees Fahrenheit D MODE M T BUTTON The Mode of the stove can be switched between manual and controlled with a Thermostat Separate LEDs to the left of the two digit display indicate the mode of operation Manual or T Stat The stove has to be in normal operation to be switched from Manual to T Stat mode Manual mode operates according to the...

Страница 11: ...e smoke and dirty glass They will create a need for more frequent maintenance You will have to empty the burn pot plus vacuum the entire system more often Poor quality pellets could damage the auger We cannot accept responsibility for damage due to poor quality pellet PRE START UP CHECK Remove burn pot making sure it is clean and none of the air holes are plugged Clean the firebox and then reinsta...

Страница 12: ...he best setting Consult your dealer if you need help NOTE On heat range 1 damper should be either completely closed or open no more than a of the way If damper is open to far it can cause the fire to go out OPENING DOOR If the door is opened while the stove is in operation it must be closed within 30 seconds or the stove will shut down If the stove shuts down push the On Off button to re start you...

Страница 13: ...e smoke and burn poorly Failure to clean and maintain this unit as indicated can result in poor performance and safety hazards Unplug your stove s electrical cord prior to removing the back panel or opening the exhaust system for any inspection cleaning or maintenance work Never perform any inspections cleaning or maintenance on a hot stove Do not operate stove with broken glass leakage of flue ga...

Страница 14: ...O NOT VACUUM HOT ASH CLEANING Heat Exchanger Tubes Your Pellet Stove Room Heater is designed with a built in heat exchanger tube cleaner This should be used every 2 or 3 days to remove ash build up on the heat exchanger tubes which can reduce heat transfer The handle for the heat exchanger tube cleaner is located in front of the vent tubes on front side of heater Slide the rod front to back severa...

Страница 15: ...CLEAN ANNUALLY 1 Remove the front glass by releasing the two latches attaching it to the unit They are located behind the right side panel 2 Remove the two side brick panels 3 Remove the two interior side panels FRONT CLEANOUTS 15 ...

Страница 16: ... This unit s door uses a 3 4 diameter rope gasket BLOWER MOTORS Clean the air holes on the motors of both the exhaust and distribution blowers annually Remove the exhaust blower from the exhaust duct and clean out the internal fan blades as part of your fall start up PAINTED SURFACES Painted surfaces may be wiped down with a damp cloth If scratches appear or you wish to renew your paint contact yo...

Страница 17: ...changer tubes see Heat Exchanger Cleaning section Make sure Pellet Stove is at room temperature before touching 3 Open the ash pan door remove the burn pot and empty into metal container 4 Vacuum to remove ashes from the firebox 5 BE SURE THAT ASHES ARE COOL TO THE TOUCH BEFORE VACUUMING Some vacuum cleaners may leak ash into the room Your vacuum cleaner should have a special filter or bag to elim...

Страница 18: ...amount of CO emitted out the chimney exposure to the gases in closed or confined areas can be dangerous Make sure your stove gaskets and chimney joints are in good working order and sealing properly to ensure unintended exposure It is recommended that you use both smoke and CO monitors in areas having the potential to generate CO STEP 1 Locate the Burn Pot Above are the decorative logs in there co...

Страница 19: ... Remedies Unplug stove first when possible 1 The convection blower is overheating and tripping the internal temperature shutoff Clean any dust off of the windings and fan blade If oiling the blower does not help the blower may be bad 2 The stove is being left on the highest setting for extended periods of time If operating the heater on the highest heat setting the room temperature could increase ...

Страница 20: ...es to the air switch 6 Combustion blower failure With the stove on check to see if the combustion blower is running If it is not you will need to check for power going to the combustion blower It should be a full current If there is power the blower is bad If there is not see 8 7 Control board not sending power to combustion blower If there is no current going to the combustion blower check all wi...

Страница 21: ...s bad 8 The Proof of Fire POF thermodisc has malfunctioned Temporarily bypass the POF thermodisc by disconnecting the two wires and connecting them with a short piece of wire Then plug the stove back up If the stove comes on and works you need to replace the POF thermodisc This is for testing only DO NOT LEAVE THE THERMODISC BYPASSED Your blowers will never shut off and if the fire went out the au...

Страница 22: ...r signs of damage such as burrs rough spots or grooves cut into the metal that could have caused a jam 7 The auger motor has failed Remove the auger motor from the auger shaft and try to run the unit If the motor will turn the shaft is jammed on something If the motor will not turn the motor is bad Stove Feeds Pellets But Will Not Ignite Possible Causes Possible Remedies Unplug stove first when po...

Страница 23: ... light comes on as designed Possible Causes Possible Remedies Unplug stove first when possible 1 High limit switch has tripped or is defective Wait for the stove to cool for about 30 45 minutes Locate the High Limit thermodisc and press the reset button on the back of it If the heater will not restart check the thermodisc to see if it s bad To test if the thermodisc is bad you can bypass it as des...

Страница 24: ...BLACK TIPS AFTER STOVE HAS BEEN ON FOR A WHILE THE BURNPOT OVERFILLS Possible Causes Possible Remedies Unplug stove first when possible 1 Stove or vent pipe is dirty which restricts airflow through the burnpot Follow all cleaning procedure in the maintenance section of the owner s manual 2 Vent pipe installed improperly Check to make sure the vent pipe has been installed according to the criteria ...

Страница 25: ...party components will void the warranty Bushing 891998 2 Blower Convection 80622 1 Gasket Convection Blower 88167 1 Pressure Switch 80549 1 Auger 891999 1 Ash Pan 891996 1 Igniter 80604 1 Gasket Exhaust Blower 88166 1 Switch Hi Temp 80601 1 Blower Exhaust 80602 1 Latch Door 891540 4 Gasket Door 88082 6 ft Motor Auger 80606 1 Micro Switch 80491 1 PCBA Board 80631 1 Switch Low Temp 80599 1 25 ...

Страница 26: ...e of third party components will void the warranty Housing PCBA Controller 892199 1 Brick Panel Right 88165 1 PCB Circuit Board 80676 1 Brick Panel Center 88163 1 Glass w Gasket Side 88162 2 Brick Panel Left 88164 1 Magnet 891995 4 Hearth Trim 892037 1 Exhaust Grill 69794 1 Decorative Log not shown 892064 1 Glass w Gasket Center 88161 1 Latch Ash Pan 891997 2 Burn Pot 891994 1 26 ...

Страница 27: ...Wiring Diagram CORRECT WRONG Insure the wires are connected to the bottom two prongs of the hopper switch as shown 27 ...

Страница 28: ...ruptions or fluctuations of electrical power supply to the appliance Non USSC venting components hearth components or other accessories used in conjunction with the appliance USSC s obligation under this warranty does not extend to the appliance s capability to heat the desired space Information is provided to assist the consumer and the dealer in selecting the proper appliance for the application ...

Страница 29: ...__________ Company ________________________________________ Telephone No ______________________________________ Stove Inspected Chimney Swept Items Replaced ____________________________________ Service 05 Date ________________________ Engineer Name _____________________________________ Company __________________________________________ Telephone No ______________________________________ Stove Insp...

Страница 30: ...ble de votre poêle et vous permettra de commander correctement toute pièce détachée Gardez ce manuel dans un lieu sûr pour toute consultation ultérieure Lorsque vous nous écrivez donnez toujours le numéro de modèle complet qui se trouve sur la plaque signalétique fixée sur l appareil de chauffage Lors de commandes de pièces détachées donnez toujours les informations suivantes telles qu illustrées ...

Страница 31: ...___________________________ Company__________________________________________ N de téléphone ___________________________________ Poêle Inspecté Cheminée Swept Articles Remplacé __________________________________ Date________________________ Ingénieur Nom _____________________________________ Service de 06 Refustratuib No ____________________________________ Company_________________________________...

Страница 32: ...et approuvées par écrit par USSC et ou 9 les interruptions ou fluctuations de l alimentation électrique de l appareil Composants d évacuation des gaz composants de l âtre ou accessoires utilisés avec l appareil et qui n ont pas été fournis par USSC Obligations de USSC en vertu de cette garantie ne couvrent pas la capacité de l appareil à chauffer l espace souhaité Des informations sont fournies pou...

Страница 33: ... COMMUNICATIONS CABLE CONSEIL D AFFICHAGE Vue arrière BROWN GRIS BLEU ROSE PURPLE BLANC BLACK SOURCE DE COURANT 120 Volts AC BLACK BLANC ORANGE BLEU RED IGNITOR E1 ALARME DE SURCHAUFFE E2 VIDE ALARME E3 OFF ALARME INCENDIE E4 Allumer FAIL ALARME E5 THERMOSTAT CAPTEUR ALARME CHAMBRE VENTILATEUR le ventilateur d évacuation CORRECT FAUX Assurez vous que les fils sont connectés aux deux broches inféri...

Страница 34: ...omposants tiers annulera la garantie PCB Circuit Imprimé 80676 1 Aimant 891995 4 Cendrier À Cendres 891997 2 Brûler Le Pot 891994 1 Pcba Boîtier Du Contrôleur 892199 1 Panneau De Brique Droite 88165 1 Panneau De Brique De Centre 88163 1 Verre Latéral Avec Joint 88162 2 Panneau De Brique Gauche 88164 1 Verre Central Avec Joint 88161 1 Garniture de foyer 892037 1 Grille d échappement 69794 1 Journal...

Страница 35: ... la garantie Bague 891998 2 Souffleur À Convection 80622 1 Interrupteur De Pression 80549 1 Tarière 891999 1 Cendrier 891996 1 Allumeur 80604 1 Souffleur Échappement 80602 1 Loquet Porte 891540 4 Joint De Porte 88082 6 ft Moteur De Tarière 80606 1 Micro Interrupteur 80491 1 Conseil PCBA 80631 1 Joint De Ventilateur De Convection 88167 1 Joint De Ventilateur D échappement 88166 1 Interrupteur De Te...

Страница 36: ...T FLAMME EST MOLLE DARK ET A TIPS NOIR APRÈS POELE A ÉTÉ SUR UN TOUT LA pot de combustion déborde CAUSES POSSIBLES SOLUTIONS POSSIBLES DÉBRANCHEZ RÉCHAUD PREMIER SI POSSIBLE 1 Tuyau de poêle ou de ventilation est sale ce qui limite le flux d air à travers le pot de combustion Suivez toutes les procédures de nettoyage dans la section maintenance du manuel du propriétaire 2 Vent tuyau installé incor...

Страница 37: ... et d essayer de faire fonctionner l unité Si le moteur va tourner l arbre est coincé sur quelque chose Si le moteur ne tourne pas le moteur est mauvais 3 Confiture Auger Commencez par vider la trémie Retirez ensuite le moteur de la vis en retirant la goupille de la tarière Retirer la plaque d inspection de l arbre de vis sans fin dans la trémie de sorte que vous pouvez voir l arbre de vis sans fi...

Страница 38: ...de combustion 4 élément allumeur Bad Mettez la puissance directement à l élément allumeur Regardez la pointe de l allumeur de l avant du poêle Après environ 2 minutes la pointe doit briller Dans le cas contraire l élément est mauvais 5 Le panneau de commande n envoie courant à l allumeur Vérifiez la tension va à l allumeur lors du démarrage Il devrait être un plein courant Si la tension est inféri...

Страница 39: ...curité de la trémie activera Vérifiez les fils menant de l interrupteur de sécurité de la trémie sur le panneau de commande et le moteur de la vis sans fin pour des connexions sécurisées Utilisez un testeur de continuité pour tester l interrupteur de sécurité de la trémie remplacer si nécessaire 6 L arbre de la vis sans fin est coincé Commencez par vider la trémie Retirez ensuite le moteur de la v...

Страница 40: ...e de la tarière puis retirer les deux vis qui maintiennent le support de la vis sur le tube de la vis sans fin Le support de la vis sans fin va maintenant pouvoir être retiré sous forme du tube de la tarière Retirez le deux boulons sur le côté du tube de vis sans fin pour enlever le palier inférieur de la vis sans fin Tirer la vis sans fin hors du tube pour libérer le blocage 7 Le moteur de la vis...

Страница 41: ...u commutateur d air 6 Combustion panne du ventilateur Avec le sur poêle vérifier pour voir si le ventilateur de combustion est en cours d exécution Dans le cas contraire vous devez vérifier pour pouvoir aller à la soufflerie de combustion Il devrait être un plein courant Si l alimentation le ventilateur est mauvais S il n y a pas voir 8 7 Le panneau de contrôle ne pas envoyer pouvoir de ventilateu...

Страница 42: ...IBLE 1 Le ventilateur de convection est en surchauffe et le déclenchement de l arrêt de la température interne Nettoyez toute la poussière hors de l enroulement et pale de ventilateur De huiler le ventilateur ne fonctionne pas le ventilateur peut être mauvais 2 Le poêle est laissé sur le réglage le plus élevé pour des périodes de temps prolongées Si le fonctionnement du dispositif de chauffage sur...

Страница 43: ...z vous que vos joints de cuisinière et les joints de cheminée sont en bon état de fonctionnement et correctement scellés pour assurer une exposition involontaire Il est recommandé d utiliser à la fois de la fumée et des moniteurs de CO dans les zones susceptibles de générer du CO ÉTAPE 1 Localisez le Burn Pot Ci dessus sont les journaux décoratifs dans leur emplacement correct Vos journaux décorat...

Страница 44: ...ière Il peut être souhaitable de pulvériser l intérieur de la trémie nettoyée avec une aérosol en silicone si votre poêle est dans une zone d humidité élevée Le système d échappement doit être soigneusement nettoyé CALENDRIER DE MAINTENANCE Utilisez les éléments suivants comme guide dans les conditions d utilisation moyennes Les joints autour du verre de porte et de porte doivent être inspectés et...

Страница 45: ...yez au besoin JOINTS DE PORTES ET DE VERRE Joints de portes et de verre Inspectez périodiquement les joints de la porte principale et des vitres La porte principale peut être retirée pour que les distributeurs effilochés cassés ou compactés soient remplacés par votre revendeur agréé La porte de cette unité utilise un joint de corde de 3 4 de diamètre MOTEURS SOUFFLEURS Nettoyez les trous d air sur...

Страница 46: ...VANT NETTOYANT ANNUELLEMENT 1 Retirez la vitre avant en libérant les deux loquets qui la fixent à l unité Ils sont situés derrière le panneau latéral droit 2 Retirez les deux panneaux de brique latérale 3 Retirez les deux panneaux latéraux intérieurs ...

Страница 47: ...SPIRER HOT ASH NETTOYAGE Tubes d échangeur thermique Votre poêle à granulés de chauffage de pièce est conçu avec un nettoyeur intégré de tubes d échangeur Il doit s utiliser tous les 2 ou 3 jours pour éliminer l accumulation de cendres sur les tubes de l échangeur thermique qui peut réduire le transfert de la chaleur La poignée pour le nettoyeur d échangeur thermique est située devant les tubes de...

Страница 48: ...ntretien Ne jamais effectuer des inspections le nettoyage ou la maintenance sur un poêle chaud Ne pas utiliser poêle avec du verre brisé des fuites de gaz de combustion peut entraîner SYSTÈME D ÉCHAPPEMENT Formation de créosote Quand tout le bois brûle lentement il produit du goudron et d autres vapeurs organiques qui se combinent à l humidité évacuée pour former la créosote Les vapeurs de créosot...

Страница 49: ... gamme thermique 1 l amortisseur doit être soit complètement fermé ou ouvert plus d un quart de la manière Si l amortisseur est ouvert à présent il peut provoquer le feu sortir OUVERTURE DE PORTE Si la porte est ouverte pendant que le poêle est en fonctionnement il doit être fermé dans les 30 secondes ou le poêle sera fermé Si le poêle éteint pousser le Marche Arrêt pour redémarrer votre poêle Le ...

Страница 50: ...ar la main ne sera pas augmenter la production de chaleur mais peut nuire gravement à la performance des poêles en générant beaucoup de fumée Ne pas brûler des granules humides La performance du poêle dépend fortement de la qualité de votre carburant en pastilles Évitez les marques de granulés qui présentent les caractéristiques suivantes 1 Amendes excédentaires Amendes est un terme décrivant des ...

Страница 51: ...rres passant du niveau 1 au niveau 5 de chauffage C TOUCHE C F La touche C F fait passer l affichage à deux chiffres des degrés Celsius aux degrés Fahrenheit et vice versa D TOUCHE MODE M T Le Mode de fonctionnement du poêle peut être Manuel ou commandé par un Thermostat Des diodes distinctes à gauche de l écran à deux chiffres indiquent le mode de fonctionnement Manuel ou T stat Le poêle doit êtr...

Страница 52: ...433mm 17 06 291mm 11 47po L installation en maison mobile doit être faite en conformité avec la norme de sécurité pour maison préfabriquée HUD CFR3280 Partie 24 Les installations au Canada nécessitent que le poêle soit connecté à une cheminée d usine en 3 ou 4 pouces conformément à CAN ULC S629 Consultez les illustrations d installations dans ce manuel pour la hauteur minimale au dessus du toit U ...

Страница 53: ...de nettoyage et tuyau vertical intérieur jusqu à ce que le niveau du sol est atteint Avec cette installation vous devez être conscient de la hauteur de la neige l herbe morte et les feuilles Nous recommandons un 0 91m élévation verticale minimale de 3 pieds à l intérieur ou à l extérieur de la maison L installation à travers le mur est l installation la moins chère et la plus simple Ne jamais mett...

Страница 54: ...tampon de foyer non combustible sous le poêle à granulés Ce coussin doit dépasser d au moins 6 152mm en face de l unité 3 Placez le poêle à granulés environ 15 381mm de loin de la paroi intérieure 4 Localisez le centre du tuyau d échappement de votre unité Ce point devrait ensuite être étendu à la paroi intérieure de votre maison Une fois que vous avez localisé le point central sur la paroi intéri...

Страница 55: ...é d une porte ou fenêtre qui ouvre B Le minimum 0 3 m 1 pieds dégagement au dessus d une porte ou fenêtre qui ouvre C Le minimum de 0 9 m 3 pieds de dégagement de tout bâtiment adjacent D Le minimum de 2 13 m 7 pieds l autorisation de tout grade lorsqu ils sont adjacents aux passages publics E 0 61m 2 pieds de dégagement E minimale au dessus toute l herbe les plantes ou d autres matériaux combusti...

Страница 56: ... pouvant causer des conditions malsaines ou nuisibles PELLET TYPE D ÉVENT Une liste UL de 3 pouces ou 4 pouces de type culot PL évent système d échappement doit être utilisé pour l installation et relié au connecteur du tuyau fourni à l arrière du poêle utiliser un 3 pouces à 4 pouces adaptateur pour 4 tuyau de pouce Connexion à l arrière du poêle doit être scellé à l aide Salut Temp RTV Utilisez ...

Страница 57: ...t d échappement Cela se applique aux appareils de chauffage autoportant et insérez chauffe PROTECTION DU SOL Ce chauffe eau doit avoir un protecteur de plancher non combustible protection de braises installé en dessous si le sol est un matériau combustible Si une plaquette de chaussée est utilisé il devrait être UL ou égale Le tampon de plancher ou une surface non combustible devraient être suffis...

Страница 58: ...age Stockez vos pastilles dans un endroit sec NE PAS stocker le carburant dans les dégagements d installation de l unité ou à l intérieur de l espace nécessaire pour le ravitaillement et l enlèvement des cendres Cela pourrait provoquer un incendie de maison Ne pas surcombustion ou utiliser des combustibles volatiles ou combustibles cela pourrait entraîner un danger de dégâts et blessures CONFORMIT...

Страница 59: ...aquant la porte N essayez pas de faire fonctionner l unité avec une vitre cassée Une vitre de remplacement peut être achetée chez votre revendeur u S Stove de chauffages pour pièce carburant aux granulés N essayez pas de nettoyer la vitre quand elle est encore chaude Pour nettoyer la vitre veuillez attendre que le poêle à granulés ait refroidi puis utilisez un chiffon en coton et du produit nettoy...

Страница 60: ...iment ou des pompiers au sujet des restrictions et des exigences d inspection de l installation dans votre région Ces poêles pour poêles à granules ont été conçus pour être utilisés aux États Unis et au Canada et conviennent aux maisons mobiles Cette unité n est pas destinée à être utilisée comme source principale de chaleur U S Environmental Protection Agency Certifié pour se conformer aux normes...

Отзывы: