7
MAINTENANCE CLEARANCES
Your furnace has recommended minimum maintenance clearance requirements. These clearances insure that
there is adequate room to preform maintenance and service your furnace. DO NOT store fuel within the speci
fi
ed
clearances. The clearances will change depending on what kits are installed with your furnace. See the tables
and diagram below to determine the clearances for your furnace.
Standard unit (no additional kits)
Dimension
Inch mm
H
Maintenance
Clearance (Front)
24
610
J
Maintenance Clearance (Left) 10
254
K
Maintenance
Clearance (Right)
10
254
L
Maintenance
Clearance (Rear)
29
737
Unit with Blower Kit
Dimension
Inch mm
H
Maintenance
Clearance (Front)
24
610
J
Maintenance Clearance (Left) 24
610
K
Maintenance
Clearance (Right)
24
610
L
Maintenance
Clearance (Rear)
36
915
P
M
Q
N
R
R
J
K
L
H
MAINTENANCE CLEARANCE
Dimension
Inch mm
M*
Front
22
558.8
N
Flue rear
2
51
P**
Left
8
204
Q**
Right
8
204
R
Flue Side
2
51
FLOOR PROTECTOR REQUIREMENTS
FLOOR PROTECTOR
The furnace must be placed on solid concrete, solid masonry, or when installed on a combustible
fl
oor, on a
fl
oor protector. The
fl
oor protector is required to provide heat, live ember, and ash protection and must be of a
non-combustible, continuous solid surface to protect against in
fi
ltration of live embers and ash. Floor protection
must have and R-Value of at least 1.03. Refer to
fl
oor protector manufacturer’s instructions for installation directions.
The
fl
oor protector or non combustible
fl
oor must extend under the furnace and beyond each side as shown below.