background image

N U M E R I C A L   O C / E F   P R O T E C T I O N   R E L AY                                                                                             AD R 1 4 1 C / 2 4 1 C  

 

             

 

 

ASHIDA Electronics Pvt. Ltd.      

Ref: Manual / ADR141C / 241C 

Issue: 04D 

Date : 10.07.2014   

Page

 4/86 

 
 
 

8.3.5 

Relay Setting 

32 

8.3.5.1 

To Set – Relay Setting 

32 

8.3.5.2 

To View – Relay  Setting 

35 

8.3.6 

Cold Load Settings  

36 

8.3.6.1 

To Set – Cold Load Setting 

36 

8.3.6.2 

To View – Cold Load Setting 

40 

8.3.7 

Relay/LED Configuration   

41 

8.3.7.1 

Bit Definition for Relay/LED Configuration   

41 

8.3.7.2 

To Set – Relay/LED Configuration   

44 

8.3.7.3 

To View – Relay/LED Configuration  

 

49 

8.3.8 

Trip Test

 

51 

8.3.8.1 

To View – Trip Test

 

51 

8.3.9 

Fault 1

 

52 

8.3.9.1 

To View – Fault 1 Data [Fault 2 to Fault 8]

 

52 

8.3.10 

Events Log 

 

53 

8.3.10.1 

To View – Error Log 

53 

8.3.11 

Error Log

 

53 

8.3.11.1 

To View – Error Log 

53 

8.3.12 

Status

 

54 

8.3.12.1 

To View – Status 

54 

8.3.13 

Date Time Setting 

55 

8.3.13.1 

To Set – Date Time setting  

55 

8.3.13.2 

To View – Date Time Setting 

56 

8.3.14 

Secondary Current

  

57 

8.3.14.1 

To View – Secondary Current  

57 

9.0 

Flow Chart   

58 

9.1 

Flow Chart – To View Primary Current   

58 

9.2 

Flow Chart – To Set / View General Settings  

59 

9.3 

Flow Chart – To Set / View Relay Settings 

60 

9.4 

Flow Chart – To Set / View Cold Load Settings 

61 

9.5 

Flow Chart – To Set / View Relay/LEDs Settings 

62 

9.6 

Flow Chart – To View Trip Test Settings 

63 

9.7 

Flow Chart – To View Fault 1  (Fault 2 – Fault 8)  

64 

9.8 

Flow Chart – To View Events Log Settings  

64 

 
 

Содержание ADR141C

Страница 1: ...UMERICAL OC EF PROTECTION RELAY ADR141C 241C ASHIDA Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 1 86 Numerical Over Current Earth Fault Protection Relay Type ADR141C 241...

Страница 2: ...this manual at any time and without notice All rights are reserved No part of this manual may be reproduce copied translated or transmitted in any form or by any means without the prior written permi...

Страница 3: ...11 6 Self Check Feature 11 7 Technical Details 12 7 1 Technical Specification 12 7 2 Type Test Detail 14 7 3 Cabinet Drawing 16 7 4 Block Diagram 17 8 Front Panel and Control 18 8 1 User s Interface...

Страница 4: ...8 3 9 1 To View Fault 1 Data Fault 2 to Fault 8 52 8 3 10 Events Log 53 8 3 10 1 To View Error Log 53 8 3 11 Error Log 53 8 3 11 1 To View Error Log 53 8 3 12 Status 54 8 3 12 1 To View Status 54 8 3...

Страница 5: ...67 10 Communication Only for ADR241C Relay 68 10 1 General 68 10 2 General Questions 69 10 3 Physical connection and link layer 70 10 4 Relay Talk System for downloading the data 71 10 5 ADR241C IED M...

Страница 6: ...d waveform generated electronics loco motive All these measure values are then used for different protection function such as IDMT DMT Over current protection Instantaneous Over current protection Ear...

Страница 7: ...Continuous monitoring of module s internal hardware and alarm generation in case of failure of any critical components 9 4 Digital Output contacts for local alarm as Trip 9 2 dedicated status input f...

Страница 8: ...resholds for phase earth over current can be selected with an Inverse Definite Minimum Time IDMT characteristic The time delay is calculated with a mathematical formula where t operation time a consta...

Страница 9: ...NUMERICAL OC EF PROTECTION RELAY ADR141C 241C ASHIDA Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 9 86...

Страница 10: ...not sufficient DC fail 9 When CB NO and CB NC both active or both inactive CB NO as well as CB NC are both close or open 9 Relay detects any internal hard ware Error B B TC CB NO CB NC To Relay CPU T...

Страница 11: ...re within the chip The controller check all the components which are outside of chip such as ADC Non volatile memory used for disturbance data and event non volatile memory used for relay setting real...

Страница 12: ...uty user assignable X Contact Rating Continuous 5A Make carry for 0 5 sec 30A Make carry for 3 sec 15A XI Opto Isolated input 1 for CB NO 1 for CB NC XII Thermal With stand for CT 20 x of rated for 3...

Страница 13: ...of 0 1Sec IP Settings 50 3000 in steps of 50 IP Delay 0 2 00 Sec in steps of 0 01Sec XVII Earth Fault Section 3Io 3Io Settings 10 250 in steps of 1 3Io Time Multiplier TMS x0 01 x1 00 in step of 0 01...

Страница 14: ...n 15ms Repetition rate 300ms Both polarities Ri 50 duration 1 min 5 Surge Immunity Test IEC 60255 22 5 IEC 61000 4 6 class 4 Differential Mode 2kV Common Mode 4kV 1 2 50uS 5 surges of each polarity 6...

Страница 15: ...Test IEC 60255 21 2 Class 1 1000 bumps of 10gn peak acceleration and 16ms pulse duration in each of the two opposite direction per axis as per IEC 60255 21 2 class 1 No of axes 3 19 Shock Withstand I...

Страница 16: ......

Страница 17: ......

Страница 18: ...dicates Relay OK Protection Healthy Red LED indicates Fault in following conditions 1 Problem in relay Hardware 2 Trip Circuit Fault 2 L2 PKP Red LED indicate Start of timer Self Reset SR Type 3 L3 FA...

Страница 19: ...rns to the main menu When the Left Arrow key is pressed than you are able to enter the setting which can be now modified in the Main Menu using Up Arrow key Down Arrow key When the Left Arrow key pres...

Страница 20: ...screen by pressing HW RESET LED RESET EDIT Simultaneously Password 0001 Use Inr Dec To Enter the previously set Password Press the LED Reset Key this will display the curser below the password digits...

Страница 21: ...ally return to General Settings OK This window will flash for moment The control will return to the main menu Password 0000 New Password To Change Password New Password Press the LED Reset Key this wi...

Страница 22: ...lowing sequences 1 Press HW RESET LED RESET EDIT and LEFT ARROW KEY this will initialize relay hardware 2 Release HW RESET LED RESET EDIT and keeping the left arrow key pressed till the following mess...

Страница 23: ...ry Current these are the Main Menus available in this relay Since the LCD Display consist only of 2 Lines the main menu list can be scrolled up or down by using the up arrow key or the down arrow key...

Страница 24: ...Trip Ckt BF Enable BF Delay and Frequency Press the down arrow key the relay will display as follows Relay Settings Password protected window for Relay Settings for setting IP Enable IP Range IP TMS...

Страница 25: ...t RL1 A RL1 B RL2 A RL2 B RL3 A RL3 B RL4 A RL4 B L1 Green A L1 Green B L1 Red A L1 Red B L2 Green A L2 Green B L2 Red A L2 Red B L3 Green A L3 Green B L3 Red A L3 Red B L4 Green A L4 Green B L4 Red A...

Страница 26: ...follows Fault 6 This menu is to view the fifth latest Fault data stored by the relay That is Trip Flags Instantaneous and Phase primary Current Trip Counter TC Fault Date Time Press the down arrow ke...

Страница 27: ...e actual load current in Secondary as per the CT Secondary selection Press the down arrow key the relay will display as follows Pri Current This menu is to view the actual load current in Primary as p...

Страница 28: ...to communicate with the SCADA computer Press the left arrow key the relay will display as follows CT Sec 5A 1 1A 2 5A By using the up arrow key or the down arrow key the CT Sec setting can be selected...

Страница 29: ...lay as follows Trip Ckt YES 01 YES 02 N0 By using the up arrow key or the down arrow key the Trip Ckt can be selected i e YES or NO If set YES then Trip Ckt Supervision is enabled and if set NO then i...

Страница 30: ...lay will save the changes and the following message is display Note If changes made are not to be saved press LED Reset or leave key pad untouched for 100 sec Frequency 50Hz Range 50 60Hz By using the...

Страница 31: ...etting done previously Press the right arrow key the relay will display as follows CT Sec 1Amp CT Primary 0100A This window will show General Setting done previously Press the right arrow key the rela...

Страница 32: ...01 YES 02 N0 By using the up arrow key or the down arrow key the desired IP Enable can be selected i e YES or NO If set YES then IP setting is enabled and if set NO then it will be disabled Press the...

Страница 33: ...rrow key the desired 3Io TMS can be set The setting range is from X0 01 1 00 in steps of 0 01 Press the left arrow key the relay will display as follows Ip Curve 006 Range C1 C6 By using the up arrow...

Страница 34: ...key or the down arrow key the desired 3Io Delay can be selected The setting range is from 0 to 2 00s in steps of 0 01s Press the left arrow key the relay will display as follows Ip C6 Delay 99 5 Rang...

Страница 35: ...y as follows IP Normal Inv 2 3Io Normal Inv 1 This window will show Relay setting done previously Press the right arrow key the relay will display as follows IP 200 t X1 00 IP 800 This window will sho...

Страница 36: ...will display as follows CL Enable YES 01 YES 02 N0 By using the up arrow key or the down arrow key the desired CL Enable can be selected i i e YES or NO If set YES then CL setting is enabled and if s...

Страница 37: ...he left arrow key the relay will display as follows Ip 001 Multiply by 50 By using the up arrow key or the down arrow key the desired Ip can be set The setting range is multiply of 50 in steps of 1 Pr...

Страница 38: ...0 2 00s By using the up arrow key or the down arrow key the desired Ip Delay can be selected The setting range is from 0 to 2 00s in steps of 0 01s Press the left arrow key the relay will display as...

Страница 39: ...C6 Delay can be selected Range is in between 0 1 99 9s in steps of 00 1s Press the left arrow key the relay will display as follows Save Settings Mode for save To Save any changes Press the left arrow...

Страница 40: ...e previously Press the right arrow key the relay will display as follows IP Enable YES IP Enable YES This window will show Cold Load setting done previously Press the right arrow key the relay will di...

Страница 41: ...digital input Binary 0 to Reset Bit Self Reset SR Assign Bit no 9 in Relay LED B as Binary input 0 to set selected function Self Reset Hand Reset HR Assign Bit no 9 in Relay LED B as Binary input 1 to...

Страница 42: ...nput CB NO Trip Circuit Supervision Digital input TC Fail Trip Circuit Supervision Faulty TC OK Trip Circuit Supervision OK Proth Trip Circuit Supervision and Internal Hardware OK Error Trip Circuit S...

Страница 43: ...want to set Relay 4 for BF SR then you set bit as follow i e RL2 A 0200 RL2 B 0000 Bit Posit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 A 3Io Trip B Trip Y Trip R Trip B SR HR Bit for A 0 0 0 0 0 0 0 0 1 1...

Страница 44: ...Green A 0000 L3 Green B 0000 L3 Red A 01FF L3 Red B 0200 L4 Green A 01FF L4 Green B 0000 Relay LED s config Password protected window for Relay LED confi Setting Password Load fact setting RL1 A RL1...

Страница 45: ...s the LED Reset Key it will come out of curser Note The entire detailed information regarding the Bit specification is given below in Bit Definitions Press the left arrow key the relay will display as...

Страница 46: ...play as follows L1 Green A 4000 This window shows the Relay LED configuration That is L1 Green A Press the left arrow key the relay will display as follows L1 Green B 0000 This window shows the Relay...

Страница 47: ...LED configuration That is L3 Green A Press the left arrow key the relay will display as follows L3 Green B 0000 This window shows the Relay LED configuration That is L3 Green B Press the left arrow k...

Страница 48: ...wing message is display Note If changes made are not to be saved press LED Reset or leave key pad untouched for 100Sec OK This window will flash for moment The control will return to the main menu L4...

Страница 49: ...as follows L1 Green A 0000 L1 Green B 0000 This window will show Relay config setting done previously Press the right arrow key the relay will display as follows RL2 A 01FF RL2 B 0000 This window will...

Страница 50: ...will display as follows L3 Green A 0000 L3 Green B 0000 This window will show Relay config setting done previously Press the right arrow key the relay will display as follows L4 Green A 0000 L4 Green...

Страница 51: ...ndow will show Trip flag Press the right arrow key the relay will display as follows R 0000 Y 0000 B 0000A This window will show primary fault current in R Y B Press the right arrow key the relay will...

Страница 52: ...t Date Time Press the right arrow key the relay will display as follows I I T This window will show Trip flag Press the right arrow key the relay will display as follows R 0000 Y 0000 B 0000A This win...

Страница 53: ...s Error Code 0000 This window will show Error Code detected by self supervision function of Relay Press the right arrow key the relay will display main menu Events Log This menu is to view the Events...

Страница 54: ...display as follows Status Status This menu is to view the Status of Digital Input Trip Circuit Supervision circuit breaker and H W S W version Press the right arrow key the relay will display as follo...

Страница 55: ...eps of 1 Press the left arrow key the relay will display as follows SET Mins 017 Range 0 59 By using the up arrow key or the down arrow key Minutes can be set The setting range is from 0 59 in steps o...

Страница 56: ...key the relay will display as follows Save Setting Mode For Save To save any changes Press the left arrow key the relay will save the change and the following message is display Note If changes made...

Страница 57: ...rent This menu is to view the actual secondary load current as per the CT Secondary selection Press the right arrow key the relay will display as follow R 00 00 Y 00 00 B 00 00 This window will show s...

Страница 58: ...LAY ADR141C 241C ASHIDA Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 58 86 9 0 FLOW CHART 9 1 Flow Chart To View Primary Current 3Io 0000A R 0000 Y 0000 B 0000A Primary C...

Страница 59: ...d 0000 Use Inr Dec CT Sec 001 1 1A 2 5A OK Unit Id 001 General Settings Unit ID 001 Test Block NO Trip Ckt NO Test Block Yes 01 Yes 02 N0 CT Primary 0100 Range 10 3000 BF Enable Yes 01 Yes 02 No Trip...

Страница 60: ...Relay Settings Ip Enable NO Ip Enable NO 3Io Enable No 3Io Enable No Ip Curve 002 Range C1 C6 3Io Enable Yes 01 YES 02 NO Ip Delay 0 01 Range 0 2 00s Ip 250 t x1 00 Ip 0100 Ip 250 Range 10 250 Passwo...

Страница 61: ...mer 0 50 Ip 250 t x1 00 Ip 1000 3Io Enable Yes 01 YES 02 NO 3Io 250 Range 10 250 Ip Curve 001 Range C1 C6 Ip Enable No Ip Enable No CL Timer 01 00 Range 0 1 10 0S Password 0000 Use Inr Dec Ip Enable Y...

Страница 62: ...RL3 A 0077 RL3 B 0000 RL4 A 0088 RL4 B 0000 Load Fact set Yes 01 Yes 02 No Password 0000 Use Inr Dec RL1 B 0000 RL2 A 01FF RL1 A 01FF L1 Red B 0000 L1 Red A 8000 L1 Green B 0000 L2 Red A 0000 L2 Gree...

Страница 63: ...Y ADR141C 241C ASHIDA Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 63 86 9 6 Flow Chart To View TRIP TEST Trip Test I I T R 0000 Y 0000 B 0000A 3Io 0000A Trip Count 0000...

Страница 64: ...View Faults Note Faults 2 to Fault 8 can be viewed respectively 9 8 Flow Chart To View Events Log Note Events 2 to Events 16 can be viewed respectively Fault 2 Fault 1 I I T R 0000 Y 0000 B 0000A 3Io...

Страница 65: ...nics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 65 86 9 9 Flow Chart To View Error Log Settings 9 10 Flow Chart To View Status Settings Error Log Error Code 0000 Status CB NO OFF C...

Страница 66: ...10 07 2014 Page 66 86 9 11 Flow Chart To Adjust To View Date Time Settings Password 000 Use INR DEC SET Mins 032 Range 0 59 SET Sec 020 Range 0 59 SET Hrs 04 Range 0 23 Date Time OK Time 04 32 20 Date...

Страница 67: ...OC EF PROTECTION RELAY ADR141C 241C ASHIDA Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 67 86 9 12 Flow Chart To View Secondary Current 3Io 00 00 Sec Current R 00 00 Y 00...

Страница 68: ...gh different status flags There are two types of status flags 1 Logical status such relay Pick up Relay operation setting change etc these are generated within relay 2 Similarly there is opto coupler...

Страница 69: ...ation with unlikely any distortion in the transmission and reception of data The major advantage of RS485 Port is it is multidrop i e upto 32 different devices can be connected to single port 10 2 6 W...

Страница 70: ...ted in the higher level protocol to detect the data corruption and resend the information at a later time 10 3 Physical connection and link layer Connection is available for IEC60870 5 103 through the...

Страница 71: ...ng is a brief step by step instruction to down load relay data Start Relay Talk program from program menu Following is the main screen of Relay talk system Fig 10 3 For success communication setting o...

Страница 72: ...After pressing Configuration button display will show following screen And follow steps Fig 10 4 Now check communication setting Fig 10 5 Adjust Proper Values of CT PT Primary and Secondary Press this...

Страница 73: ...HIDA Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 73 86 To finalise setting Press then Press finally Press This will return to main screen Default IDs settings Here we se...

Страница 74: ...YA V2 Series ADITYA2_2 Fig 10 7 Summary to ADR241C interface with relay talk system 1 Connect RS485 port on the back of ADR241C to PC through cable 2 Check that relay setting will match to software co...

Страница 75: ...e settings of the relay and also edit the settings of the relay 4 History Faults It will read all fault data i e last 5 fault which is also available on LCD display 5 Reset This is used to reset the r...

Страница 76: ...n from PC 12 General This is used to view Relay name Version and compatibility 10 5 1 Parameter Display Online Parameters along with their values in units are displayed along with the Date and Time st...

Страница 77: ...The control operation is used to control the relays parameters i e either to Reset the LEDs or to open the CB by TRIP command Fig 10 11 This window is not used in ADR241C This window is used to opera...

Страница 78: ...ts i e Trip Counter Date Time of the Faults Type of faults and present current values Fig 10 15 The windows Buttons functions are as follows Sr No Name Description 1 Fault Buffer To view the fault buf...

Страница 79: ...241C Issue 04D Date 10 07 2014 Page 79 86 10 7 Settings This window is to view and edit the parameter of the relay The setting are of two types General Settings and Bank Settings 10 7 1 General Settin...

Страница 80: ...CTION RELAY ADR141C 241C ASHIDA Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 80 86 10 7 2 Bank Settings This window is to view and edit the parameters in Bank settings of...

Страница 81: ...A Electronics Pvt Ltd Ref Manual ADR141C 241C Issue 04D Date 10 07 2014 Page 81 86 10 8 Event list This window shows the all events generated in the relay The following picture shows the auxiliary sta...

Страница 82: ...10 07 2014 Page 82 86 Following events occurred while relay is in Trip mode when local test Trip is occurred 1 General start pick up ON 2 General Trip ON 3 Test event ON Fig 10 20 When the relay is no...

Страница 83: ...perating Time Test For PHASE 3IO Ref Table Phase Trip at 100 and Phase TMS set at Maximum Position To be checked for 5 Amp Set Current at Delay in Sec C1 C2 C3 C4 C5 2N 10A Phase 10N 50A 20N 100A Phas...

Страница 84: ...1 5N of pickup setting Definite Time delay settings 0 5 10 0 Observed Delay Phase Observed Delay 3IO Tolerance 5 0 475 to 0 525 9 5 to 10 5 3 Breaker Fail LBB Time Test Set BF Delay mSecs 100 400 800...

Страница 85: ......

Страница 86: ...Description 01 06 03 2010 Original Version 02 26 08 2010 Communication Details added 03 03 09 2010 Test Report added 04 15 11 2010 Software Version Changed 04A 22 03 2011 IDMT Graph modified 04B 03 1...

Отзывы: