To avoid additional temperature increase, the devices should not be exposed to direct exposure to sunlight when in
operation!
EU design type test certification for the installed inductive proximity switches:
PTB 99 ATEX 2219 X
The integrated proximity switch is indicated on the type label/wiring diagram.
The surrounding housing has protection class IP65 as per EN 60529.
For use in explosion risk areas, the devices must be connected to certified intrinsically safe power circuits:
Max. voltage
U
max
= 16 V
Max. current
I
max
= 25 mA
Max. power
P
max
= 64 mW
Device data (per contact):
max. internal capacitance
Ci max = 30 nF
max. internal inductance
Li max
= 100 μH
The permitted limit values for U
i
, I
i
and P
i
for the intrinsically safe feed power circuits depend on the proximity switch
type. They are to be found in the respective EU design type test certifications.
For the non-electrical part of the devices, the standards EN 1127-1 (2007), EN 13463-1 (2009) und EN 13463-5
(2011) are applicable with regard to explosion protection. The relevant requirements of these standards are satisfied.
The documentation for the mechanical part has been filed with TÜV-Nord-Cert (see declaration of conformity).
Labeling:
II 2 G c IIC T6 and PTB 99 ATEX 2219 X
II 2 G Ex ia IIC T6 for the inductive proximity switch
Recommended isolating switch devices:
MTL 5011B
1-channel, for contacts/inductive proximity switch, operating voltage 20-35 VDC
MTL 5015
2-channel, for contacts/inductive proximity switch, operating voltage 20-35 VDC
KFA6-SR2-Ex1.W
1-channel, for contacts/inductive proximity switch, operating voltage 230 VAC
KFA6-SR2-Ex2.W
2-channel, for contacts/inductive proximity switch, operating voltage 230 VAC
4 Technical data
The detailed technical information can be found in the documents in the Appendix, Chapter 12.
5 Labeling on the device
The label with the serial number and type designation is located on the outside of the housing. The materials identifier
is encoded in the type designation.
5.1 Labeling on the device for explosion risk areas (ATEX)
The label with the marking for explosion risk areas is located on the outside of the housing.
Device without switching contacts:
###T5500####ATEX or ###T6500####ATEX
Содержание T5500
Страница 13: ...Page 13 of 21 12 2 Declaration of Conformity for device without switching contact ...
Страница 14: ...Page 14 of 21 12 3 Declaration of Conformity for device with inductive proximity switch ...
Страница 16: ...Page 16 of 21 ...
Страница 17: ...Page 17 of 21 ...
Страница 18: ...Page 18 of 21 ...
Страница 19: ...Page 19 of 21 ...
Страница 20: ...Page 20 of 21 ...
Страница 21: ...Page 21 of 21 ...