Step 
11 

 

S    bt

 To enter switch mode of momentary flow rate and integrated 

volume. There is manual mode (bt) or automatic mode (ti). 

 

For this application manual switch mode shall be selected. 

 

It only displays integrated volume when cover is removed and M 
button is pressed. Otherwise it only displays flow rate.  

 

Automatic setting time is selectable from 1 to 10 seconds cycle.  

 

Press UP or Down arrow until “bt” is displayed.  

 

Press and release M button to select and move to the next step. 
 

 

 
 
 

Step 

12 

 

 

C    0.0 

Loop check mode allows program and analog output 

verification with the transmitter pressurized or non-pressurized. It 
simulates the process and allows for troubleshooting. 

 

Press Up or Down arrow to change within transmitter range (0 to 88 
GPM of water). 

 

Press and release M button to return to the begin of program 

 

After verification press and hold M button for more three seconds to 
return to measuring mode. 

 

        
 
 
 

Function Verification: 
 

The GC52 

loop-check

 allows to verify program and analog output with the transmitter pressurized or 

non-pressurized. 
 

  

 

 

Once Step-11 is reached, the unit is in Loop-
check mode.  The system can be verified by 
increasing or decreasing the flow rate value (0 to 
88 GPM of water). 

 

Use the Up or down arrow and observe the 
display segments get brighter as the flow rate 
value increases. That, is an indication that the 
analog output and wiring are reacting properly.

 

 

 

 

 

 

 
 
 
 
 
 
 

Содержание GC52

Страница 1: ...C52 Differential Pressure Transducer Water Flow Rate and Volume Application This example demonstrates the use of GC52 differential pressure transmitter to measure and control flow rate in GPM Also to...

Страница 2: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 2 of 8 Figure 2 GC52 Flow Rate Diagram Example Figure 3 GC52 Installation Example Installation Remove the lid from the transmitter by turning it c...

Страница 3: ...ow and integrated Volume Program Guidelines Below is an Illustration to program the transmitter in GPM and integrated volume in gallons as the arbitrary units Proceed to scale down the transducer rang...

Страница 4: ...play n rot Press and release M button to select and move to the next step Step 3 P 20 0 To enter the maximum differential pressure corresponding to the maximum flow rate 88 GPM This is the orifice pla...

Страница 5: ...next step Step 8 _ _ _ _ A 100 0 To enter span analog output reference corresponding to 20 mA The operational range is from 0 to 88 GPM of water Therefore 100 full span is selected as the span or 20 m...

Страница 6: ...p Step 12 C 0 0 Loop check mode allows program and analog output verification with the transmitter pressurized or non pressurized It simulates the process and allows for troubleshooting Press Up or Do...

Страница 7: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 7 of 8 Analog output terminal check When the front cover is removed the analog output check terminals CH and CH are visible at the upper part of...

Страница 8: ...g measurement mode or loop check see results below for reference Connect amp meter per manual instructions or figure above Press the Down arrow until 0 0 GPM is displayed or apply 0 IWC Verify amp met...

Отзывы: