F   0

 To enter filter selection (selections of 0,2,4,8, and 16 times).  

 

The filter function is used when pressure fluctuates to improve 
analog output and difficult to read display.  

 

Select the factory default filter F0. Since pressure fluctuation is not 
expected. 

 

 Press and release M button to select and move to the next step. 

 

 

 
 
 
 

Step 

 

 

n̅ rot

 To enter configuration mode. There are three pressure modes, 

linear, non-linear, and square root function.  

 

Select square root function to convert pressure into flow rate and to 
use arbitrary units. 

 

Press UP or Down arrow to display “n̅ rot”. 

 

Press and release M button to select and move to the next step. 

 

 

 
 
 
 

Step 

 

 

P̅   ̅20̅.0̅

 To enter the maximum differential pressure corresponding 

to the maximum flow rate (88 GPM). 

 

This is the orifice plate specification value. 

 

Press Up or Down arrow until 20.0 is displayed. That, is the 
maximum differential pressure corresponding to 88 GPM of water. 

 

Press and release M button to select and move to the next step. 
 

 

 

 
 
 
 

Step 

 
 

 

d    1

 To select the decimal point position. There are four decimal 

point selections (0,1, 2, and 3 digits).  

 

Press Up or Down arrow until 1 is display. For this application one 
digit after decimal point shall be used. 

 

Press and release M button to select and move to the next step. 
 

 

 

 
 
 
 

Step 

 _ _ _ _ 

 

d   88.0 

To enter the maximum arbitrary units 88 GPM of water 

corresponding to differential pressure of 20 IWC. 

 

Press Up or Down arrow until 88.0 is selected. That, is the 88 GPM of 
water corresponding to 20 IWC.  

 

Press and release M button to select and move to the next step. 

 

 

Содержание GC52

Страница 1: ...C52 Differential Pressure Transducer Water Flow Rate and Volume Application This example demonstrates the use of GC52 differential pressure transmitter to measure and control flow rate in GPM Also to...

Страница 2: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 2 of 8 Figure 2 GC52 Flow Rate Diagram Example Figure 3 GC52 Installation Example Installation Remove the lid from the transmitter by turning it c...

Страница 3: ...ow and integrated Volume Program Guidelines Below is an Illustration to program the transmitter in GPM and integrated volume in gallons as the arbitrary units Proceed to scale down the transducer rang...

Страница 4: ...play n rot Press and release M button to select and move to the next step Step 3 P 20 0 To enter the maximum differential pressure corresponding to the maximum flow rate 88 GPM This is the orifice pla...

Страница 5: ...next step Step 8 _ _ _ _ A 100 0 To enter span analog output reference corresponding to 20 mA The operational range is from 0 to 88 GPM of water Therefore 100 full span is selected as the span or 20 m...

Страница 6: ...p Step 12 C 0 0 Loop check mode allows program and analog output verification with the transmitter pressurized or non pressurized It simulates the process and allows for troubleshooting Press Up or Do...

Страница 7: ...com info ashcroft com 1 800 328 8258 Rev A 02 17 Page 7 of 8 Analog output terminal check When the front cover is removed the analog output check terminals CH and CH are visible at the upper part of...

Страница 8: ...g measurement mode or loop check see results below for reference Connect amp meter per manual instructions or figure above Press the Down arrow until 0 0 GPM is displayed or apply 0 IWC Verify amp met...

Отзывы: