VII. Precautions   

1. 

A detector can not share an address with other equipment in a single bus circuit, or else an 

address conflict may occur.   

2. 

Never  dismount  the  protective  cover  delivered  with  the  detector  too  early  after  the  field 

installation and before the use of the detector, or else the detector may be contaminated. 

3. 

It is not permitted to use open flames (such as lighters) to firing thermistor during alarm tests, so 

as to avoid damage to the detector. It is recommended to use a hot air gun and other heating 

equipment in a simulation alarm test.   

4. 

The protection area and quantity of the detectors should comply with relevant provisions  and 

regulations of the local codes 

VIII. Maintenance   

   

Warning:  Before  conducting  maintenance  for  a  detector,  inform  the  related  management 

department  that  the  monitoring  will  be  stopped  temporarily  when  the  system  maintenance. 

Meanwhile,  disable  the  logic  control  function  of  the  area  or  system  to  be  maintained  to  avoid 

unnecessary  alarm  linkage.  After  the  test,  inform  the  management  department  to  restore  the 

normal functions of the system. 

1. 

According to the requirements of local codes, each quarter, some special testing instruments should 

be used to test the detector’s operation and confirm the indication state of its indicators by batch and 

stage; for a detector that has been installed and used, It is recommended to have it maintained once 

every two years. 

2. 

If a detector fails due to a material defect or a manufacturing process defect under normal conditions 

of use in one year following the date of its delivery, we shall repair or replace it for free. However, the 

faults of the detector due to artificial damage, improper use, or authorized adjustment, reconstruction 

or disassembly are not covered in the guarantee and we shall assume no responsibilities for any the 

consequence thereby caused. 

3. 

We may provide paid repair service for products with any faults beyond the guarantee range. If you 

have such products that need repair, please contact us. When sending such a product to us for repair, 

you are expected to provide some important information about the product, such as the phenomenon 

and possible cause of the product fault, so that we can find out the cause of the fault in the shortest 

time  and  so  the  information  may  be  used  as  a  reference  in  our  future  product  development  and 

improvement. 

IX. Fault analysis and troubleshooting   

Fault   

Possible cause   

Troubleshooting method 

Remarks 

The  detector  can’t  be 

coded. 

The internal circuit is damaged. 

Send the detector back to the factory for 

repair. 

 

The  detector  can’t  be 

logged into normally.   

The detector has no address or has 

a coincident code. 

Recode the detector. 

 

The  detector  reports  a 

fault after login. 

The contact with the base is poor 

Inspect and reinstall the base. 

 

The internal circuit is damaged. 

Send the detector back to the factory for 

repair. 

 

The  detector  reports  a 

fire alarm after login. 

The internal circuit has failed. 

Send the detector back to the factory for 

repair. 

 

The 

detector 

can’t 

send  out  fire  alarm 
signal  during  an  alarm 
test. 

The internal circuit is damaged. 

Send the detector back to the factory for 

repair. 

 

 
 

 

 

Содержание AW-D302

Страница 1: ...m current no remote indicator 1 5mA has remote indicator 3 5mA 6 Work indication The red indicator will blink in the monitoring status or remain lit in the alarm status 7 Weight about 115g with the base 8 External dimensions diameter 100mm height 60mm with the base I Product overview AW D302 Addressable Heat Detector Detector hereunder is a mated product of the AW FP300 fire alarm control panel It...

Страница 2: ... machine AW FP300 fire alarm control panel IV Appearance and dimensions see Fig 1 Fig 1 unit mm V Use and engineering application 1 Fig 2 is the schematic diagram of the matched mounting base Fig 2 Definitions of terminals non polarity two wire system 1 Signal terminal L1 2 Negative of remote indicator 3 Signal terminal L2 4 Positive of remote indicator 2 Wiring method The detector is accessed thr...

Страница 3: ...ld respectively connect on terminals 2 and 4 as shown in Fig 4 Fig 4 4 Coding address As shown in Fig 5 detector is accessed via the detector mounting base on the coder non polarity connection is adopted for the terminals L1 and L2 set the coder with the coding function select the correct address number and press the RUN key to complete the address code setup Note See the User s Manual of the code...

Страница 4: ...tion via the mounting holes A and B shown in Fig 6 as instructed in the construction drawing and make sure the matched mounting base has been firmly installed 3 Use a coder to make the detector coded according to the detector address on the construction drawing 4 Disconnect the power supply of the fire alarm control panel and connect the detector correctly according to the construction drawing 5 T...

Страница 5: ...aintained once every two years 2 If a detector fails due to a material defect or a manufacturing process defect under normal conditions of use in one year following the date of its delivery we shall repair or replace it for free However the faults of the detector due to artificial damage improper use or authorized adjustment reconstruction or disassembly are not covered in the guarantee and we sha...