VI. Installation and debugging 

Determine the location, mounting distance and numbers for mounting the detectors in the protection area 
according to relevant provisions and regulations of the local codes.

 

A self-contained complete base is necessary during the installation of a detector. As shown in Fig.6, the 
model, the external dimensions, the mounting hole diameter and the mounting hole spacing of the base 
are DZ-912, 100mm

×

26.4mm (diameter

×

thickness), 4.5mm and 44.5mm

64.3mm respectively.   

 

 

  Fig.6(unit:mm) 

Wiring requirement:   

It is proper to use RVS twisted pairs with a section area of equal to or larger than 1.0mm

2

 for the signal 

buses L1 and L2.   

 

Specific installation and debugging methods: 

1. 

Make sure the type of the detector matches the type of the host machine of the fire alarm control 
panel; 

2. 

Use  two  M4  screws  to  fix  the  matched  mounting  base  on  the  designated  position  via  the 
mounting holes A and B shown in Fig.6 as instructed in the construction drawing and make sure 
the matched mounting base has been firmly installed.   

3. 

Use a coder to make the detector coded according to the detector address on the construction 
drawing. 

4. 

Disconnect the power supply of the fire alarm control panel and connect the detector correctly 
according to the construction drawing. 

5. 

The lower edge of the detector base raised position aligned with the groove position, and then 
the detector into the base, the detector clockwise until it locks into place the detector. 

6. 

After all the products are installed and checked, connect the power supply of the fire alarm control 
panel and conduct automatic login.   

7. 

when automatic login is success, the red indicator of the detector will blink once about every 12 
seconds, which suggests that the detector has begun to operate normally.   

8. 

Finally conduct an alarm test for the detector through some special tools or direct hot air gun 
blowing. After the detector gives a fire alarm, the indicator will remain lit and the fire alarm control 
panel will simultaneously give corresponding alarm prompt information. After the alarm test, reset 
the fire alarm control panel and restore to the monitoring status. 

 

Содержание AW-D302

Страница 1: ...m current no remote indicator 1 5mA has remote indicator 3 5mA 6 Work indication The red indicator will blink in the monitoring status or remain lit in the alarm status 7 Weight about 115g with the base 8 External dimensions diameter 100mm height 60mm with the base I Product overview AW D302 Addressable Heat Detector Detector hereunder is a mated product of the AW FP300 fire alarm control panel It...

Страница 2: ... machine AW FP300 fire alarm control panel IV Appearance and dimensions see Fig 1 Fig 1 unit mm V Use and engineering application 1 Fig 2 is the schematic diagram of the matched mounting base Fig 2 Definitions of terminals non polarity two wire system 1 Signal terminal L1 2 Negative of remote indicator 3 Signal terminal L2 4 Positive of remote indicator 2 Wiring method The detector is accessed thr...

Страница 3: ...ld respectively connect on terminals 2 and 4 as shown in Fig 4 Fig 4 4 Coding address As shown in Fig 5 detector is accessed via the detector mounting base on the coder non polarity connection is adopted for the terminals L1 and L2 set the coder with the coding function select the correct address number and press the RUN key to complete the address code setup Note See the User s Manual of the code...

Страница 4: ...tion via the mounting holes A and B shown in Fig 6 as instructed in the construction drawing and make sure the matched mounting base has been firmly installed 3 Use a coder to make the detector coded according to the detector address on the construction drawing 4 Disconnect the power supply of the fire alarm control panel and connect the detector correctly according to the construction drawing 5 T...

Страница 5: ...aintained once every two years 2 If a detector fails due to a material defect or a manufacturing process defect under normal conditions of use in one year following the date of its delivery we shall repair or replace it for free However the faults of the detector due to artificial damage improper use or authorized adjustment reconstruction or disassembly are not covered in the guarantee and we sha...

Отзывы: