DBT12 Operations Manual....
22
7.
TROUBLESHOOTING AND DIAGNOSTICS
7.1.
COMMON PROBLEMS
When encountering difficulty in achieving successful operation of the DBT12, there are some
problems which are easily identified and solved. The following list is not intended to be
exhaustive.
SYMPTOM
POSSIBLE CAUSE/SUGGESTED ACTION
Upon initial power-up, the unit does not
behave in accordance with the Section 6.1
description (no display or fan).
Ensure dock power is available. Check
pedestal and shore cord circuit breakers.
Have input power to the unit checked by a
qualified electrician.
The unit powers-up in accordance with the
Section 6.1 description, but does not close
contactors and output voltage and power.
Review the unit display for an input voltage
between 167-270VAC.
The unit trips to a POWER OFF state and
reports the message “FAULT: Latched
OFF, Recycle Power”
Review Section 0.
7.2.
SOFT-START INHIBIT
If the unit is turned off within approximately 5 seconds from the time it was turned on, at the
next power up the following screen is displayed. The soft-start inhibit timer will count down
from 60 seconds and the unit will then proceed with normal power up.
SOFT-START INHIBIT COUNTDOWN:59 seconds
If Converter Turn-On Problem Persists,
Please Contact ASEA Factory Service Rep