AC55LC-3, AC63LC-3, and AC75LC-3 Operations Manual....
32
6.1
POWER TURN-ON PROCEDURE, cont.
6.1.2 Systems Equipped With The Seamless Transfer Option, cont.
If the generator is supplying power to the ship, the SHIP’S POWER - GENERATOR LED (12A) is
lit, and the GENERATOR metering display indicates approximately the same voltage as the
CONVERTER metering display, then proceed by pressing the
SHIP’S POWER - CONVERTER
(9) button. In dual generator installations, the converter will determine the appropriate transfer
generator and the transfer will proceed. The converter will match the generator in voltage,
frequency, and phase. When the two power forms are matched, the converter will place itself
momentarily in parallel with the generator, and then open the generator circuit breaker removing the
generator from the distribution grid. The entire process may take up to 5 seconds to complete. The
generator can now be secured from operation.
If the generator is off-line as indicated by the SHIP’S POWER - GENERATOR LED (12A) being
off, the converter will immediately place itself on the ships distribution system, with no
synchronization period required, when the
CONVERTER
(9) button is pushed.
When attempting transfer from the converter to the generator and the generator is off, or if its voltage
is outside the allowed voltage or frequency limits, the transfer will be aborted.
When load has been transferred to the converter, monitor the converter load currents and voltages.
Ensure the load is within the system ratings as indicated by the STATUS display. Monitor the shore
power voltage and current levels with load applied to avoid tripping shore power breakers. Refer to
published rating curves for maximum current, kVA, and kW levels. Additional loading information
may be obtained on shore power and converter loading by selecting the desired source button (2, 4),
then pressing
F2
,
F3
, and
F4
(13). To return to the default metering display, press
F1
(13).
Содержание AC55LC-3
Страница 20: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 20 5 2 WATER LINE PLUMBING cont FIGURE 6 WATER LINE PLUMBING ...
Страница 42: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 42 This page intentionally left blank ...
Страница 58: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 58 8 DIAGNOSTICS cont FIGURE 12 STATUS BIT DEFINITIONS ...
Страница 62: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 62 11 MSDS SHEET COOLANT OIL ...
Страница 63: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 63 11 MSDS SHEET COOLANT OIL cont ...
Страница 64: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 64 11 MSDS SHEET COOLANT OIL cont ...
Страница 65: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 65 11 MSDS SHEET COOLANT OIL cont ...
Страница 66: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 66 11 MSDS SHEET COOLANT OIL cont ...
Страница 67: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 67 11 MSDS SHEET COOLANT OIL cont ...
Страница 68: ...AC55LC 3 AC63LC 3 and AC75LC 3 Operations Manual 68 11 MSDS SHEET COOLANT OIL cont ...