m. The device TVR Y, directly supplied by the instrument, it allows
to visualize the temperature measured by the probe Pr1 through a
2 ½ digit display.

SUPPLY

TVR Y

cable 10 m MAX.

For additional info, please have a look at the TVR Y instruction
manual.

4.7.3 - RS 485 SERIAL INTERFACE BY “TLCNV”

The instrument can be connected by a special cable to the

 TLCNV

device  (mod. C - TTL/RS485 interface), by means of which it is
possible to connect the regulator with a net to which other
instruments (regulators of PLC) are connected, all depending
typically on a personal computer used as plant supervisor. 
Using a personal computer it is possible to acquire all the function
information and to program all the instrument’s configuration
parameters. 
The software protocol adopted for the instrument is a MODBUS
RTU type, widely used in several PLC and supervision programs
available on the market (Y and Z series protocol manual is
available on request).
If the instrument is used with TLCNV program by the parameter

"t.Ad"

 the station Address.

Set a different number for each station, from 1 to 255.

Note: 

The baud-rate are fixed at 9600 baud.

TLCNV interface is directly supplied by the instrument.

SUPPLY

TLCNV

cable

6

5

4

8

7

9

ON

3

2

1

TX/RX

TTL

TLCNV

B

GND

A

RS 485

For additional info, please have a look at the TLCNV instruction
manual.

5 - PROGRAMMABLE PARAMETERS TABLE

Here below is a description of all the parameters available on the
instrument. Some of them may not   be present because depend
on the model/type of instrument.

0.0

-30.0 ÷ 30.0

Probe  Calibration

i.C1

7

2.0

oF ÷ 20.0

sec

Measurement filter

i.Ft

6

C1

C0 / F0 / C1 /

F1

Unit of measurement

 

and resolution

 

(decimal point)
C0 = °C with 1° res.

 

F0 = °F with 1° res.

 

C1 =

 

°C with 0

.

1° res.

 

F1 = °F with 0

.

1° res.

i.uP

5

nt

Pt / nt

Probes Type

i.SE

4

i. -

 

parameters relative to inputs

0.0

LS ÷ HS

Set Point

SP

3

99.9

LS ÷ 999

Maximum Set Point 

S.HS

2

-50.0

-99.9 ÷ HS

Minimum Set Point 

S.LS

1

S. - parameters relative to Set Point

Note

Def.

Range

Description

Par.

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Temperature Alarms
delay

A.At

24

1.0

0.0 ÷ 30.0

°C/°F

Temperature Alarms
Differential

A.Ad

23

oF

oF / -99.9 ÷

999 °C/°F

Low temperature
Alarm threshold

A.LA

22

oF

oF / -99.9 ÷

999 °C/°F

High temperature
Alarm threshold 

A.HA

21

1

1 / 2

(/ 3 / 4 / 5 / 6 /

7 / 8 = don’t

use)

Temperature alarms
Type:
1 = Absolute
2 =Relative to Set

A.Ay

20

A. - parameters relative to alarms

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Delay at power on

P.od

19

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Out delay between
switching-on

P.P3

18

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Out delay after switch
off

P.P2

17

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Out delay at switch on

P.P1

16

P. parameters relative to compressor protection and power

on delay

oF

oF - on - Lb

Defrost display Lock
oF= display free
on=  Lock on
temperature Pr1
before defrost
Lb= Lock on label
“dEF” (during
defrosting) and “PdF”
(during
post-defrosting)

d.dL

15

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Lenght of defrost cycle

d.dE

14

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Delay first defrost after
power-on
(oF = Defrost at
power-on)

d.Sd

13

oF

oF/ 0.01 ÷ 9.59

(hrs.min. ) ÷

99.5

(hrs.min.x10)

Defrosting interval

d.di

12

d. - parameters relative to defrosting control

C

H - C

Output operating mode
H= Heating
C= Cooling

r.HC

11

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Output deactivation
time for probe  error

r.t2

10

oF

oF/ 0.01 ÷ 9.59

(min.sec ) ÷  

99.5

(min.sec.x10)

Output activation time
for probe  error

r.t1

9

2.0

0.0 ÷ 30.0

°C/°F

Differential
(Hysteresis)

r.d

8

r. - parameters relative to temperature control

°C/°F

ASCON TECNOLOGIC - Z31- 

 

-OPERATING INSTRUCTIONS- Vr. 02 - 03/12 -  ISTR-MZ31-ENG02 -  PAG. 6

Advanced Thermoelectric       toll-free 1-866-665-5434      (603) 888-2467      [email protected]

oF

OFF

0.0

4

 °C

Содержание Z31

Страница 1: ...TALLATION AND USE 3 KEYBOARD LOCK FUNCTION 2 6 RESET PARAMETERS TO DEFAULT VALUE LEVEL 2 5 CUSTOMIZED MODE PARAMETER PROGRAMMING PARAMETERS PROGRAMMING LEVEL 2 4 PARAMETER PROTECTION USING THE PASSWOR...

Страница 2: ...identifies the first parameter Using the UP and DOWN keys the desired parameter can be selected and pressing the P key the display will alternately show the parameter code and its setting that can be...

Страница 3: ...nting Make a hole 71 x 29 mm and insert the instrument fixing it with the provided special brackets We recommend that the gasket is mounted in order to obtain the front protection degree as declared A...

Страница 4: ...r HC H SP off O N r HC H tim e r d SP Temp r d tim e r HC C O N O N ON ON O N off off off Temp Out Out In the event of probe error it is possible to set the instrument so that that the output continue...

Страница 5: ...arm thresholds set in parameters A HA maximum alarm and A LA minimum alarm and the relative differential A Ad Through the parameter A Ay it is possible to set the alarm thresholds A HA and A LA which...

Страница 6: ...nt Probes Type i SE 4 i parameters relative to inputs 0 0 LS HS Set Point SP 3 99 9 LS 999 Maximum Set Point S HS 2 50 0 99 9 HS Minimum Set Point S LS 1 S parameters relative to Set Point Note Def Ra...

Страница 7: ...t of a faulty instrument either within the period of warranty or further to its expiry please contact our sales department to obtain authorisation for sending the instrument to our company The faulty...

Страница 8: ...37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 7 5 INSTRUMENT ORDERING CODE Z31 instrument with mechanical keyboard Z31S instrument with Sensitive Touch keyboard a b c d e f g h ii jj...

Отзывы: