49
7 - Technical specification
Features
(at 25°C environmental temp.)
Description
Operational safety
Measure input
Detection of out of range, short circuit or sensor break with automatic
activation of the safety strategies and alerts on display
Control output
Safety value:
-100…100%
Parameters
Parameter and configuration data are stored in a non volatile memory for
an unlimited time
Access protection
Password to access the configuration and parameters data,
keypad lock, output lock
General
characteristics
Power supply
(PTC protected)
100...240Vac (-15...+10%) 50/60 Hz or
24Vac (-25...+12%), 50/60 Hz and
Power consumption 2.6W max.
24Vdc (-15...+25%)
Safety
Compliance to EN61010-1 (IEC 1010 – 1), installation class 2
(2.5kV) pollution class 2,
instrument class II
Electromagnetic
compatibility
Compliance to the CE standards
(see page 2)
Protection EN60529
(IEC 529)
IP65 front panel
Dimensions
1
/
16
DIN - 48 x 48, depth 120 mm, weight 130 g approx.
UL and cUL approval
File 176452