31
6 - Technical specification
Features
(at 25°C enviromental temp.)
Setpoint
OP4 PV retransmission
(option)
One shot Fuzzy-Tuning
with automatic selection
Serial comm.
(option)
Auxiliary Supply
Operational safety
General
characteristics
Description
Ramp up and down. User inhibited
Low limit
High limit
Galvanic isolation: 500 Vac/1 min
Resolution:
12bit (0.025%)
Accuracy:
0.1 %
The controller selects automatically the best
method according to the process conditions
Natural frequency method
Step method
Current output: 0/4…20mA 750
Ω
/15V max.
From low limit to the high range
From low range to the high limit
0.1…999.9 digit/min (OFF = 0)
RS485 isolated, Modbus/Jbus protocol, 1200, 2400, 4800, 9600 bit/s 2 wires
Electromagnetic
compatibility
Access protection
Power supply
Protection EN650529
Compliance to the CE standards for industrial system and equipment
Electric safety
IP20 terminal block
IP65 front panel
18Vdc ±20%, 30mA max. for an external transmitter supply
Password to access the configuration and parameters data
100...240Vac (-15...+10%) 50/60Hz or
24Vac (-25...+12%) 50/60Hz and
24Vdc (-15...+25%)
Power consumption
2.6W max.
Compliance to EN61010, installation class 2 (2.5kV) pollution class 2
Detection of out of range, short circuit or sensor break with automatic
activation of the safety strategies and alerts on display
Dimensions
Safety value:
0…100%.
(user enabled/disabled)
Parameter and configuration data are stored in a non volatile memory for
an unlimited time
Measure input
1
/
16
DIN - 48 x 48, depth 120 mm, weight 130 g approx.
Control output
Parameters
UL and cUL approvals
File 176452