Ascon Tecnologic - Y39 Line - Operating Instructions - Pag. 14
“P” - Compressor protection and power on delay parameters
Parameter
Description
Range
Default
40
P.P1
Output
ot
activation delay
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
41
P.P2
Delay after output
ot
switch off
oF/.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
42
P.P3
Minimum time between two output
ot
power on
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
43
P.od
Delay outputs activation at power on
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
“A” - Alarm parameters
Parameter
Description
Range
Default
44
A.Ay
Temperature alarms type
1
Absolute to
Pr1,
label (Hi-Lo);
2
Relative to
Pr1
, label (Hi-Lo);
3
Absolute to
Au,
label (Hi-Lo);
4
Relative to
Au
, label (Hi-Lo);
5
Absolute to
Pr1,
no label;
6
Relative to
Pr1
, no label;
7
Absolute to
Au
no label;
8
Relative to
Au
, no label.
1
45
A.HA
High temperature Alarm threshold
oF/-99.9 ÷ +999°C/°F
oF
46
A.LA
Low temperature Alarm threshold
oF/-99.9 ÷ +999°C/°F
oF
47
A.Ad
Temperature Alarms Differential
0 ÷ 30°C/°F
1.0
48
A.At
Temperature Alarms delay
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
49
A.tA
Alarm memory
oF/on
oF
50
A.PA
Temperature Alarms delay at power ON
oF/0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10)
2.00
51
A.dA
Temp. Alarms delay after defrost and continuous cycle
and unlock display delay after defrost
oF/0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10)
1.00
52
A.oA
Alarm delay with door open
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
3.00
“o” - Outputs and buzzer configuration parameters
Parameter
Description
Range
Default
53
o.o1
OUT1 function
oF
No function;
ot
Temp. Control (compressor);
dF Defrosting;
Fn Fan;
Au Auxiliary;
At
Silenceable alarm;
AL
Not silenceable Alarm;
An
Stored alarm;
on
On when instrument switched
on
.
ot
54
o.o2
OUT2 function
dF
55
o.o3
OUT3 function
Fn
56
o.bu
Buzzer function mode
oF Disable;
1
Active alarms only;
2
Key pressed only;
3
Active alarms and key pressed.
3
57
o.Fo
Function mode auxiliary output
oF
No Function;
1
Control output
ot
delayed;
2
Manual activation by key or digital input;
3
Light with eco mode (ON with
SP
, OFF with
SP2
);
4
Internal light (OFF with door closed and ON with
door opened).
oF
58
o.tu
Time relative to auxiliary output
oF/0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10)
oF
“t” - Keyboard parameters
Parameter
Description
Range
Default
59
t.UF
Function mode key
oF
No function;
1
Auxiliary output command;
2
Continuous cycle command;
3
Selection of active Set Point (+ light off-eco mode);
4
Switch on/off (Stand-by)
oF
60
t.Fb
Function mode key
oF
61
t.Lo
Keyboard lock function delay
oF/0.01 ÷ 9.59 (min.s) ÷ 30.0 (min.s x 10)
oF
62
t.PP
Access Password to parameter functions
oF/999
oF
63
t.AS
MODBUS address (serial communication)
0 ÷ 255
1