3.  INSTALLATION WARNINGS

3.1 

Mechanical mounting

The device, in an 80 x 80 mm plastic container, is designed 
for wall mounting using screws passing through the slotted 
holes on the case.

 

Install the instrument as far as possible from electromagnet-
ic sources as motors, power relay, relays, electrovalves, etc.;

 

Avoid to place the probe in places where are present cor-
rosive and polluting gases and to do so that the probe are 
installed in a ventilated position;

 

The signal cables of the device must be routed separately 
from the power cables.

D

D

Should be necessary to remove the protective cap, do 
not cause any mechanical stress to the sensor and 
absolutely avoid touching the Humidity sensor surface.

3.2 

Dimensions

 [mm]

3.2.1 

Mechanical dimensions

2.0 

79.6

121.8 

65.7 

79.6 

100.0 

2x Ø3.2 

50.5

79.6 

100.0 

3.2.2 

Dimensions of the mounting slotted holes

2

6

2

6

Ø 4

Ø 4

3.2.3 

Mounting holes

89.6 

2x Ø4.2 

3.3 

Electrical connections

3.3.1 

Vdc power supply

1 2 34

4

3

:

2

: Relative humidity output

1

: +V (12/24 Vdc)

NTC Temperature output

Connection example

1 2 34

NTC Temp. output
NTC Temp. output
RH Output
V+ (12/24 Vdc)

NTC NTC

12/24V+

AI

1 2 34

Controller 1

Humidity controller with

12/24Vdc power supply

Controller 2

Temperature controller

4.  OPERATING MODE

The controller(s) to which the probe is to be connected must 
be provided with a 4... 20 mA current input and an NTC input.
To have a correct measure indication is necessary to set;

 

The NTC probe for the temperature;

 

The lower and upper input limits for the relative humidity. 
These limits determine the values that the instrument must 
show when 4 mA (lower limit or start of scale) and when 20 mA 
(upper limit or full scale limit) circulates in the input circuit.

Consult the controller user manual to see for how these limits 
are to be set.

4.3.1 

Values to be set on the controller

 

Lower humidity measurement limit (4 mA): 

0%

;

 

Humidity measurement upper limit (20 mA): 

100%

;

 

Type of temperature input: 

NTC

.