Ascon Tecnologic - e33 - OPERATING INSTRUCTIONS - PAG. 16
Parameter
Description
Range
Def.
Note
58
APA
Temperature Alarms delay at power ON
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
2.00
59
AdA
Temperature Alarms delay and
unlock display delay after defrost
oF
Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
1.00
60
AoA
Open Door Alarm Delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
3.00
61
oo1
OUT1 function
oF
No function;
ot
Temperature control (compr.);
dF
Defrost;
Fn
Fans;
Au
Auxiliary;
At/-t
Silenceable alarm;
AL/-L
Not silenceable Alarm;
An/-n
Stored Alarm;
on
ON when the instrument is ON;
HE
Heating (Neutral zone control).
ot
62
oo2
OUT2 function
dF
63
oo3
OUT3 function
Fn
64
obu
Buzzer function mode
oF
Function disabled;
1
Active for alarms only;
2
Active for key pressed only;
3
Active for alarms and key pressed.
oF
65
oFo
Auxiliary output function
oF
Function disabled;
1
Control output
ot
delayed;
2
Manual activation by key or digital inpu;
3
Shop window light with Eco mode (ON with SP, OFF with SPE);
4
Internal light (OFF with door closed and ON with door opened).
oF
66
otu
Time relative to auxiliary output
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
67
tUF
/ Key Function
oF
No function;
1
Auxiliary output command;
2
Normal/Eco Mode selection;
3
Switch ON/Switch OFF (Stand-by);
4
Turbo cycle command.
oF
68
tFb
/Aux Key Function
oF
69
tLo
Keyboard lock function delay
oF
Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).
oF
70
tEd
Set Point visibility with
key fast procedure
0
None;
1
SP;
2
SPE;
3
SP and SPE;
4
Active SP;
5
SP and SPH;
6
SP, SPE and SPH.
4
71
tPP
Password to Access Parameter functions
oF
Function disabled;
001 ÷ 999.
oF