7. PROGRAMMABLE PARAMETERS TABLE
Here below is a description of all the parameters available on the instrument. Some of them may not be present, either due
to the fact they depend on the type of instrument or because they are automatically disabled as unnecessary.
Parameter
Description
Range
Def.
Note
1
SLS
Minimum Set Point
-99.9... HS
-50.0
2
SHS
Maximum Set Point
LS... 999
99.9
3
SP
Set Point
LS ÷ HS
0.0
4
SPE
Set Point Eco
SP ÷ SHS
0.0
5
SPH
Turbo Set Point (or indep. Heating Set Point, HC mode) SLS ÷ SP
0.0
6
iuP
Unit of measurement and resolution (decimal point)
C0
°C, resolution 1°;
F0
°F, resolution 1°;
C1
°C, resolution 0.1°;
F1
°F, resolution 0.1°.
C1
7
iFt
Measurement filter
oF
Not used;
0.1 ÷ 20.0 s
2.0
8
iC1
Pr1 Probe Calibration
-30.0 ÷ +30.0°C/°F
0.0
9
iC2
Pr2 Probe Calibration
-30.0 ÷ +30.0°C/°F
0.0
10
iC3
Pr3 Probe Calibration
-30.0 ÷ +30.0°C/°F
0.0
11
iCU
Display offset
-30.0 ÷ +30.0°C/°F
0.0
12
iP2
Input Pr2 usage
oF
Unused;
EP
Evaporator probe;
Au
Auxliary probe;
dG
Digital Input.
dG
13
iP3
Input Pr3 usage
dG
14
iFi
Function and logic functioning of the Digital Input
(adding the “-” minus sign the logic is inverted)
0
No function;
1
Open Door;
2
Open Door with Fan Lock;
3
Open Door with Fan and Output Lock;
4
External Alarm;
5
External alarm with control output disabling;
6
Normal/Eco select;
7
On/Stand by select;
8
Start a Turbo cycle;
9
Defrost cycle start;
10
Defrost cycle end.
0
15
iti
Digital Input Delay
oF
Disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
16
iEt
Eco Mode activation delay at Door closed
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
17
itt
Max. time functioning in Eco Mode
oF
Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
18
idS
Variable normally displayed
oF
Display not lit;
P1
Probe Pr1 measure;
P2
Probe Pr2 measure;
P3
Probe Pr3 measure;
Ec
Measure
Pr1
in Normal mode +
ECO
label when in ECO mode;
SP
Active Set Point.
P1
19
rd
Differential (Hysteresis)
0.0 ÷ 30.0°C/°F
2.0
20
rEd
Differential (Hysteresis) in ECO mode
0.0 ÷ 30.0°C/°F
2.0
21
rHd
Differential (Hysteresis) in Turbo mode or Heating in
HC mode
0.0 ÷ 30.0°C/°F
2.0
22
rt1
Output activation time for Pr1 probe error
oF
Disabled;
-1 ÷ -59 (s) 1 ÷ 99 (min).
oF
23
rt2
Output deactivation time for Pr1 probe error
oF
Disabled;
-1 ÷ -59 (s) 1 ÷ 99 (min).
oF
24
rHC
Output operating mode
H
Heating;
C
Cooling;
nr
Neutral zone;
HC
Neutral Zone with indep. Set Point;
C3
Cooling with3 autom. switch modes.
C
25
rtC
Lengh of Turbo cycle
oF
Function disabled;
-1 ÷ -59 (min) 1 ÷ 99 (h).
oF
26
dtE
Defrost stop temperature
-99.9 ÷ +999°C/°F
8.0
27
dtS
Defrost enable temperature
-99.9 ÷ +999°C/°F
2.0
28
dtF
Defrost start temperature
-99.9 ÷ +999°C/°F
-99.9