Chapter 3 -
CPU Setup
13
Gateway Address:
To set the Gateway Address of the device;
Server Address:
To set the Server Address of the device;
DHCP:
To enable or disable DHCP Client on the device;
Port:
To set the Port for the connection with OpenPCS;
Exit:
To exit this menu and return to the previous one.
To set items 2, 3, 4 and 5, the user must digit on the keyboard the menu item
number and press ENTER. The screen will then change, asking the user to “
insert
new value:
”. When the system displays the “
insert new value:
” message the user
can enter the new values in number and dot notation.
To set DHCP value select item 6 and set 0 to DISABLE or 1 to ENABLE. To set the
Port, select item 7 and enter the desired value.
WARNING
Please note that items 2, 4 and 5
MUST
have the same subnet in order to avoid communications
problems.
3-2-6
Serial Setup Menu
Figure 3.7 - Serial Setup Menu
Baudrate:
This choice allows the user to set the baud rate for the RS232 commu-
nications port. The correspondence between the baud rate and the
item number is specified in Table 3.3 - Serial Port Speed:
Table 3.3 - Serial Port Speed
Parity:
To set the parity for the RS232 communication port, according to Table
3.4 - Parity;
Table 3.4 - Parity
Stop Bit:
To set the number of stop bits for the RS232 communications. Valid val-
ues are1 or 2;
Exit:
To exit this menu and return to the previous one.
To change the value of an item, the user has to select the item number and press
ENTER. The screen will then change, asking the user to
“Insert new value:
”.
VALUE
0
1
2
3
4
5
Speed bps
2400 4800 9600 19200 38400 57600
VALUE
0
1
2
Parity
NONE
EVEN
ODD
SERIAL SETUP MENU
1. Baudrate: 2, (9600bps)
2. Parity: 0 (NO PARITY)
3. Stop Bit: 1
4. Exit
Enter Selection:
Ascon S.p.a.
SigmaPAC Control Unit CU-02
Device configuration
Содержание CU-02
Страница 1: ...sigmadue Control Unit CU 02 User Manual M U CPU CB CU 02 5 14 04 Cod J30 478 1A CU02 E...
Страница 26: ...Sigmadue sigmaPAC CU 02 User manual 20...
Страница 32: ...Sigmadue sigmaPAC CU 02 User manual 26...
Страница 44: ...Sigmadue sigmaPAC CU 02 User manual 38...
Страница 46: ...Sigmadue sigmaPAC CU 02 User manual 40...