Ascon Tecnologic - ATT1/ATT1-I - ENGINEERING MANUAL - PAG. 1
ATT1
SIGNAL TRANSMITTER
FOR ALL SENSOR TYPES
ATT1
not insulated model
ATT1-I
insulated model
Engineering manual
Cod.: ENG - Vr. 02 - 19/05 - ISTR-MATT1ENG02
ASCON TECNOLOGIC S.r.l.
Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY
TEL.: +39 0381 69871 - FAX: +39 0381 698730
http:\\www.ascontecnologic.com
e-mail: [email protected]
FOREWORD
D
D
This manual contains the information necessary for the
installation of the product, we therefore recommend that
the utmost attention is paid to the following instructions
and to save it.
This document is exclusive property of Ascon Tecnologic which
forbids any reproduction and disclosure, even in part, of the
document, unless expressly authorized. Ascon Tecnologic
reserves the right to make any formal or functional changes at
any moment and without any notice.
Ascon Tecnologic and its legal representatives do not assume
any responsibility for any damage to people, things or animals
deriving from violation, wrong or improper use or in any case not
in compliance with the instrument features.
D
D
Whenever a failure or a malfunction of the device
may cause dangerous situations for persons, thing
or animals, please remember that the plant must be
equipped with additional electromechanical devices
which will guarantee safety.
Disposal
The appliance (or the product) must be
disposed of separately in compliance
with the local standards in force on waste
disposal.
INSTRUMENT DESCRIPTION
General description
ATT1/ATT1-I is a signal transmitter (Not insulated/Insulated)
capable of accepting in input various types of sensors and
retransmitting their signals with a programmable range.
The transmitter accepts input signals from:
Pt100 Measuring range: -200... +800°C, type of connection:
2, 3, 4 wires, accuracy: 0.1% fs ±10 μA;
Pt1000 Measuring range: -200... +800°C, type of connection:
2 wires, accuracy: 0.1% fs ±10 μA;
Ni100 Measuring range: -60... +180°C, type of connection:
2, 3, 4 wires, accuracy: 0.5% fs ±10 μA;
TC B Measuring range: 40... 1820°C, the accuracy: 0.2% fs ±10 μA
(only in the range 900... 1800°C);
TC E Measuring range: -200... +940°C, accuracy: 0.2% fs ±10 μA;
TC J Measuring range: -200... +1200°C, accuracy: 0.2% fs ±10 μA;
TC K Measuring range: -200... +1340°C, accuracy: 0.2% fs ±10 μA;
TC N Measuring range: -200... +1280°C, accuracy: 0.2% fs ±10 μA;
TC R Measuring range: -40... +1760°C, accuracy: 0.2% fs ±10 μA
(only in the range 400... 1760°C);
TC S Measuring range: -40... +1760°C, accuracy: 0.2% fs ±10 μA
(only in the range 400... 1760°C);
TC T Measuring range: -200... +400°C, accuracy: 0.2% fs ±10 μA
(only in the range -100... +400°C);
mV
Measuring range: -10... +70 mV, accuracy: 0.1% fs;
Potentiometer 10... 400
Ω
type of connection: 2, 3, 4 wires;
accuracy: 0.1% fs ±10 μA;
Poteniometer 10... 4000
Ω
type of connection: 2 wires,
accuracy: 0.1% fs ±10 μA.
It transmits, on the output, 4... 20 mA current signals.
The transmitter can be programmed using an Android Smart-
phone equipped with the NFC functionalities (Near Field Commu-
nications) and the APP ATNfc (available, free of charge, on Google
store) or using a PC with the AFC1 transmitter and the ATNfcSoft
program (downloadable, free of charge, from our Internet site).
Instrument description
2
6
5
4
3
1
Vdc
+
Out
mA
A
B
B1
A1
Tc
NFC
-
+
PWR
7..30Vdc
1
3
4
2
6
7
5
1, 2
Power/Output terminals (2 wires transmitter);
3, 4, 5, 6 Input terminals;
7
Orange label: Not isolated transmitter (ATT1),
Blue label: Isolated trasmitter (ATT1-I).