background image

Ascon Tecnologic - ATT1/ATT1-I - ENGINEERING MANUAL - PAG. 1

ATT1

SIGNAL TRANSMITTER  

FOR ALL SENSOR TYPES

ATT1

not insulated model

ATT1-I

insulated model

Engineering manual 

Cod.: ENG - Vr. 02 - 19/05 - ISTR-MATT1ENG02

ASCON TECNOLOGIC S.r.l.

Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY

TEL.: +39 0381 69871 - FAX: +39 0381 698730

http:\\www.ascontecnologic.com
e-mail: [email protected]

FOREWORD

D

D

This manual contains the information necessary for the 

installation of the product, we therefore recommend that 

the utmost attention is paid to the following instructions 

and to save it.

This document is exclusive property of Ascon Tecnologic which 

forbids any reproduction and disclosure, even in part, of the 

document, unless expressly authorized.  Ascon Tecnologic 

reserves the right to make any formal or functional changes at 

any moment and without any notice.
Ascon Tecnologic and its legal representatives do not assume 

any responsibility for any damage to people, things or animals 

deriving from violation, wrong or improper use or in any case not 

in compliance with the instrument features.

D

D

Whenever a failure or a malfunction of the device 

may cause dangerous situations for persons, thing 

or animals, please remember that the plant must be 

equipped with additional electromechanical devices 

which will guarantee safety.

Disposal

The appliance (or the product) must be 

disposed of separately in compliance 

with the local standards in force on waste 

disposal.

INSTRUMENT DESCRIPTION

General description

ATT1/ATT1-I is a signal transmitter (Not insulated/Insulated) 

capable of accepting in input various types of sensors and 

retransmitting their signals with a programmable range.
The transmitter accepts input signals from:
Pt100  Measuring range: -200... +800°C, type of connection:  

2, 3, 4 wires, accuracy: 0.1% fs ±10 μA;

Pt1000 Measuring range: -200... +800°C, type of connection:  

2 wires, accuracy: 0.1% fs ±10 μA;

Ni100  Measuring range: -60... +180°C, type of connection:  

2, 3, 4 wires, accuracy: 0.5% fs ±10 μA;

TC B  Measuring range: 40... 1820°C, the accuracy: 0.2% fs ±10 μA 

(only in the range 900... 1800°C);

TC E  Measuring range: -200... +940°C, accuracy: 0.2% fs ±10 μA;
TC J  Measuring range: -200... +1200°C, accuracy: 0.2% fs ±10 μA;
TC K  Measuring range: -200... +1340°C, accuracy: 0.2% fs ±10 μA;
TC N  Measuring range: -200... +1280°C, accuracy: 0.2% fs ±10 μA;
TC R  Measuring range: -40... +1760°C, accuracy: 0.2% fs ±10 μA 

(only in the range 400... 1760°C);

TC S  Measuring range: -40... +1760°C, accuracy: 0.2% fs ±10 μA 

(only in the range 400... 1760°C);

TC T  Measuring range: -200... +400°C, accuracy: 0.2% fs ±10 μA 

(only in the range -100... +400°C);

mV 

Measuring range: -10... +70 mV, accuracy: 0.1% fs;

Potentiometer 10... 400 

Ω

 type of connection: 2, 3, 4 wires; 

accuracy: 0.1% fs ±10 μA;

Poteniometer 10... 4000 

Ω

 type of connection: 2 wires, 

accuracy: 0.1% fs ±10 μA.

It transmits, on the output, 4... 20 mA current signals.
The transmitter can be programmed using an Android Smart-

phone equipped with the NFC functionalities (Near Field Commu-

nications) and the APP ATNfc (available, free of charge, on Google 

store) or using a PC with the AFC1 transmitter and the ATNfcSoft 

program (downloadable, free of charge, from our Internet site).

Instrument description

2

6

5

4

3

1

Vdc

+

Out

mA

A

B

B1

A1

Tc

NFC

-

+

PWR

7..30Vdc

1

3

4

2

6

7

5

1, 2 

Power/Output terminals (2 wires transmitter);

3, 4, 5, 6  Input terminals;
7 

Orange label: Not isolated transmitter (ATT1), 

Blue label: Isolated trasmitter (ATT1-I).

Отзывы: